1 Siemens tiastarTM Motor Control Center (MCC)
© Siemens All rights reserved.

2 UL Validated Testing of Arc-Resistant Motor Control Centers
tiastar ™ Arc Resistant MCCs UL Validated Testing of Arc-Resistant Motor Control Centers

3 Statistics tiastar ™ Arc Resistant MCCs ____________________________
Arc flashes are responsible for about 80 percent of electrical accidents in the U.S. each year1. In human terms, they are responsible for hundreds of deaths, thousands of serious injuries, and significant lost work time every year.2 ____________________________ Bureau of Labor Statistics Census of Fatal Occupational Injuries

4 Arc Flash tiastar ™ MCCs
Arc flashes are responsible for about 80 percent of electrical accidents in the U.S. each year. Personal Protective Equipment (PPE) can help avoid or reduce the severity of injuries Electrical equipment manufacturers have applied strengthened structural design to improve the safety potential of its Switchgears. Standards for performance-testing arc-resistant features defined for switchgear not MCCs. Manufacturers are using those standards for testing arc-resistant MCCs.

5 Prevention tiastar ™ Arc Resistant MCCs
The simplest and most effective measure to prevent an arc flash is to shut off all power to the equipment to be worked on. Siemens advises that individuals should only work on MCCs or other electrical equipment after all power to the equipment has been turned off. Arc flash prevention, safety training and PPE can only go so far in keeping workers out of harm’s way should an arc fault occur. Although PPE can provide protection from an arc flash, it still cannot protect an operator from being struck by enclosure doors blown off or open from an arc flash – or from fragments ejected from a disintegrating enclosure.

6 Arc Mitigation & Arc Resistant Equipment
tiastar ™ Arc Resistant MCCs Arc Mitigation & Arc Resistant Equipment Arc flash hazard mitigation and arc-resistant features. Designed to complement each other. Arc flash mitigation features: To keep the workers beyond the Arc Flash Boundary To shorten the arc flash duration Arc resistant equipment: To make sure that, in the event of an arc flash when the MCC’s doors are closed and latched, the equipment will contain the explosion, directing the arc blast, including its heat, plasma and pressure, away from workers.

7 Arc Flash Mitigation tiastar ™ MCCs
Arc Flash Hazard Mitigation Features available in tiastar MCC: Dynamic Arc Flash Sentry (DAS): This is a patented feature available in both Siemens MCCs and type WL Low Voltage Switchgear. DAS (alternate parameter settings) can be activated using a variety of activation methods (keyed switch, occupancy sensors, light curtains, etc.). Visual verification of DAS activation can be as simple as a pilot light or more elaborate such as horn and strobe light.

8 Maintenance Operation
tiastar ™ Arc Resistant MCCs Arc Flash Mitigation Normal Operation Parameter A Maintenance Operation Parameter B

9 tiastar ™ Arc Resistant MCCs Arc Flash Mitigation

10 tiastar ™ Arc Resistant MCCs
Siemens is the first manufacturer in the industry to have Underwriters Laboratories (UL) observe and validate the testing of its arc-resistant tiastarTM MCC model. The tiastar arc-resistant MCC successfully met the testing criteria required by the standards, and a qualified, independent third-party has confirmed this satisfactory performance.

11 The new tiastar ™ product family: tailor made feature sets focused on your industry
Base HD H2O Smart Your Industry Construction Commercial Offshore O&G Real estate Warehouses Municipal W/WW Process Industries Pharmaceuticals Why Tiastar Fastest shippingat lowest price point Smallest footprint with highest safety and performance Always-on reliability, industry-leading asset protection Always on, autonomous backup (failover), automatic process adjustments Arc-Resistant MCC 11 11

12 tiastar ™ Arc Resistant: Features that reach farther
Arc Flash Resistant Setting a new safety standard, tiastar is the first IEEE C compliant arc resistant motor control center with UL-witnessed testing. Decrease the risk of exposure to arc flash incidents to better protect personnel. 12 12

13 tiastar ™ Arc Resistant: Protecting your most valuable asset – your personnel
Reinforced enclosure and doors, with bolted rear covers: Increased hinge and latching locations combined with additional structural supports ensure sections will withstand, contain and re-direct internal arcing fault incident energy. Insulated vertical bus bar system: Isolates energized components preventing inadvertent contact and propagation of arcing faults. Automatic shutters in plug-in unit compartments: Isolates the plug-in location to prevent inadvertent access and lowers the risk to personnel. Internal venting system: The structure components are designed to vent and channel arc flash gasses to the back and out the top of the MCC. 13 13

