1 Introduction to Jan. 20, 2011 Vio Fan ICP DAS Co., Ltd. tDS-700 Series tGW-700 Series.

Similar presentations


Presentation on theme: "1 Introduction to Jan. 20, 2011 Vio Fan ICP DAS Co., Ltd. tDS-700 Series tGW-700 Series."— Presentation transcript:

1 1 Introduction to Jan. 20, 2011 Vio Fan ICP DAS Co., Ltd. tDS-700 Series tGW-700 Series

2 Features Comparison 2 Features\ Series PPDSPDS DStDStGW Virtual COMYes - ProgrammableYes --- PoEYes -- Modbus Gateway Yes --- Multi-clientYes -- RemarksIsolation for DS-715 Cost- effective

3 3 Specifications Comparison I-7188ENPDS-700tDS-700tGW-700 OSMiniOS7 --- CPU80188-40 MHz80186-80 MHz32-bit MCU 50MHz Ethernet10 Mbps10/100 Mbps EEPROM2 KB16 KB--- Frame Ground---Yes Total Models810+7+ Models with DI/DO250 Virtual COMYes --- Virtual I/O---Yes---

4 4 tDS/tGW-700 Common Features Tiny Device Server tDS-700: Tiny Device Servers Tiny Modbus Gateway tGW-700: Tiny Modbus

5 tDS/tGW-700 Common Features Contains a 32-bit MCU that efficiently handles network traffic 10/100 Base-TX Ethernet, RJ-45 x1 (Auto-negotiating, auto MDI/MDIX, LED Indicators) Includes redundant power inputs: PoE and DC jack Supports TCP, UDP, HTTP, DHCP, BOOTP and TFTP protocols Supports UDP responder for device discovery Allows automatically RS-485 direction control Supports pair-connection applications Allows easy firmware updates via the Ethernet Contains a tiny Web server for configuration Tiny form-factor and low power consumption RoHS compliant and no Halogen Made from fire retardant materials (UL94-V0 Level)

6 Redundant Power Inputs PoE ◆ DC Jack (IEEE 802.3af, Class 1) (+12 ~ 48 VDC )

7 Automatic MDI / MDI-X crossover

8 8 tDS-700 / tGW-700 Naming Conventions tDS-7 X Y tGW-7 X Y X: Number of Total Ports Y: Serial Ports Type 2: RS-232 4: RS-485 and RS-232 5: RS-422 / RS-485 8: RS-232 / 422 / 485

9 9 tDS-700 (tGW-700) Selection Guide tDS-712 tGW-712 tDS-722 tGW-722 tDS-732 tGW-732 tDS-715 tGW-715 tDS-725 tGW-725 tDS-735 tGW-735 tDS-718 tGW-718 COM 1 5-wire RS-232 5-wire RS-232 3-wire RS-232 2-wire RS-485 4-wire RS-422 2-wire RS-485 3-wire RS-232 2-wire RS-485 4-wire RS-422 COM 2 5-wire RS-232 3-wire RS-232 2-wire RS-485 COM 3 3-wire RS-232 2-wire RS-485 We are planning to have two new models as follows: tDS-724 (tGW-724) : RS-485 x1, RS-232 x1 (5-wire) tDS-734 (tGW-734) : RS-485 x1, RS-232 x2 (3-wire)

10 UDP Search Use "eSearch Utility“ or “VxComm Utility”, you can find the module quickly and configure the proper network settings.

11 Init Switch ModeFlash ProtectionFirmware UpdateConfiguration InitialNoYesFactory RunYesNoUser-Defined  If there are something wrong in network settings or other settings accidentally, you can make the switch is placed in the “Init mode”. After re-booting, all values can be restored to factory settings.

12 12 Firmware Update (1/2) Connect the tGW-700 to the same HUB or same sub-network as your PC. (For tDS-700, tGW-700, PETL-7000 and tPET Series) Right-click above the module name and choose the firmware file in “eSearch Utility”. Power-on reboot the module in initial mode to request the update.

