Presentation is loading. Please wait.

Presentation is loading. Please wait.

Grundfos CM, CME Pumps CM Pumps Horizontal multi-stage pumps

Similar presentations


Presentation on theme: "Grundfos CM, CME Pumps CM Pumps Horizontal multi-stage pumps"— Presentation transcript:

1 Grundfos CM, CME Pumps CM Pumps Horizontal multi-stage pumps
Utilize Grundfos ,otors Are replacing the CH, CHN, CHI pumps

2 CM(E) Pump Features Compact design ( about 30% smaller than the comparable CH & CHI pumps ) State-of-the-art shaft seal Rotation indicator included on 3-Phase pumps Low noise level E-coated cast iron components FPVs (Factory Product Variants) available

3 Third Party Testing Information for CM(E) Pumps
CM pumps are UL listed for use with water CME pumps are UL recognized CM / CME pumps are ANSI /NSF 61 Annex G certified

4 CM(E) Series Information
Horsepower: 3/4 HP – 10 HP RPM: 3,450 (nominal) Fluid temp: Up to 248 Degrees-F ( stainless steel construction ) Up to 145 Degrees-F ( cast iron construction ) Ambient temp: -4 Degrees-F through 131 Degrees-F ( depends on temperature of liquid ) Maximum WP: Up to 232 PSIG ( depends on temperature of liquid ) Motors: Grundfos – All motors are IP55 enclosure ( 3-Phase MLE motors have a NEMA 3R environmental rating ) Connections: Threaded ( female NPT ) standard Tri-clamp, ANSI flange, DIN flange, JIS flange , victaulic or Rp as an option

5 Materials of Construction of CM(E) Pumps
Wetted parts: Mechanical seal faces: Elastomers: Cast iron / 304 SS – CM-A 304 SS – CM-I 316 SS – CM-G SC vs SC or carbon vs aluminum oxide EPDM FKM ( like Viton ) FFKM ( like Kalrez )

6 Hydraulic Coverage Range of CM Pumps
Complete performance range. - Unmatched.

7 Hydraulic Coverage Range of CME Pumps
Complete performance range. - Unmatched.

8 Efficiency Example

9 CM(E) Pump Motors Same motor for all material versions
All motors are IP55 enclosure ( 3-Phase MLE motors are rated at NEMA 3R ) 1/60/115/230 ML motors available through 1-1/2 HP ( no built-in motor protection ) 3/60/ / ML motors are available from 2 through 10 HP 5 HP and larger motors have built-in thermistors ( PTC ) 3 X Hz / 60 Hz Motors available ( not UL Listed ) Installation indicator on three phase motors – Checks motor rotation 1/60/ MLE motors available through 1-1/2 HP ( 50 Hz / 60 Hz ) 3/60/ MLE motors are available through 7-1/2 HP Same motor unit is used on both Stainless steel and cast iron variants Allows central motor production. Significant reduction of motor variants compared to CH/CHI The Δt is reduced significantly. This results in a higher limit in the ambient temperature. With a reduction of Δt with 10°C the lifetime of the motor can be doubled The installation indicator will indicate if the direction of rotation is correct on three phase motors. When the installation indicator is black the direction of rotation is right.

10 Drive End Motor Bearing Protection
O-ring Slinger The slinger is rotating. In case of a shaft seal leakage, the slinger will avoid the water penetrate into the motor. The bearing cover is designed with a labyrinth sealing and includes an O-ring sealing All motors are available with angular contact bearing if needed. Labyrinth sealing Slinger diverts liquid from the motor O-ring & labyrinth prevent liquid from penetrating the motor

11 Mechanical Seal Pusher type O-ring seal Carbon vs aluminium oxide
Silicon carbide vs silicon carbide No special tools for dismantling Improved dry running: The stationairy seal ring on the SIC/SIC seal is designed with ”wings” which avoids un-wanted rotation > No risk of damaging the o-ring. The stationary ring touches the motor flange > heat transfer will not damage the o-ring Service: Shaft seal can be dismantled for inspection with out special tools

12 Mechanical Seal Pressure & Temperature Ratings
If the liquid temperature is below -20°C (-4°F) the pump must be build specially for this purpose. ** CM and CME pumps for pumping liquids below –4 °F are available on request. *** AQQV above +194°F only in medias not containing water.

13 Noise Levels of CM(E) Pumps
Noise levels are for pumps operating at full speed Noise levels of CME pumps will be less when operating at reduced speeds

14 CM(E) Pump Standard Optional Piping Connections
Standard NPT ( female ) Connections: CM1 – CM3 are 1” X 1” NPT CM5 are 1” X 1-1/4” CM10 are 1-1/2” X 1-1/2” CM15 – CM25 are 2” X 2” Optional Piping Connections: Rp DIN flange Tri-Clamp ANSI flange JIS flange Victaulic Flange versions with oval holes covering DIN/JIS/ANSI standards in one base.

15 Installation Orientations of CM(E) Pumps

16 CM(E) Pump FPVs Undersized & oversized motors
PT100 or PTC motor sensors Angular contact motor bearings Low temperature pump – Down to -22 Degrees-F Discharge rotated to 3 O’clock or 9 O’colck Different piping connections Certificates Conformance Testing Etc. Terminal box mounted at 3 O’clock or 9 O’clock Frame sizes 71 and 80 only Surface treatments


Download ppt "Grundfos CM, CME Pumps CM Pumps Horizontal multi-stage pumps"