Presentation is loading. Please wait.

Presentation is loading. Please wait.

Actuators By themselves, valves cannot control a process

Similar presentations


Presentation on theme: "Actuators By themselves, valves cannot control a process"— Presentation transcript:

1 Actuators By themselves, valves cannot control a process
Actuators By themselves, valves cannot control a process   Manual valves require an operator to position them to control a process variable. Valves that must be operated remotely and automatically require special devices to move them. These devices are called actuators. Actuators  may be  pneumatic, hydraulic, or electric solenoids or motors NH BEE4523 Chapter 3 : Actuator

2 Actuators 1 Electrical actuator 2 Pneumatic 3 Hydraulic 4 Fluid valve
NH BEE4523 Chapter 3 : Actuator

3 Electrical Actuator NH BEE4523 Chapter 3 : Actuator

4 Electrical Actuator 2 types of electrical actuators : Solenoid
Electrical Motors Dc Motor Ac Motor Stepping motor NH BEE4523 Chapter 3 : Actuator

5 Solenoid Solenoid : converts an electrical signal into mechanical motion, usually rectilinear Used when a large, sudden force must be applied to perform some job NH BEE4523 Chapter 3 : Actuator

6 Solenoid Consist of a coil n plunger (freestanding / spring loaded)
Coil will have voltage or current rating in dc or ac NH BEE4523 Chapter 3 : Actuator

7 Solenoid NH BEE4523 Chapter 3 : Actuator

8 Solenoid Solenoid used to change the gears of a two-position transmission Used SCR to activate solenoid coil NH BEE4523 Chapter 3 : Actuator

9 Electric Solenoid Actuators A typical electric solenoid actuator is shown in Figure 38.  It consists of a coil, armature, spring, and stem. The coil is connected to an external current supply.   The spring rests on the armature to force it downward.  The armature moves vertically inside the coil and transmits its motion through the stem to the valve. When current flows through the coil, a magnetic field forms around the coil.  The magnetic field attracts the NH BEE4523 Chapter 3 : Actuator

10 armature toward the center of the coil
armature toward the center of the coil.   As the armature moves upward, the spring collapses and the valve opens.  When the circuit is opened and current stops flowing to the coil, the magnetic field collapses. This allows the spring to expand and shut the valve. A major advantage of solenoid actuators is their quick operation.   Also, they are much easier to install    NH BEE4523 Chapter 3 : Actuator

11 than pneumatic or hydraulic actuators
  than pneumatic or hydraulic   actuators. However,   solenoid   actuators   have    two disadvantages. First, they have only two positions:   fully open and fully closed.   Second, they don’t produce much force, so they usually only operate relatively small valves. NH BEE4523 Chapter 3 : Actuator

12 Figure 38    Electric Solenoid Actuator
NH BEE4523 Chapter 3 : Actuator

13 Electrical Motors Electrical motors : accept electrical input and produce a continuous rotation as a result Motor styles and sizes vary as demands for rotational speed (rpm), starting torque, rotational torque, etc NH BEE4523 Chapter 3 : Actuator

14 DC Motor Rotation of dc motor : produced by the interaction of two constant magnetic fields Employs permanent magnet (PM) to form one of the magnetic fields 2nd magnetic field formed by current through coil of wire within PM NH BEE4523 Chapter 3 : Actuator

15 DC Motor Coil of wire (armature) : free to rotate
Coil is connected to current source through slip rings and brushes (commutator) Slip rings are split so that current reverses direction as the armature rotates NH BEE4523 Chapter 3 : Actuator

16 DC Motor NH BEE4523 Chapter 3 : Actuator

17 DC Motor NH BEE4523 Chapter 3 : Actuator

18 DC Motor NH BEE4523 Chapter 3 : Actuator

19 DC Motor Torque will drive the N armature from the N PM & the S armature from the S PM Armature rotate counterclockwise Rotation will continuous NH BEE4523 Chapter 3 : Actuator

20 DC Motor Field coil : coil used to produce static field
Many dc motors use electromagnet instead of PM to provide static field Field coil : coil used to produce static field Wound field motor : dc motor to produce static field Current can be provided by placing the coil in series or parallel (shunt) or else with two windings (compound) with the armature NH BEE4523 Chapter 3 : Actuator

21 Series field Large starting torque Difficult to speed control
Good for starting heavy, where speed control is not important NH BEE4523 Chapter 3 : Actuator