13 Firmware Update (2/2) The tGW-700 has a built-in feature of flash protection that prohibits modification to the firmware in the flash. Before updating the firmware, we have to set “Init Switch” in “Init” state and then power-on reboot the tGW-700 and disable the flash protection. Since the flash becomes writable, we can update the firmware through the Ethernet network 。 The code (in the boot loader) used to update the firmware image is not part of the firmware it-self. Thus, users can update the firmware even the built-in one is broken or does not exist. If the firmware update fails, we just need to rerun the update procedures again.

14 14 tDS/tGW-700 Common Features Tiny Device Server tDS-700: Tiny Device Servers Tiny Modbus Gateway tGW-700: Tiny Modbus

15 tDS-700 Features Incorporates any RS-232/422/485 serial device in Ethernet Supports pair-connection (serial-bridge, serial-tunnel) applications Male DB-9 or terminal block connector for easy wiring Allows easy firmware updates via the Ethernet Contains a tiny Web server for configuration Cost-effective Device Servers 15

16 Virtual COM Basis Meter PLC 10/100 M Ethernet RS-485 VCOM6/7 Transparent tDS-725 Command/Data/Modbus/Anything Note: 1. In the virtual COM application, the command or data is being copied between the PC and tDS-700 module with no protocol convert. This allows most of the serial protocols can be used with the virtual COM. Transparent (with no protocol convert) Meter PLC RS-485

17 Virtual COM Application RFID Reader Meter NS-208PSE Ethernet Switch with PoE Meter PLC 10/100 M Ethernet RS-232 RS-485 VCOM5 VCOM6 VCOM7 VCOM8 … VCOM5 VCOM6 VCOM7 VCOM8 tDS-712 tDS-715 tDS-725 VxComm Driver PLC Note: 1. The max. COM port number in a PC is up to COM256. 2. The COM port is configured and mapped by using the VxComm Utility.

18 Direct TCP Socket Connection Meter PLC 10/100 M Ethernet RS-485 tDS-725 Send raw data via TCP socket. Raw data Note: 1. The serial ports of the tDS-700 can be also accessed via TCP socket connections. TCP port 10001 = COM1, TCP port 10002 = COM2, TCP port 10003 = COM3. 2. Users have to configure the baud rate and data format via web configuration first, else the serial ports may send garbage data. Transparent (with no protocol convert) Meter PLC RS-485 Port 10001 (COM1) Port 10002 (COM2)

19 Serial Port Pair-connection Basis PLC 2 uses 115200 bps tDS-715 uses 115200 bps tDS-715 uses 115200 bps Serial Port Pair-connection Through the Ethernet Port 1(RS-485) PLC 1 uses 115200 bps Port 1(RS-485) Note: 1.PLC 1 and PLC 2 can communicate with each other via the RS-485 port that has pair-connection link through the Ethernet. Virtual RS-485 bus through the pair-connection.

20 Pair-connection with Different Baud Rate PLC 2 uses 115200 bps tDS-715 uses 115200 bps tDS-725 uses 9600 bps Serial Port Pair-connection Through the Ethernet Port 1(RS-485) PLC 1 uses 9600 bps Port 1(RS-485) Note: 1.PLC 1 and PLC 2 can use different baud rate and different data format at the same time when using pair-connection. But please make sure that the tDS-700 has the same setting as local serial devices. 2.The pair-connection can be created by using same or different tDS-700 models. The pair-connection is working as port-to-port. Virtual RS-485 bus through the pair-connection.

21 Virtual RS-485 Network (base on pair-connection) PLC Meter RS-485 tDS-715 tDS-725 Meter tDS-725 tDS-735 RS-485 Serial Port Pair-connection Through the Ethernet Serial Port Pair-connection Through the Ethernet Port 1 Port 2 Port 1 Port 2 (RS-485) Port 1(RS-485) Port 1 Port 1 (RS-485) Port 2 Port 2 (RS-485) Serial Port Pair-connection Through the Ethernet PLC Note: When connecting several tDS-700 (RS-485 master) in RS-485 network, you should remove the pull-high/low resister in most of the tDS-700 modules, and make sure there is only one master in the RS-485 network. Port 3

