Presentation is loading. Please wait.

Presentation is loading. Please wait.

Objectives Finish DOAS Control Terminology Types of controllers

Similar presentations


Presentation on theme: "Objectives Finish DOAS Control Terminology Types of controllers"— Presentation transcript:

1 Objectives Finish DOAS Control Terminology Types of controllers
Differences Controls in the real world Problems Response time vs. stability

2 www.doas.psu.edu DOAS with multi-split systems
Fresh air?

3 DOAS fresh air configurations

4 DOAS fresh air configurations

5 Issues Related to DOAS Split of sensible and latent load
Selection of hydronic system Winter vs. summer operation Winter operation with DX systems (heat pump)

6 Sequence of operation for the control system design
Adiabatic humidifier CC HC SA OA mixing RA Define the sequence of operation for: WINTER operation and: - case when humidity is not controlled - case when humidity is precisely controlled Solution on the whiteboard

7 Economizer Fresh air volume flow rate control % fresh air TOA (hOA)
enthalpy 100% Fresh (outdoor) air TOA (hOA) Minimum for ventilation damper mixing Recirc. air T & RH sensors

8 Economizer – cooling regime
Example of SEQUENCE OF OERATIONS: If TOA < Tset-point open the fresh air damper the maximum position Then, if Tindoor air < Tset-point start closing the cooling coil valve If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-point Other variations are possible

9 Basic purpose of HVAC control
Daily, weekly, and seasonal swings make HVAC control challenging Highly unsteady-state environment Provide balance of reasonable comfort at minimum cost and energy Two distinct actions: 1) Switching/Enabling: Manage availability of plant according to schedule using timers. 2) Regulation: Match plant capacity to demand

10 Terminology Sensor Controller Controlled device
Measures quantity of interest Controller Interprets sensor data Controlled device Changes based on controller output Figure 2-13

11 Direct Indirect outdoor Closed Loop or Feedback
Open Loop or Feedforward

12 Set Point Control Point Error or Offset Desired sensor value
Current sensor value Error or Offset Difference between control point and set point

13 Two-Position Control Systems
Used in small, relatively simple systems Controlled device is on or off It is a switch, not a valve Good for devices that change slowly

14 Anticipator can be used to shorten response time
Control differential is also called deadband

15 Residential system - thermostat
~50 years old DDC thermostat Daily and weekly programming

16 Modulating Control Systems
Example: Heat exchanger control Modulating (Analog) control air water Cooling coil x (set point temperature)

17 Modulating Control Systems
Used in larger systems Output can be anywhere in operating range Three main types Proportional PI PID Position (x) fluid Electric (pneumatic) motor Vfluid = f(x) linear or exponential function Volume flow rate

18 The PID control algorithm
constants time e(t) – difference between set point and measured value Position (x) Proportional Integral Differential For our example of heating coil: Differential (how fast) Proportional (how much) Integral (for how long) Position of the valve

19 Proportional Controllers
x is controller output A is controller output with no error (often A=0) Kis proportional gain constant e = is error (offset)

20 Unstable system Stable system

21 Issues with P Controllers
Always have an offset But, require less tuning than other controllers Very appropriate for things that change slowly i.e. building internal temperature

22 Proportional + Integral (PI)
K/Ti is integral gain If controller is tuned properly, offset is reduced to zero Figure 2-18a

23

24 Issues with PI Controllers
Scheduling issues Require more tuning than for P But, no offset

25 Proportional + Integral + Derivative (PID)
Improvement over PI because of faster response and less deviation from offset Increases rate of error correction as errors get larger But HVAC controlled devices are too slow responding Requires setting three different gains

26 Ref: Kreider and Rabl.Figure 12.5

27 The control in HVAC system – only PI
Proportional Integral value Set point Proportional affect the slope Set point Integral affect the shape after the first “bump”

28 The Real World 50% of US buildings have control problems
90% tuning and optimization 10% faults 25% energy savings from correcting control problems Commissioning is critically important


Download ppt "Objectives Finish DOAS Control Terminology Types of controllers"

Similar presentations


Ads by Google