14 Features tiastar ™ Arc Resistant MCCs
ANSI/IEEE Type 2 arc resistance to protect personnel at the front, back and sides of the equipment Reinforced enclosure to withstand pressure from internal arcing faults Internal venting system with pressure vents to channel the flow of arc fault gases and vent these gases out the top of the gear and away from personnel

15 Features tiastar ™ Arc Resistant MCCs
Reinforced front with doors with extra hinges and stronger latching systems Reinforced bolted rear covers

16 Features tiastar ™ Arc Resistant MCCs Insulated bus bar system
Automatic Shutters

17 Features tiastar ™ Arc Resistant MCCs
Arc flashes present a serious safety risk. The best protection is prevention by enforcing strict safety rules, mandate proper maintenance, and support that with regular safety training. Advances in technology have enabled electrical equipment the means to design and engineer much more arc flash safety features into their products and systems such as switchgear and MCCs. While standards continue to evolve, they inherently follow these kinds of innovations. It is important that the application testing of new safety features be validated by a qualified third-party like UL to ensure that the safety features work as intended and to prevent tragic accidents.

18 Smart Motor Management
© Siemens All rights reserved.

19 Smart MCCs What is a Smart MCC? A smart MCC can communicate via a network by incorporating intelligent devices to: control motors monitor motor operation monitor energy consumption monitor power quality monitor system operation communicate with a data network

20 Monitoring System Operation
Smart MCCs Monitoring System Operation Historically MCCs have played a limited roll in monitoring system operation. providing basic information to the PLC Example - start-stop motor control circuit PLC inputs are connected to normally open auxiliary contacts. M contact closes when the motor starter coil energizes. OL contact closes when an overload occurs. M OL

21 Run and Trip Input Signals
Smart MCCs Monitoring System Operation Historically basic information to the adding to the initial cost of the system Conventional Wiring for 1 motor starter (5 wires minimum) ON OFF FAULT Remote PLC /DCS Motor Starter Run and Trip Input Signals Motor RUN Output

22 Smart Motor Control Centers: What is the cost?
5 Motors – 25 Wires Remote PLC / DCS Motor Starter Here is a sample of some of the available data fields from SIMOCODE that directly improve system availablity. There are more fields then this. All of the set up parameters for SIMOCODE can also be monitored or changed as well Page 22 22

23 Smart Motor Control Centers: What is the cost?
25 Motors – 125 Wires PLC / DCS Motor Starter Here is a sample of some of the available data fields from SIMOCODE that directly improve system availablity. There are more fields then this. All of the set up parameters for SIMOCODE can also be monitored or changed as well Page 23 23

24 Smart Motor Control Centers: What is the cost?
PLC / DCS Motor Starter Here is a sample of some of the available data fields from SIMOCODE that directly improve system availablity. There are more fields then this. All of the set up parameters for SIMOCODE can also be monitored or changed as well Page 24 24

25 Smart MCCs Monitoring System Operation Historically basic information to the PLC adds to the initial cost of the system PLC wiring labor

26 Smart MCCs Monitoring System Operation Historically Increase system complexity Increase the number of wires Increase cost to gain limited information NOW Smart MCCs incorporate intelligent devices Providing expanded protection to motors Communicate information previously difficult to obtain or unavailable Motor Operation Power Conditions Status of External Events

27 tiastar ™ Smart MCCs Network Communication PROTOCOL Many different protocol exist PROFIBUS PROFINET Industrial Ethernet AS-Interface PROFIBUS DP is the primary network used internal to a tiastar SMART MCC PROFIBUS DP is an open network based on the IEC 61158/61784 standard.

28 Smart Motor Control Centers: What is the cost?
Motor Starter PLC / DCS Motor Starter Assuming 25 starters and 100’ between mcc units and the PLC/DCS: (25) SIMOCODEs (0) Starter aux. contacts (0) Overload alarm contacts (0) Digital PLC input points (0) Digital PLC output points 200 feet PROFIBUS cable and connectors Approximately $12500 Motor Starter Here is a sample of some of the available data fields from SIMOCODE that directly improve system availablity. There are more fields then this. All of the set up parameters for SIMOCODE can also be monitored or changed as well Motor Starter Motor Starter Page 28 28

29 Intelligent Components
tiastar ™ Smart MCCs Monitoring System Operation Intelligent Components Simocode • VFD • Power Meter WL CB •RVSS

30 tiastar ™ Smart MCCs SIMOCODE – Siemens Motor Management and Control Device Pro C The compact system for: Direct starters Reversing starters Pro V The variable system for: all control functions extendable additional functions

31 Monitoring System Operation
tiastar ™ Smart MCCs Monitoring System Operation Conventional Information Additional desirable information, such as …… UNDER LOAD ON OFF FAULT WARNING FAIL TO START JAM PHASE LOSS OVER TEMP AUTO CONTROL POWER ??? Typically not provided on most motors due to cost 31