22 22 tDS-700 Web Configuration : Login Default Settings: ItemFactory Default Settings IP 192.168.255.1 Gateway 192.168.0.1 Mask 255.255.0.0 PasswordAdmin

23 23 tDS-700 Web Configuration : Home Page

24 24 tDS-700 Web Configuration : Network Setting

25 25 tDS-700 Web Configuration : Port Setting

26 tDS-700 Web Configuration : IP Filter

27 27 tDS/tGW-700 Common Features Tiny Device Server tDS-700: Tiny Device Servers Tiny Modbus Gateway tGW-700: Tiny Modbus Gateway

28 tGW-700 Features Cost-effective Modbus/TCP to RTU/ASCII Gateway Supports Modbus/TCP master and slave Supports Modbus RTU/ASCII master and slave Supports pair-connection (serial-bridge, serial-tunnel) applications Tiny form-factor and low power consumption

29 Modbus Gateway Basis Meter PLC 10/100 M Ethernet RS-485 tGW-725 Modbus/TCP Modbus RTU or Modbus ASCII Note: 1. The tGW-700 act as Modbus/TCP to Modbus RTU/ASCII converter. The client program must use Modbus/TCP protocol. 2. The Modbus RTU or ASCII protocol, baud rate and data format used are depending on the serial devices, and are setting via web configuration. Port 502 (COM1) Meter PLC RS-485 Port 503 (COM2)

30 Modbus Gateway Application RFID Reader Meter NS-208PSE Ethernet Switch with PoE Meter PLC Meter PLC 10/100 M Ethernet RS-232 RS-485 Port 502 Port 503 tGW-712 with Modbus RTU tGW-715 with Modbus ASCII tGW-725 PLC Modbus/TCP Modbus RTU or ASCII Note: 1. The default TCP ports used in tGW-700 are 502 (COM1), 503 (COM2) and 504 (COM3). These TCP ports can be changed via the web configuration.

31 Serial Port Pair-connection Basis PLC 2 uses 115200 bps and Modbus RTU tGW-715 uses 115200 bps and Modbus RTU tGW-715 uses 115200 bps and Modbus RTU Serial Port Pair-connection Through the Ethernet Port 1(RS-485) PLC 1 uses 115200 bps and Modbus RTU Port 1(RS-485) Note: 1.PLC 1 and PLC 2 can communicate with each other via the RS-485 port that has pair-connection link through the Ethernet. Virtual RS-485 bus through the pair-connection.

32 Pair-connection with Different Protocols PLC 2 uses 115200 bps and Modbus ASCII tGW-715 uses 115200 bps and Modbus ASCII tGW-715 uses 9600 bps and Modbus RTU Serial Port Pair-connection Through the Ethernet Port 1(RS-485) PLC 1 uses 9600 bps and Modbus RTU Port 1(RS-485) Note: 1.PLC 1 and PLC 2 can use different protocol (RTU or ASCII), baud rate and data format at the same time when using pair-connection. But please make sure that the tGW-700 has the same setting as local serial devices. 2.The pair-connection can be created by using same or different tGW-700 models. The pair-connection is working as port-to-port. Virtual RS-485 bus through the pair-connection ( with Modbus RTU to ASCII converter ).

33 Virtual RS-485 Network (base on pair-connection) PLC Meter RS-485 tGW-715 with Modbus ASCII tGW-725 With Modbus RTU tGW-725 Meter tGW-725 tGW-735 RS-485 with Modbus RTU/ASCII (Single Protocol) Serial Port Pair-connection Through the Ethernet Serial Port Pair-connection Through the Ethernet Port 1 Port 2 Port 1 Port 2 (RS-485) Port 1(RS-485) Port 1 Port 1 (RS-485) Port 2 Port 2 (RS-485) Serial Port Pair-connection Through the Ethernet PLC Note: When connecting several tGW-700 (RS-485 master) in RS-485 network, you should remove the pull-high/low resister in most of the tGW-700 modules, and make sure there is only one master in the RS-485 network. Port 3

34 tGW-700 Web Configuration : Network Setting

35 tGW-700 Web Configuration : Port Setting 35

36 Application : Pair Connection

37 37 Q & A Thank You!! service@icpdas.com http://www.icpdas.com