MNM Fatal 2006-23 Electrical Electrical October 12, 2006 (Minnesota) October 12, 2006 (Minnesota) Taconite Operation Taconite Operation Maintenance Coordinator.

Similar presentations


Presentation on theme: "MNM Fatal 2006-23 Electrical Electrical October 12, 2006 (Minnesota) October 12, 2006 (Minnesota) Taconite Operation Taconite Operation Maintenance Coordinator."— Presentation transcript:

1 MNM Fatal 2006-23 Electrical Electrical October 12, 2006 (Minnesota) October 12, 2006 (Minnesota) Taconite Operation Taconite Operation Maintenance Coordinator Maintenance Coordinator 24 years old 24 years old 16 months experience 16 months experience

2 Overview The victim was fatally injured when an electrical short occurred in a ball mill starter circuit. He was troubleshooting an electrical problem in the motor ladder start-up sequence for the No. 4 ball mill electrical motors. An air-magnetic circuit breaker that provided over current protection to the circuit failed, resulting in a sustained arc- flash.

3

4 Root Causes Management policies and controls were inadequate. There were no procedures requiring the circuit breakers to be examined and tested periodically to ensure these over-current protective devices functioned properly. Management policies and controls were inadequate. There were no procedures requiring the circuit breakers to be examined and tested periodically to ensure these over-current protective devices functioned properly. Management failed to recognize the potential hazard of not providing over- current protective devices on all electrical circuits. Management failed to recognize the potential hazard of not providing over- current protective devices on all electrical circuits.

5 Best Practices Before YOU perform any electrical work or troubleshooting: Before YOU perform any electrical work or troubleshooting: Periodically calibrate and maintain circuit protective devices to ensure they operate properly under fault conditions. Periodically calibrate and maintain circuit protective devices to ensure they operate properly under fault conditions. Wear the proper Personal Protective Equipment (PPE), such as fire resistant clothing, hoods, face shields and gloves, which are designed to protect against electrical arc flashes (as per NFPA 70E). Wear the proper Personal Protective Equipment (PPE), such as fire resistant clothing, hoods, face shields and gloves, which are designed to protect against electrical arc flashes (as per NFPA 70E). Stop, Look, Analyze, and Manage (SLAM) each task to identify all potential hazards before performing work. Stop, Look, Analyze, and Manage (SLAM) each task to identify all potential hazards before performing work.