Presentation is loading. Please wait.

Presentation is loading. Please wait.

Self-Contained Breathing Apparatus

Similar presentations


Presentation on theme: "Self-Contained Breathing Apparatus"— Presentation transcript:

1 Self-Contained Breathing Apparatus
Basic SCBA Self-Contained Breathing Apparatus

2 Introduction Failure to use the SCBA properly can result in injury or death Respiratory system extremely vulnerable Fire departments must have a mask rule Wear and use SCBA in IDLH atmosphere SCBA necessary even during exterior defensive operations

3 Introduction (cont’d.)
Any inhaled toxic gas can directly cause disease of the lung tissue One in 12 firefighters is injured in the line of duty each year Smoke inhalation accounts for 18 percent of fatalities 21 percent of fireground injuries

4 Conditions Requiring Respiratory Protection
Oxygen deficiency High temperatures Smoke or by-products of combustion Toxic environments

5 Oxygen-Deficient Environments
Fire consumes oxygen Produces toxic gases Displace or dilute oxygen Oxygen concentrations below 19.5 percent are oxygen-deficient atmospheres Affects on the human body: Muscular impairment Mental confusion Death

6 Table 7-1 Effects of Hypoxia (Reduced Oxygen)

7 Elevated Temperatures
Respiratory system sensitive to temperature Air temperatures as low as 165°F can cause death within 1 minute Inhaling gases causes: Pulmonary edema Asphyxiation Long-term damage Temperatures in structure fire reach 1000°F One unprotected breath will cause death or severe damage to respiratory system

8 Smoke Unburned products of combustion, particles of carbon, tar, associated gases Large amounts of gases due to use of plastics Inhalation of small amounts may be fatal Four causes of damage by smoke: Asphyxiation Chemical irritation Chemical asphyxiation Any combination of these

9 Effects of Toxic Gases and Toxic Environments
Combustion produces toxic gases and irritants Affect short- and long-term health When combustion products combine may form lethal toxins Some common gases affect circulatory system Commercial occupancies may produce additional toxins Requires higher level of protection

10 Table 7-2 Toxic Gases Formed as Products of Combustion

11 Legal Requirements for Self-Contained Breathing Apparatus Use
Common sense: Use SCBA on every fire scene Start to finish Regulations developed for SCBA use Organizations established regulations and standards

12 Title 29 Code of Federal Regulations, Section 1910.134
Establishes standards for all entries into IDLH atmospheres April 1998 revision contains requirements related to interior structural firefighting Defines interior structural firefighting as IDLH Requires the use of SCBA Requirements for complete respiratory protection program Regular medical evaluation

13 NFPA 1500: Standard on Fire Department Occupational Safety and Health Program
Authority having jurisdiction (AHJ) must adopt the standard for the fire department Three additional standards: NFPA 1404: minimum requirements for protection programs NFPA 1981: design and performance criteria NFPA 1982: standards on PASS

14 Limitations of Self-Contained Breathing Apparatus
Understand limitations to use unit effectively and safely Limitations of the SCBA unit itself Size, weight, air supply Physiological limitations of the user

15 Figure 7-7 Continuous training with SCBA is one of the keys to effective firefighting operations.

16 SCBA Design and Size SCBA units add weight and bulk to PPE
SCBA cylinder consumed more quickly than length of time rated for: Limits advance into building More frequent crew rotations Other concerns: Restricted visibility Added weight and bulk Firefighter’s voice muffled Limited air quantity

17 Limitations of the SCBA User
Physical, mental, emotional state cause usage problems Physical limitations: added weight and bulk Physiological limitations Lack of confidence in SCBA unit Physical stress and anxiety Emotional conditions

18 Air Supply Management Air supply management
Must understand air consumption rates Individual point of no return Heads up display Various methods of breathing take experimentation on the part of the firefighter Use normal breaths and exhale slowly Never hold breath Controlled breathing is most efficient use of air

19 Figure 7-11 An example of an air consumption test.

20 Types of Self-Contained Breathing Apparatus
Two types of SCBA: Open-circuit SCBA Exhaled air is vented to outside atmosphere Most common Closed-circuit SCBA Exhaled air stays in the system for filtering, cleaning, circulation Sometimes used for specialized rescue incidents

21 Open-Circuit Self-Contained Breathing Apparatus
Designed and built in accordance with NIOSH and NFPA standards Four basic assembly components: Backpack and harness Cylinder Regulator Face piece assembly

22 Figure The four components of the open-circuit SCBA are the backpack/harness, cylinder, regulator, and face piece assemblies.

23 Head Harness Head Straps Nose Cone Voice Emitter Head Straps Regulator Adapter Port

24 Air Saver Switch or the Don/Doff Switch
Heads Up Display (HUD) Purge Valve (Emergency Bypass) Face Piece Lock Tab Mechanism Regulator Quick Disconnect with HUD Connector Air Saver Switch or the Don/Doff Switch

25 Closed-Circuit Self-Contained Breathing Apparatus
Not used for firefighting operations Most common use: hazardous materials incidents Air supplies range from 30 minutes to four hours Contain cylinder, filter system, regulator, and valves Clean and filter exhaled breath and add oxygen Air supply duration based on filtering/cleaning and oxygen capacity of unit

26 Open-Circuit Supplied Air Respirators
Open-circuit supplied air respirators (SARs) Also called airline respirators Remote air supply Commonly used for hazardous materials incidents Confined space rescues Long-duration of air supply, mobility, agility SCBA escape unit with 510 minutes

