AMS Ground Safety Review II Sept. 2008 – KSC 1 AMS 02 –Thermal Control System Design Thermal control GSE at KSC.

Similar presentations


Presentation on theme: "AMS Ground Safety Review II Sept. 2008 – KSC 1 AMS 02 –Thermal Control System Design Thermal control GSE at KSC."— Presentation transcript:

1 AMS Ground Safety Review II Sept. 2008 – KSC 1 AMS 02 –Thermal Control System Design Thermal control GSE at KSC

2 AMS Ground Safety Review II Sept. 2008 – KSC 2 AMS 02 –Thermal Control System Design TCS – GSE scope AMS at KSC will be in flight configuration (radiators) The TCS GSE shall allow the correct detector operation during the ground integration. The only GSE to be used at KSC will be electrically powered fans of two kind, to provide forced convection cooling. Several fans will blow air towards specific AMS components in order to keep their temperature in the operative range.

3 AMS Ground Safety Review II Sept. 2008 – KSC 3 AMS 02 –Thermal Control System Design Elements to be cooled –Air cooling Electronic crates and XPDs –Main radiators (RAM and WAKE) mounted Cryocoolers (with LHP integrated, hence sunk to the zenith radiators) PDS (mounted on WAKE radiator) CAB (with LHP integrated, hence sunk to the wake radiator) All other subdetectors don’t need forced convection cooling, free convection being sufficient.

4 AMS Ground Safety Review II Sept. 2008 – KSC 4 AMS 02 –Thermal Control System Design Type A Fans Quantity12 Diameter> 0.45 m Flow Rate4100 m 3 /h Unit power (reference value)135 W Voltage110 V AC supply Frequency60 Hz

5 AMS Ground Safety Review II Sept. 2008 – KSC 5 AMS 02 –Thermal Control System Design Four fans will blow to the electronic units mounted on the Ram radiator, having their axis parallel to the radiator Four fans will blow to the electronic units mounted on the Wake radiator, having their axis parallel to the radiator Four fans will blow the Zenith Radiator, having their axis parallel to the 4 zenith radiator quadrants

6 AMS Ground Safety Review II Sept. 2008 – KSC 6 AMS 02 –Thermal Control System Design Fans on zenith radiators Main Radiator Wake Main Radiator Ram Wake

7 AMS Ground Safety Review II Sept. 2008 – KSC 7 AMS 02 –Thermal Control System Design Main Radiator Wake Main Radiator Ram Wake Fans on RAM radiator

8 AMS Ground Safety Review II Sept. 2008 – KSC 8 AMS 02 –Thermal Control System Design Main Radiator Wake Main Radiator Ram Wake Fans on WAKE radiator

9 AMS Ground Safety Review II Sept. 2008 – KSC 9 AMS 02 –Thermal Control System Design

10 AMS Ground Safety Review II Sept. 2008 – KSC 10 AMS 02 –Thermal Control System Design

11 AMS Ground Safety Review II Sept. 2008 – KSC 11 AMS 02 –Thermal Control System Design Type B Fans Quantity3 Diameter>0.18 m Flow Rate740 m 3 /h Unit power (reference value)50 W Voltage110 V AC supply Frequency60 Hz

12 AMS Ground Safety Review II Sept. 2008 – KSC 12 AMS 02 –Thermal Control System Design Type B fans usage One fan is dedicated to the PDS, and it shall work at the same time of the Wake radiator fans. The other two fans shall blow air to the CAB on two of its faces (wake and starboard).

13 AMS Ground Safety Review II Sept. 2008 – KSC 13 AMS 02 –Thermal Control System Design Type B fans location Main Radiator Wake Main Radiator Ram Wake

14 AMS Ground Safety Review II Sept. 2008 – KSC 14 AMS 02 –Thermal Control System Design Quality stamp on COTS All fans will be commercial off the shelf (COTS) and have the European “CE” quality symbol on it. The supplier of the fans is TBD.


Download ppt "AMS Ground Safety Review II Sept. 2008 – KSC 1 AMS 02 –Thermal Control System Design Thermal control GSE at KSC."