22 Shunt field Smaller starting torque Good speed control
Good for application where speed is to be controlled NH BEE4523 Chapter 3 : Actuator

23 Compound field The best features of both series & shunt
Large starting torque Good speed control NH BEE4523 Chapter 3 : Actuator

24 AC Motor Principle of ac motor : involves the interaction between 2 magnetic fields Both fields varying with the voltage Force between fields is a function of rotor angle and current phase NH BEE4523 Chapter 3 : Actuator

25 Synchronous ac motor AC voltage applied to field coils (stator)
Armature (rotor) is PM or dc electromagnet Rotor follows stator Speed of rotation: NH BEE4523 Chapter 3 : Actuator

26 Induction ac motor Rotor is neither PM nor dc electromagnet
Current induced from stator coils Ac field of stator produces magnetic field changing through closed loop of rotor NH BEE4523 Chapter 3 : Actuator

27 Stepping Motor Stepping motor : rotating machine that completes a full rotation by sequencing through a series of discrete rotational steps Rotational rate : determined by the number of steps per revolution and the rate at which the pulses are applied NH BEE4523 Chapter 3 : Actuator

28 Stepping motor 90° per step
Rotor is PM driven by set of electromagnets Switches : transistors, SCRs or TRIACs Switch sequencer will direct the switches through a sequence of positions as the pulses received NH BEE4523 Chapter 3 : Actuator

29 Stepping motor Pulse will change S2 from C to D
Poles of electromagnet reversing fields Pole N/S orientation is different Rotor repelled and attracted, moves to new position Next pulse will change S1 from A to B – same kind of pole reversal and rotation of rotor NH BEE4523 Chapter 3 : Actuator

30 Stepping motor Next pulse will change S2 from D to C– same kind of pole reversal and rotation of rotor Next pulse will change S1 from B to A– same kind of pole reversal and rotation of rotor, send back system to original position Continuous sequence as pulse come in NH BEE4523 Chapter 3 : Actuator

31 Example 1 A stepper motor has 10° per step and must rotate at 250 rpm. Calculate the required input pulse rate, in pulses per second. NH BEE4523 Chapter 3 : Actuator

32 Electric Motor Actuators Electric motor actuators vary widely in their design and applications.    Some electric motor actuators are designed to operate in only two positions (fully open or fully closed).  Other electric motors can be positioned between the two positions.   A typical electric motor actuator is shown in Figure 39.   Its major parts include an electric motor, clutch and gear box assembly, manual hand wheel, and stem connected to a valve. NH BEE4523 Chapter 3 : Actuator

33 The motor moves the stem through the gear assembly
The motor moves the stem through the gear assembly.   The motor reverses its rotation to either open or close the valve.  The clutch and clutch lever disconnects the electric motor from the gear assembly and allows the valve to be operated manually with the hand wheel. Most electric motor actuators are equipped with limit switches, torque limiters, or both.   Limit switches de-energize the electric motor when the valve has reached a specific position.   Torque Rev. 0 Page 59 IC-07 NH BEE4523 Chapter 3 : Actuator

34 Limiters de-energize the electric motor when the amount of turning force has reached a specified value. The  turning  force  normally  is  greatest  when  the  valve  reaches  the  fully  open  or  fully closed position.  This feature can also prevent damage to the actuator or valve if the valve binds in an intermediate position. NH BEE4523 Chapter 3 : Actuator

35 Figure 39 Electric Motor Actuator
* 07/16/96 Figure 39    Electric Motor Actuator NH BEE4523 Chapter 3 : Actuator *

36 Pneumatic NH BEE4523 Chapter 3 : Actuator

37 Pneumatic Pneumatic : based on concept of pressure as force per unit area Net force acts on diaphragm ; NH BEE4523 Chapter 3 : Actuator

38 Direct Pneumatic Condition in low signal-pressure state
Spring, S maintains diaphragm and connected control shaft in position Pressure on opposite side is maintained at atmospheric pressure by open hole, H NH BEE4523 Chapter 3 : Actuator

39 Direct Pneumatic Increasing control pressure applies force on diaphragm Forcing diaphragm and connected shaft down against spring force Maximum control pressure and travel of shaft NH BEE4523 Chapter 3 : Actuator

40 Pneumatic Shaft position is linearly related to applied control pressure Shaft position; NH BEE4523 Chapter 3 : Actuator