32 Application: Electrical pump (up to 550 kW)
tiastar ™ Smart MCCs Application: Electrical pump (up to 550 kW) + Spannungserfassung Engineering Station Maintenance Station Power Management Operator Station Configuring of the application within SIMOCODE pro possible Application remains available during fails of the automation or communication system Profibus interface is the standardized interface between application and automation system SIMOCODE pro Basic unit Temperature module monitoring e.g. of the bearings, windings, medium, cooling fluid Analog module Monitoring e.g. of the filling level, filter dirt, flow rate, run dry protection, Pressure of the cooling fluid or gear oil Digital modules Monitoring/Status e.g. overflow, run dry protection, Check-back signals: Open, Closed, On, Off - Protection - Control - Interlockings - Monitoring - Communication Protection against overload, stall, phase failure, Monitoring of power, Cos-Phi motor idling, rotational direction Pump Flow rate Filter

33 PARTIAL LIST OF INFORMATION AVAILABLE
tiastar ™ Smart MCCs – Siemens Motor Management and Control Device PARTIAL LIST OF INFORMATION AVAILABLE MOTOR OPERATION POWER CONDITIONS STATUS OF EXTERNAL EVENTS OPERATIONAL STATUS PHASE CURRENTS DISCRETE INPUTS NUMBER OF STARTS PHASE VOLTAGES ANALOG INPUTS OPERATING TIME PHASE FAILURE RESULTS OF INTERNAL LOGIC STOP TIME PHASE IMBALANCE NUMBER OF FORWARD STARTS GROUND FAULT NUMBER OF REVERSE STARTS ENERGY CONSUMED MOTOR/BEARING TEMPERATURE REAL POWER NUMBER OF OVERLOAD TRIPS APPARENT POWER TIME TO TRIP POWER FACTOR LAST TRIP CURRENT COOL DOWN PERIOD

34 tiastar ™ Smart MCCs Process Visualization and Control integration to a larger system SIMATIC WinCC SCADA system Configurable to provide complete operating and monitoring functionality SIMATIC PCS 7 uniform data management, communication, and configuration capabilities open platform for solutions in batch, continuous, and hybrid process applications

35 Data Record Capability with Simocode ES software or S7300 PLC

36 Data Record Capability with S7400 PLC with PCS7
Limits -current limits Maintenance -Local/Remote Standard -Control Alarm - PCS7 Alarm logging Statistic Trend Faults Warnings Batch Control - PCS7 Batch Control

37 tiastar ™ Smart Start A truly plug-n-play option for tiastar Smart. Fully operational the moment you switch it on. Faster Start: Pre-programmed, pre-configured and pre-tested PLC and HMI combination reduces field engineering and commissioning times for quicker installation. Fast Access: Standardized PLC and HMI offer instant access and control of all the information in every PROFIBUS device from the moment the unit is switched on. Users can start, stop, test and verify all motor operations immediately after installation. SmartStart: Optional feature offers quick and easy start-up with pre-configured PLC and HMI. 37 37

38 Smart Start Elevation Configuration

39 Smart Start Main Screen, SIMOCODE View

40 Smart Start Main Screen, Variable Frequency Drive View

41 Smart Start Main Screen, RVSS View

42 Siemens tiastar ™ Motor Control Centers
Base HD H2O Smart Arc-Resistant Designed to meet your application requirements

43 The new tiastar ™ product family
Base Attractive Price Point & Lead Times HD Smallest Footprint Arc Resistant Increased Operational Safety H20 Integrated Drives Smart Diagnostics & Fast Start up 43

44 Totally Integrated Automation and Totally Integrated Power
Field instrumentation Process analyzers Process control system SIMATIC PCS 7 PLC (SIMATIC S7) HVAC MES (SIMATIC IT) Drives (SINAMICS) Medium Voltage Switchgear WL Low Voltage Switchgear TIASTAR Motor Control Centers ACCESS Power Monitoring Automation MES Manufacturing Execution Systems ERP Enterprise Resource Planning Medium Voltage Low Voltage TIP TIA >=110kV

45 Smart Motor Control Centers: What is the cost?
PLC / DCS Motor Starter Assuming 25 starters and 100’ average per wire length, the traditional wiring solution requires: (25) Starter aux. contacts (25) Overload alarm contacts (50) Digital PLC input points (25) Digital PLC output points 12,500 feet interconnect wire Approximately $12500 (components, wire, installation) Here is a sample of some of the available data fields from SIMOCODE that directly improve system availablity. There are more fields then this. All of the set up parameters for SIMOCODE can also be monitored or changed as well Page 45 45


Download ppt "Siemens tiastarTM Motor Control Center (MCC)"