Presentation is loading. Please wait.

Presentation is loading. Please wait.

Frankfurt (Germany), 6-9 June 2011 Vladimir Ćuk*, Sjef Cobben*, Wil L. Kling*, Roelof B. Timens** TU Eindhoven – The Netherlands, ** Universiteit Twente.

Similar presentations


Presentation on theme: "Frankfurt (Germany), 6-9 June 2011 Vladimir Ćuk*, Sjef Cobben*, Wil L. Kling*, Roelof B. Timens** TU Eindhoven – The Netherlands, ** Universiteit Twente."— Presentation transcript:

1 Frankfurt (Germany), 6-9 June 2011 Vladimir Ćuk*, Sjef Cobben*, Wil L. Kling*, Roelof B. Timens** TU Eindhoven – The Netherlands, ** Universiteit Twente – The Netherlands Presenter: Dr.ir. G.M.A. Vanalme TU Eindhoven The Netherlands Session: Power Quality and Electromagnetic Compatibility Paper 0580 ANALYSIS OF HARMONIC CURRENT INTERACTION IN AN INDUSTIAL PLANT

2 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Introduction  Current transients in the factory lighting system  A Variable Speed Drive (VSD) is causing voltage notches  Possible resonance?

3 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Lamp current in one phase

4 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Current in all three regimes

5 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Voltage in all three regimes

6 Frankfurt (Germany), 6-9 June 2011 Paper 0580 THDs over 20 ms periods

7 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Voltage harmonics

8 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Current harmonics Broadband distortion – not a resonance problem

9 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Calculated load impedance Low impedance at high orders causes high currents Cable inductance increases the impedance at the end of the plot

10 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Laboratory measurements Current with a clean voltage supply Peak current 3 A

11 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Current spectrum with a clean voltage 3 rd harmonic 5 th harmonic

12 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Simulated low distortion condition Peak current 4 A

13 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Simulated higher voltage distortion Peak current 9 A

14 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Simulated highest voltage distortion Peak current up to 20 A More oscillations than in the field – limited bandwidth of the source

15 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Harmonic fingerprint – 3 rd harmonic Current harmonics even with a clean voltage, but linear response to voltage harmonics!

16 Frankfurt (Germany), 6-9 June 2011 Paper 0580 Lamp impedance – lab. measurement Fitted curve C = 47.7 μF

17 Frankfurt (Germany), 6-9 June 2011  A parallel resonance is not being excited  Peaks are caused buy harmonic distortion – notch shape is not important, similar behavior with other shapes  These lamps create harmonics, but react linearly to voltage harmonics – parallel capacitance (compensation)  Solution – electrical separation Paper 0580 Conclusions