41 Reverse Pneumatic Moves shaft in opposite sense from direct actuator
Obeys same operating principle Shaft is pulled by application of control pressure NH BEE4523 Chapter 3 : Actuator

42 Example 2 A force of 400 N must be applied to open valve. Determine the diaphragm area if a control gauge pressure of 70 kPa (~10 psi) must provide this force. NH BEE4523 Chapter 3 : Actuator

43 Pneumatic Actuators A simplified diagram of a pneumatic  actuator is shown in figure  35. It operates by a combination of force created by air and spring force. The actuator positions a control valve  by transmitting its motion through the stem. A rubber diaphragm separates the actuator housing into two air chambers. The upper chamber receives supply air  through an opening in the top of the housing. NH BEE4523 Chapter 3 : Actuator

44 The bottom chamber contains a spring that forces the diaphragm against mechanical stops in the upper chamber.  Finally, a local indicator is connected to the stem to indicate the position of the valve. The position of the valve is controlled by varying supply air pressure in the upper chamber.  This results in a varying force on the top of the diaphragm.   Initially, with no supply air, the spring forces the diaphragm upward against the mechanical stops and holds the valve fully open.   As supply air pressure is increased NH BEE4523 Chapter 3 : Actuator

45 from zero, its force on top of the diaphragm begins to overcome the opposing force of the spring.  This causes the diaphragm to move downward and the control valve to close.With increasing supply air  pressure,  the  diaphragm  will  continue  to  move downward and compress the spring until the control valve is fully closed.  Conversely, if supply air pressure is decreased, the spring will begin to force the  diaphragm upward  and  open  the control valve.  Additionally, if supply pressure is held constant at NH BEE4523 Chapter 3 : Actuator

46 some value between zero and maximum, the valve will position at an intermediate position.    Therefore, the valve can be positioned anywhere between fully open and fully closed in response to changes in supply air pressure. A positioner is a device that regulates the supply air pressure to a pneumatic actuator.   It does this by comparing the actuator’s demanded position with the control valve’s actual position.  The demanded position is transmitted by a pneumatic or electrical control signal from a controller to the NH BEE4523 Chapter 3 : Actuator

47 positioner.  The pneumatic actuator in Figure 35 is shown in Figure 36 with a controller and positioner added. The controller generates an output signal that represents the demanded position.   This signal is sent to the positioner.   Externally, the positioner consists of an input connection for the control signal, a supply air input connection, a supply air output connection, a supply air vent connection, and a feedback linkage.   Internally, it contains an intricate network of electrical transducers, air lines, valves, linkages, and NH BEE4523 Chapter 3 : Actuator

48 necessary adjustments
necessary adjustments.   Other positioners may also provide controls for local valve positioning and gauges to indicate supply air pressure and control air pressure (for pneumatic controllers).  From an operator’s viewpoint, a description of complex internal workings of a positioner is not needed.   Therefore, this discussion will be limited to inputs to and outputs from the positioner. In Figure 36, the controller responds to a deviation of a controlled variable from set point and varies the control output signal accordingly to NH BEE4523 Chapter 3 : Actuator

49 correct the deviation. The control output signal is  sent  to  the  positioner,  which  responds  by  increasing  or decreasing the  supply  air  to  the actuator.   Positioning of the actuator and control valve is fed back to the positioner through the feedback linkage.  When  the  valve  has  reached  the  position  demanded  by  the  controller,  the positioner stops the change in supply air pressure and holds the valve at the new position.  This, in turn, corrects the controlled variable’s deviation from set point. NH BEE4523 Chapter 3 : Actuator

50 For example, as the control signal increases, a valve inside the positioner admits more supply air to the actuator.  As a result, the control valve moves downward.  The linkage transmits the valve position information back to the positioner.   This forms a small internal feedback loop for the actuator.   When the valve reaches the position that correlates to the control signal, the linkage stops supply air flow to the actuator.  This causes the actuator to stop.  On the other hand, if the control  signal  decreases,  another   NH BEE4523 Chapter 3 : Actuator

51 This causes the valve to move upward and open
  This causes the valve to move upward and open. When the valve has  opened to the proper position, the inside the positioner opens and allows  the  supply  air pressure to decrease by venting the supply air.positioner stops  venting  air  from  the actuator and stops movement of the control valve. An  important  safety  feature  is  provided  by  the  spring in an actuator. It can be designed to position a control valve in a safe position if a loss of supply air occurs. On a loss of supply air, the actuator in Figure 36 will NH BEE4523 Chapter 3 : Actuator

