1 Pole Mounted Switch Disconnector NPS
630 A, up to 36 kV

2 NPS Pole Mounted Switch Disconnectors
Easy and smart integrations Adaptable to all customer/country building standards Modular concept Suitable for live working Flexible concept From the simplest of manually operated units to motorized and automated remotely controlled units Wide range of accessories Upgrading in switching performance

3 NPS Pole Mounted Switch Disconnectors
Enhanced performance and improved reliability Only insulators with the best materials are used Cycloaliphatic epoxy with over 30 years of field experience in more than 50 countries High quality silicone or porcelain insulators are also available Lightweight design with a limited number of parts guarantees a long lifetime and trouble-free operation

4 NPS as a Line Switch Disconnector

5 Crossarm installation
One of the most common building standards where the line switch disconnector is integrated on the same crossarm as the lines. Wooden poles are most often used for this type of installation.

6 Installation below live line
Some building styles and standards require a separate crossarm below the line crossarm. Sufficient clearances to the pole and between phases can be arranged by the flexible arrangement of phase elements.

7 Installation above live line
A typical installation example above the live line on a steel structure pole.

8 Vertical installation
Used for branching lines down to cables. The vertically installed switch disconnector is also used as a transformer switch disconnector.

9 Two pole mounting All installation examples are also available for two-pole mounting. Pole fitting accessories for various pole types are also available wooden poles concrete poles steel poles and structures

10 NPS for Transformer Switch Disconnector/ NPF fuse holder

11 Fuse holders The NPS switch disconnector can be equipped with several types of fuse holders. The vertically mounted NPS can be used as transformer switch disconnector. The breaking capacity of the whip (25/50 A) is enough for disconnecting a fully loaded distribution transformer up to 800/1600 kVA. NPS24B1-J2 and NPAC5

12 Fuse holders If the pole element is horizontally mounted the fuse holder for HRC fuses (6.3, 16, 25 A) or (SMIA-KR_) melting fuses can be easily integrated (up to 63 A) to the switch disconnector. The fuses are replaced using isolated rods from ground level. NPS24B1-J2, NPAC9-J2 and NPAF7-J2

13 Fuse holders NPS can be equipped with integrated earthing contact for open and earthed position. The separate fuse holder for HRC and SMIA-KR_ can also be equipped with surge arresters for one-, two-, or three-phase installation. NPS24B1-J2 NPAE5 NPF24B2

14 Fuse holders NPS can be equipped with a separate fuse holder for DIN-type fuses (CEF outdoor HRC fuses). IEC 282 ANSI 7.2 kV up to 160 A 12.0 kV up to 100 A 17.5 kV up to 100 A 24.0 kV up to 100 A 36.0 kV up to 40 A 25.5 kV A 25.8 kV A 38.0 kV A NPF24E5

15 Components for substation switch disconnectors

16 Accessories

17 Feeder Automation

18 One terminal with REC 523 can control up to 4 slave units.

19 DTU Operating Device for pole mounted switch disconnector type NPS or other types

20 DTU Operating Device The product range includes master and slave units
Can be equipped with third party electronics/IED Two different cabinet sizes Complete with batteries and chargers Up/down tube operation of disconnectors Stainless steel cabinet and mechanism Dust tight (IP55) to secure long lifetime of critical electrical components High torque, alternative 1.2 sec or 3 sec operating time Best possible materials used Over 30 years experience Operating voltages: 24, 48, 110, 220 VDC 110, 230 VAC

21 Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA
NPS Basic pole element Disconnector (IEC) No breaking capacity For disconnecting functions only Provides a safe isolating distance NPS24B1-WWJ2

22 Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA
NPS with 25 A breaking whip Limited purpose switch disconnector (IEC) Breaking 25 A/24 kV 40 A/12 kV For disconnecting functions only Provides a safe isolating distance NPS24B1-J2 NPS24B1-J3

23 Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA
NPS with 50 A breaking whip Limited purpose switch disconnector (IEC) Breaking 50 A/24 kV 80 A/12 kV With extended breaking capacity in rural areas and transformer loads. NPS24B1-K1J2

24 Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA
NPS with 250 A breaking chamber Limited purpose switch disconnector (IEC) Breaking 250 A/24 kV For main lines and subtations where larger breaking capacity is needed. NPS24B1-K4J2

25 Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA
NPS with K5 air making and breaking chamber General purpose switch disconnector (IEC) Maximum breaking and independent spring assisted making capacity 630 A/24 kV 8 kA/24 kV 12.5 kA/12 kV For main lines and substations where both breaking and making capacity is needed. Excellent for remote and auto sectionalizers. NPS24B1-K5J NPS24B1-K5J3 NPAC9-J3

26 Breaking devices on NPS24A for max. Ith/Idyn 20/50 kA
For overhead networks with BIL up to 150 kV. Silicone insulator J3. NPS24A2-J3 NPS24A2-K5J3 NPS24A2-K5J3 NPAC1-J3

27 Breaking devices on NPS36A for max. Ith/Idyn 21/52 kA
For overhead networks with BIL, up to 200 kV. Whip (16 A) or breaking chamber K3 (400 A) can be used ase breaking elements. Two alternative silicone insulators (J2 or J3). NPS36A2-J2 NPS36A2-K3J2 NPS36A2-K3J2 NPAC11-J2

28 Unique design The unique design on breaking whips and dry type breaking chambers eliminates the risk of oil leakage. Risk of oil eliminated Pollution risk for soil waters Safety risk in case of failed interruption No need to check oil level or compensate for possible leakages Risk of conventional air breaking chambers eliminated by protected breaking contacts Malfunctions due to dust, sand, ice and small animals Risk of terrain fires due to arcing

29 Manual operating mechanism
UEKE 5A1 Hook stick lever Hook stick operation mechanism for NPS24B_ models. Also available for mounting on lower level. UEKO 1A1 One hand grip operating mechanism for low end disconnectors

30 Manual operating mechanism
UEKE 3A1 Standard two hand grip operating mechanism for all NPS_ models. UEKE 3B1 Standard two hand grip operating mechanism for all NPS_ models with additional quick adjustment rod.

31 Manual operating mechanism
UEKE 2/1 With auxiliary contacts and heating element IP55. UEKE 6A1 Wire operation