27 Inspection and Maintenance of Self-Contained Breathing Apparatus
Inspection on daily or regular basis Always follow manufacturer’s instructions Procedures in this chapter may differ from the recommendation

28 Daily Maintenance SCBA units should be checked daily
If used during emergency scene or training exercise should be serviced in same manner Follow 10-step inspection procedure

29 Monthly Maintenance Monthly SCBA check contains all elements of the daily check Adds several checks of mechanics of system Irregularities noted and repaired or pull SCBA from service

30 Annual and Biannual Maintenance
NIOSH and SCBA manufacturers require different functional tests of SCBA units Only manufacturer’s authorized or trained service personnel shall conduct these tests Firefighters should refer to the instructions for the SCBA units used

31 General Considerations
Operational safety checks must be performed Conducted on a daily or regular basis Immediately prior to using the SCBA unit If any component does not operate properly or is damaged, unit taken out of service immediately

32 Figure Firefighters must perform regular checks of SCBA to ensure the unit’s ability to operate.

33 Donning and Doffing Self-Contained Breathing Apparatus
Most common donning procedures: Seat-mounted position in the apparatus Side compartment on the apparatus Storage case Refer to manufacturer’s instructions

34 Storage Case Two methods to don unit:
“Over the head” “Coat” Choice is a matter of personal preference and training Refer to donning instructions for the particular SCBA unit

35 Seat-Mounted Apparatus
Allows for quick donning Unit readily available for regular inspection Three important safety requirements: Storing of the face piece Donning the unit while vehicle is moving Checking the cylinder gauge Never don while vehicle is in motion Check gauge before response or use the buddy system

36 Compartment or Side-Mounted Apparatus
Similar to seat-mounted position except firefighter is standing If mount bracket wrong height, use “coat” method Follow donning methods for particular mounting style

37 Donning the SCBA Face Piece
Most SCBA face pieces donned in a similar manner Difference in style of head straps, regulator location Essential to protect firefighter from toxic gases Firefighter must be fitted for the face piece to be used with a particular manufacturer’s SCBA Prohibit anything that may interfere with proper fit and seal of face piece Examples: eye glasses, beards, sideburns

38 Removing/Doffing the SCBA Unit
Generally to remove SCBA donning procedure is reversed If awaiting another assignment, remove face piece Allow normal breathing, conserve air Do not wear the mask without air flowing into it Regulator or face piece must not be contaminated After assignment complete, report to rehabilitation

39 Self-Contained Breathing Apparatus Operation and Emergency Procedures
Fire departments must establish respiratory protection programs Firefighters must be proficient in the safe use of SCBA Donning and doffing procedures Individual limitations Limitations of SCBA unit

40 Safe Use of SCBA Essential to firefighter survival
SCBA unit and protective equipment add weight and bulk Increased exertion and loss of body fluids Firefighters must be aware of symptoms of heat stress Be aware of own limitations and abilities

41 Operating in a Hostile Environment
General rules: Check in with accountability officer when entering or exiting Remain low, check the environment and conditions Never remove the face piece, maintain an awareness of location Ventilate as you advance if it does not spread fire Check for outside openings Maintain direct contact with other team members Never enter a hostile environment alone

42 Restricted Openings Probe tight spot with a tool
Be sure conditions on other side of obstacle are safe Shift pack to left side “Swim” through obstacle backwards “Forward dive” technique Do not remove SCBA unless absolutely necessary

43 Figure Firefighters may have to get beneath an obstacle to facilitate their escape, which may also require them to lower their profile.

44 Emergency Procedures Emergency procedures exist to assist a firefighter in safe escape from hazard Remain calm, rely on training and knowledge Never remove the face piece of the SCBA Standard emergency check procedure stressed If entangled, do not pull forward Use wire cutters to cut one wire at a time “Swim” method

45 Figure 7-32 Emergency procedures check.

46 Changing SCBA Cylinders
Cylinders changed after use, following local SOPs Cylinder 90 percent full could mean loss of 25 minutes of air supply Could make the difference in successful exit Follow 12-step replacement procedure Additional steps for two-person SCBA cylinder replacement

47 Servicing SCBA Cylinders
Cylinder serviced when below full Air source must be tested and certified All cylinders must have a current hydrostatic test date All fill stations must have fragmentation containment devices All manufacturer’s recommendations should be followed Fill rate may vary Cascade system Compressor/purifier system

48 (A) (B) Figure (A) A cascade system is one of the systems available to service SCBA cylinders. These may be fixed or mobile units. (B)

49 Lessons Learned SCBA unit is to a firefighter as a weapon is to a soldier No substitute for proper SCBA training Continued practice and advanced training necessary Prevent failures: thoroughly inspect and test SCBA function as often as possible Firefighters must be prepared to go in harm’s way Be knowledgeable and proficient in use of SCBA

50 Summary SCBA is one of the most important items of PPE that firefighters have available to them. An increase in safety regulations and improvements in design and construction of SCBA have greatly increased their safety and reliability. An SCBA has limitations and also increases the limitations and demands on the firefighter’s physical conditioning.

51 Summary The firefighter must be familiar and comfortable with the use, emergency procedures, inspection, and maintenance of an SCBA. The firefighter must be proficient in the proper and rapid procedures for donning and doffing SCBA.


Download ppt "Self-Contained Breathing Apparatus"

Similar presentations


Ads by Google