52 fail open.   This type of arrangement is referred to as "air-to-close, spring-to-open"  or  simply  "fail-open."   Some valves fail in the closed position.   This type of actuator is referred to as "air-to-open, spring-to-close" or "fail-closed."   This "fail-safe" concept is an important consideration in nuclear facility design NH BEE4523 Chapter 3 : Actuator

53 Figure 36 Pneumatic Actuator with Controller and Positioner
NH BEE4523 Chapter 3 : Actuator

54 Hydraulic NH BEE4523 Chapter 3 : Actuator

55 Hydraulic Hydraulic : used when large forces are required
Hydraulic pressure ; NH BEE4523 Chapter 3 : Actuator

56 Hydraulic Basic idea same as pneumatic
Except incompressible fluid used to provide pressure Pressure will be very large by adjusting area of forcing piston NH BEE4523 Chapter 3 : Actuator

57 Hydraulic allows the lifting of a heavy load with a small force NH
BEE4523 Chapter 3 : Actuator

58 Hydraulic Pressure is transferred equally throughout the liquid
Force on working piston; Working force in terms of applied force; NH BEE4523 Chapter 3 : Actuator

59 Automobile Hydraulic Lift
A hydraulic lift for automobiles is an example of a force multiplied by hydraulic press, based on Pascal's principle. The fluid in the small cylinder must be moved much further than the distance the car is lifted. NH BEE4523 Chapter 3 : Actuator

60 Pascal’s Principle NH BEE4523 Chapter 3 : Actuator

61 Example 3 Determine: The working force resulting from 200 N applied to a 1 cm radius forcing piston if the working piston has a radius of 6 cm The hydraulic pressure NH BEE4523 Chapter 3 : Actuator

62 Example 4 If the lift cylinder were 25 cm in diameter and the small cylinder were 1.25 cm in diameter, determine the force on the fluid in the small cylinder to lift a 6000 N car. NH BEE4523 Chapter 3 : Actuator

63 Hydraulic Actuators Pneumatic actuators are normally used to control processes requiring quick and accurate response, as they do not require a large amount of motive force.   However, when a large amount of force is required to operate a valve (for example, the main steam system valves), hydraulic actuators are normally used.   Although hydraulic actuators come in many designs, piston types are most common. NH BEE4523 Chapter 3 : Actuator

64 A typical piston-type hydraulic actuator is shown in Figure 37
A typical piston-type hydraulic actuator is shown in Figure 37.  It consists of a cylinder, piston, spring, hydraulic supply and returns line, and stem. The piston slides vertically inside the cylinder and separates the cylinder into two chambers. The    upper chamber contains the spring and the lower chamber contains hydraulic oil. The hydraulic supply and return line is connected to the lower chamber  and allows   hydraulic   fluid   to flow to and from the lower chamber of   the   actuator. The stem   transmits    the motion of the piston to a valve NH BEE4523 Chapter 3 : Actuator

65 Initially, with no hydraulic fluid pressure, the spring force holds the valve in the closed position. As fluid enters the lower chamber, pressure in the chamber increases.   This pressure results in a force on the bottom of the piston opposite  to the force  caused by the  spring. When  the hydraulic  force  is  greater  than  the  spring  force, the piston begins  to  move  upward,  the  spring compresses, and the  valve begins  to  open. As the hydraulic pressure  increases, the  valve continues to open.  Conversely, as hydraulic NH BEE4523 Chapter 3 : Actuator

66 oil is drained from the cylinder, the hydraulic force becomes less than the spring  force, the  piston moves downward, and the valve  closes.  By regulating  amount  of oil  supplied  or  drained  from  the  actuator, the  valve  can  be  positioned between fully open and fully closed The principles of operation of a hydraulic actuator are like those of the pneumatic actuator.  Each uses some motive force to overcome spring force to move the valve.   Also, hydraulic actuators can be designed to fail-open or fail-closed to provide a fail-safe feature. NH BEE4523 Chapter 3 : Actuator

67 Figure 37    Hydraulic Actuator
NH BEE4523 Chapter 3 : Actuator

68 Fluid valve NH BEE4523 Chapter 3 : Actuator

69 Control-valve principles
Flow rate in process control : volume per unit time If a given fluid is delivered through a pipe, the volume flow rate ; NH BEE4523 Chapter 3 : Actuator

