1 excom ® Remote I/O in Zone 1

2 excom ® excom ® One system for all requirements in Zone 1

3 excom ® Supply unit concept System connection Module overview Binary signal detection Analogue signal detection Housings Integration in Asset Management Systems Overall view of technological advantages Content

4 excom ® Supply unit concept Optimezed Power through the use of EEx-e input AC-supplying to the Backplane Design of the Backplane in EEx-m Galvanically isolated power supply of the modules with power restriction

5 excom ® Supply unit concept Power supply either 24 VDC or 115 / 230 VAC Fully redundancy Exchange in Zone 1 during operation 1 Supply unit is sufficient to supply a full equipped module rack

6 excom ® Supply unit concept 24 VDC 1 Supply unit 1 Supplyline 18-33 VDC

7 excom ® Supply unit concept 24 VDC 18-33 VDC 2 Supply unit 1 Supplyline

8 excom ® Supply unit concept 24 VDC 18-33 VDC 2 Supply unit 2 Supplyline 18-33 VDC

9 excom ® Supply unit concept 115 / 230VAC Same possibilities as with 24VDC Upgrade from an existing 24VDC- module rack possible

10 excom ® Supply unit concept mixed supply 115 / 230 VAC and 24 VDC 115 / 230 VAC 18-33 VDC

11 excom ® System connection Intrinsically safe Profibus DP Gateway Profibus DP-V1 Fully redundancy LED indication Hot swappable Configuration over Profibus HART ® -over-Profibus

12 excom ® System connection with copper cable DP SC12EX RS 485RS 485 iS Zone 1  max : 31 devices Control system

13 excom ® System connection with Fibre Optic Cable DP RS 485  max : 31 devices RS 485 iS OC11Ex/3G OC11Ex/2G LWL iS Zone 1 Control system

14 excom ® System connection with Fibre Optic Cable DP RS 485 Link cable Zone 1 LWL iS OC11Ex/3G 2 x OC11Ex/2G OC11Ex/2G RS 485 iS  max : 31 devices Control system

15 excom ® System connection Redundancy possibilities DP SC12EX Zone 1 1 Control system 1 Profibus Master Control system

16 excom ® System connection Redundancy possibilities DP SC12EX DP SC12EX Zone 1 1 Control system 2 Profibus Master Control system

17 excom ® Control system B System connection Redundancy possibilities DP SC12EX DP Zone 1 2 Control systems each 1 Profibus Master Control system A

18 excom ® Module overview AIH40Ex AIH41Ex Other devices in preparation DM80Ex DF20Ex AO40Ex AOH40Ex TI40Ex Modules for: NAMUR-sensors and actuators mechanical contacts temperature sensors, thermocouplers analogue input-/outputs signals HART® -signal transmission DI40Ex DO40Ex AI40Ex AI41Ex

19 excom ® Binary signal detection 8 channels For connection either of NAMUR-sensors and actuators or mechanical contacts Input- and Output channels configurable Designed for connecting low power valves Configurable on/off delay in the range of 2...100 ms possible for each channel In-/output module – DM80Ex

20 excom ® Binary signal detection Input module – DI40Ex 4 channels Galvanic isolation between the channels For connection either of NAMUR sensors or mechanical contacts Configurable on/off delay in the range of 2...100 ms possible for each channel

21 excom ® Binary signal detection Output module – DO40Ex 4 channels Galvanic isolation between the channels automatic adjustment of power in the range of: 10..24 VDC Typical connected loads: 24 V/6 mA 18 V/25 mA 15 V/35 mA 12 V/45 mA

22 excom ® Binary signal detection Frequency module – DF20Ex 2 channels Counter or Frequency input Up to 4 kHz 2 main inputs with 3 control in-/outputs Control inputsfor: - direction detection - reset input - release input

23 excom ® Analogue signal detection Input module – AIH40Ex 4 channels Integrated HART ® Controller For connection of 2-wire- transducer 14 Bit-resolution 0..21 mA is reproduced as a figure between 0 and 21000 Up to 8 HART ® Variables in cyclic communication

24 excom ® Analogue signal detection Input module – AIH41Ex 4 channels Integrated HART ® Controller For connection of 4-wire- transducer 14 Bit-resolution 0..21 mA is reproduced as a figure between 0 and 21000 Up to 8 HART ® Variables in cyclic communication

25 excom ® Analogue signal detection Input module – AI40Ex 4 channels Galvanic isolation between the channels For cennection of 2- and 4- wire-transducers 14 Bit-resolution 0..21 mA is reproduced as a figure between 0 and 21000

26 excom ® Analogue signal detection Input module – AI41Ex 4 channels Galvanic isolation between the channels For connection of 4-wire- transducer Current input 0..21mA Voltage input 0..10,5 V 14 Bit-resolution 0..21 mA is reproduced as a figure between 0 and 21000 0..10,5 V is reproduced as a figure between 0 and 10500

27 excom ® Analogue signal detection Output module – AOH40Ex 4 channels Integrated HART ® Controller For connection of 0/4..20 mA actuators 12 Bit-resolution 0..21 mA is reproduced as a figure between 0 and 21000 Up to 8 HART ® Variables in cyclic communication

28 excom ® Analogue signal detection Output module – AO40Ex 4 channels Galvanic isolation between the channels For connection of 0/4..20 mA actuators 13 Bit-resolution 0..21 mA is reproduced as a figure between 0 and 21000 At connected HART ® devices the parameterization will be done direct on the device

29 excom ® Analogue signal detection Temperature module – TI40Ex 4 channels Galvanic isolation between the channels Resistant- or thermocoupler measurement 16 Bit-resolution 0,1 K per Digit from 0 Kelvin upwards Channelwise external cold junction compensation or internal for all

30 excom ® Housings Using in Zone 1 Stainless steel cabinet with window Mounting rail for module rack 2 Cu-shield bus Flange plate with cable glands Mounting of 1 x MT18 or 2 x MT9 IP65

31 excom ® Housings with system approval

32 excom ® Housings with system approval Temperature calculation with Excel Download from www.turck.com Selection of the used modules Automatic calculation of the power consumption Selection of the max. ambient temperature

33 excom ® Housings with system approval

34 excom ® Housings with system approval

35 excom ® Housings customerized solutions

36 excom ® Housings customerized solutions

37 excom ® Emerson AMS ® Suite FDT/DTM Technology Integration in Asset Management Systems

38 excom ® DTM’s HART ® Communication with FDT/DTM

39 excom ® HART ® Communication with FDT/DTM As with PACTware ® Download from PACTware ® (www.turck.com) Download of the DTMs from the sites of the manufactors Installation of PACTware ® and DTMs Build up a project: → CommDTM → excom ® DTM → Geräte DTMs Start!

40 excom ® HART ® Communication with FDT/DTM

41 excom ® Integration in Emerson AMS ® suite

42 excom ® Overall view of technological advantages Non-restrictive Power redundancy in Zone 1 Gateway redundancy Status Indication via LED Hot Swap for all components in Zone 1 Minor volume dimensions

43 excom ® Overall view of technological advantages One binary output module for quite all intrinsic safe valves One temperature module für all current temperature sensors and thermocpouplers Continuous HART ® Ccmmunication

44 excom ® Thank you very much for your kind attention. For any further questions, do not hesitate to contact us: TURCK TEAM PROCESS AUTOMATION pa@turck.com