1 Zinsco Electrical Panel Failures Milestone Electric, Dallas/Ft. Worth Dallas.

Similar presentations


Presentation on theme: "1 Zinsco Electrical Panel Failures Milestone Electric, Dallas/Ft. Worth Dallas."— Presentation transcript:

1 1 Zinsco Electrical Panel Failures Milestone Electric, Dallas/Ft. Worth http://www.milestoneelectricdfw.com/ http://www.milestoneelectricdfw.com/ Dallas TX – 25 March 2010 Daniel Friedman dfriedman@inspect-ny.com dfriedman@inspect-ny.com Zinsco Info: http://inspectapedia.com/electric/Zinsco.htmhttp://inspectapedia.com/electric/Zinsco.htm

2 2 Zinsco Sylvania Failures Burning, deteriorated bus bars Burning, deteriorated circuit breaker connectors Circuit breaker case side blowouts Failures to trip on overcurrent Point of failure appears to be at the point of contact where the circuit breaker contacts clip onto the electrical panel bus, combined with the use of an aluminum electrical panel bus.

3 3 Typical Field Failure Observations Buzzing, smoking, odors at electric panel Breakers fail to trip on overcurrent Burn-ups at wired devices, outlets, &c. Lost power on individual circuits Visual inspection of panel: arcing (often not apparent without removing breakers)

4 4 Zinsco Testing / Failure Rates Expert testing on this equipment has shown that circuit breakers do not trip about 25% of the time when exposed to overcurrent - risking overheating, fire and other hazards. The failure rate of competitive-brand circuit breakers is much less than 1%. – Simmons Limited testing performed to date Fewer field-failure reports than FPE (fewer installed?)

5 5 Zinsco Product Names Sylvania™ GTE-Sylvania™ Kearney™

6 6 How to Identify Zinsco Electrical Equipment

7 7 Zinsco Bus Burning

8 8 Zinsco Breaker Contact Burning

9 9 Zinsco Breaker Blowouts

10 10 Zinsco-Sylvania Main Breaker Failures – Failure to Trip on Overcurrent

11 11 Zinsco Breaker No-Trips

12 12 Advice for Home Owners – Zinsco/Sylvania/Kearney Failure to trip on over-current, arcing, contact- point burn, & even circuit breaker case blow-out have been observed in the field Zinsco and Zinsco-Sylvania circuit breakers do not offer the level of fire protection provided by most other brands Zinsco and Zinsco-Sylvania electrical panels should be replaced to reduce fire and shock hazards.

13 13 Zinsco-Sylvania References ZINSCO SYLVANIA ELECTRICAL PANELS - http://inspectapedia.com/electric/Zinsco.htmZINSCO SYLVANIA ELECTRICAL PANELShttp://inspectapedia.com/electric/Zinsco.htm ZINSCO SAFETY PRECAUTIONS - http://inspectapedia.com/electric/Zinsco_Warnings.htmZINSCO SAFETY PRECAUTIONShttp://inspectapedia.com/electric/Zinsco_Warnings.htm IDENTIFY ZINSCO ELECTRICAL PANELS - http://inspectapedia.com/electric/Zinsco_Identification.htmIDENTIFY ZINSCO ELECTRICAL PANELShttp://inspectapedia.com/electric/Zinsco_Identification.htm IDENTIFY GTE SYLVANIA-ZINSCO PANELS - http://inspectapedia.com/electric/GTE_Sylvania_Zinsco.htmIDENTIFY GTE SYLVANIA-ZINSCO PANELShttp://inspectapedia.com/electric/GTE_Sylvania_Zinsco.htm IDENTIFY KEARNEY PANELS - http://inspectapedia.com/electric/Kearney_Electrical_Panels.htmIDENTIFY KEARNEY PANELShttp://inspectapedia.com/electric/Kearney_Electrical_Panels.htm GTE-SYLVANIA-ZINSCO FAILURE MECHANISM http://inspectapedia.com/electric/Zinsco_Failures.htmGTE-SYLVANIA-ZINSCO FAILURE MECHANISM http://inspectapedia.com/electric/Zinsco_Failures.htm ZINSCO FAILURE REPORTS - http://inspectapedia.com/electric/Zinsco_Reports.htmZINSCO FAILURE REPORTShttp://inspectapedia.com/electric/Zinsco_Reports.htm


Download ppt "1 Zinsco Electrical Panel Failures Milestone Electric, Dallas/Ft. Worth Dallas."