70 Control-valve principles
To regulate flow rate of fluids through pipes Placing variable-size restriction in flow path Stem and plug move up and down Opening size between plug and seat changes, thus changing flow rate NH BEE4523 Chapter 3 : Actuator

71 Control-valve principles
There will be a drop in pressure and flow rate varies with square root of pressure drop The volume flow rate ; NH BEE4523 Chapter 3 : Actuator

72 Control-valve types Control-valve characteristic : different types of control valves depends on relationship between valve stem position and flow rate through valve NH BEE4523 Chapter 3 : Actuator

73 Control-valve types Control valve using pneumatic actuator
To drive stem and open or close valve NH BEE4523 Chapter 3 : Actuator

74 Control-valve types Types determined by shape of plug and seat
Stem and plug move with respect to seat Shape of plug determines the amount of actual opening valve NH BEE4523 Chapter 3 : Actuator

75 Control-valve types 1. Quick opening
Used predominantly for full ON/full OFF control applications Small motion of valve stem, max possible flow rate Allow 90% max flow rate, 30% travel of stem NH BEE4523 Chapter 3 : Actuator

76 Control-valve types 2. Linear
Flow rate varies linearly with stem position Ideal situation, valve determines pressure drop; NH BEE4523 Chapter 3 : Actuator

77 Control-valve types 3. Equal percentage
Percentage change in stem position produces equivalent change in flow-equal percentage Not shut off the flow completely in its limit of stem travel Rangeability; Flow rate; NH BEE4523 Chapter 3 : Actuator

78 Control-valve types Three types of control valves open differently as function of stem position NH BEE4523 Chapter 3 : Actuator

79 Control-valve sizing Correction factor (valve flow coefficient), Cv : allow selection of proper size of valve to accommodate flow rate Measured as the number of U.S. gallons of water per minute that flow through full open valve with pressure differential 1 lb per square inch Liquid flow rate (in U.S. gallons per minute); NH BEE4523 Chapter 3 : Actuator

80 Control-valve sizing Valve size (inches) Cv 0.3 3 1 14 1½ 35 2 55 108 4 174 6 400 8 725 Control-valve flow coefficients for different size valves NH BEE4523 Chapter 3 : Actuator

81 Example 5 Alcohol is pumped through a pipe of 10 cm diameter at 2 m/s flow velocity. Calculate the volume flow rate NH BEE4523 Chapter 3 : Actuator

82 Example 6 A pressure difference of 1.1 psi occurs across a constriction in a 5 cm diameter pipe. The constriction constant is m3/s/kPa1/2. Determine: (a) The flow rate in m3/s (b) The flow velocity in m/s NH BEE4523 Chapter 3 : Actuator

83 Example 7 An equal percentage valve has a maximum flow of 50 cm3/s and a minimum of 2 cm3/s. If the full travel is 3 cm, calculate the flow at a 1cm opening. NH BEE4523 Chapter 3 : Actuator

84 Example 8 Calculate: (a) The proper Cv for a valve that must allow 150 gal of ethyl alcohol per minute with a specific gravity of at maximum pressure of 50 psi (b) The required valve size NH BEE4523 Chapter 3 : Actuator

85 Summary The important information in this chapter is summarized below
Summary The important information in this chapter is summarized below. Valve Actuator Summary Pneumatic actuators  utilize  combined  air and  spring  forces  for  quick  accurate responses for almost any size valve with valve position ranging from 0-100%.   NH BEE4523 Chapter 3 : Actuator

86 Hydraulic actuators use fluid displacement to  move  a  piston  in  a  cylinder positioning  the  valve  as  needed  for  0-100%  fluid  flow. This type actuator is incorporated when a large amount of force is necessary to operate the valve.   NH BEE4523 Chapter 3 : Actuator

87 Solenoid actuators are  used  on  small  valves  and  employ an electromagnet  to move the stem which allows the valve to either be fully open or fully closed. Equipped with limit switches and/or torque limiters, the electric motor actuator has the capability of 0-100% control and has not only a motor but also a manual hand wheel, and a clutch and gearbox assembly. End of text. NH BEE4523 Chapter 3 : Actuator


Download ppt "Actuators By themselves, valves cannot control a process"

Similar presentations


Ads by Google