Presentation is loading. Please wait.

Presentation is loading. Please wait.

FUNCTION OF OUTPUT CONTROLLER AND APPLICATION

Similar presentations


Presentation on theme: "FUNCTION OF OUTPUT CONTROLLER AND APPLICATION"— Presentation transcript:

1 FUNCTION OF OUTPUT CONTROLLER AND APPLICATION
CHAPTER 5 FUNCTION OF OUTPUT CONTROLLER AND APPLICATION

2 TIMERS Many applications in industrial control systems need timer functions. Timer is used to activate or de-activate a device after a preset time interval.

3 TIMERS Time delay relays and solid-state timers are used to provide a time delay. Time Delay Relay Solid-State Timer

4 QUANTITIES IN TIMER INSTRUCTION
Preset Time Represents the time duration of the timing circuit. e.g. if a time delay of 10 s is required, the timer will have a preset of 10 s. Accumulated Time Represents the amount of time that has elapsed since it is energized.

5 Time Base Timers can typically be programmed with several different time bases: 1 s, 0.1 s, and 0.01 s are typical time bases. E.g. if you enter 0.1 for the time base and 50 for the preset time the timer would have a 5 s delay (50 x 0.1 s = 5 s).

6 Generic Block-Formatted Timer Instruction
Timers are most often represented by boxes in a ladder logic. Control line controls the actual timing operation of the timer. Whenever this line is true the timer will time. Preset time Time base Accumulated time Retentive timer block Output line The timer continuously compares its accumulated time with its preset time. Its output is logic 0 as long as the accumulated time is less than the preset time. When the two become equal the output changes to logic 1. Reset line resets the the timer's accumulated value to zero.

7 On-Delay Timing Relay Operating coil
Instantaneous contacts NO NC Nontimed contacts are controlled directly by the timer coil, as in a general-purpose control relay. Time control contacts NO NC Time adjustment When the coil is energized, the timed contacts are prevented from opening or closing until the time delay period has elapsed. However, when the coil is de-energized, the timed contacts return instantaneously to their normal state.

8 Timed Contact Symbols On-Delay Symbols
Normally open, timed closed contact (NOTC) Contact is open when relay coil is de-energized When relay is energized, there is a time delay in closing Normally closed, timed open contact (NCTO) Contact is closed when relay coil is de-energized When relay is energized, there is a time delay in opening

9 On-Delay Timer Program
Ladder Logic Program L1 L2 TON Input A TIMER ON DELAY Timer T4:0 Time base Preset Accumulated Input A Output B G EN DN 10 Output C R T4:0 Output B EN Output D Y T4:0 Output C TT T4:0 Output D DN

10 On-Delay Relay Timer Circuit (NOTC Contact)
Sequence of operation S1 S1 is opened, TD de-energizes, TD1 opens instantly, L1 is switched off. S1 closes, TD energizes, timing period starts, TD1 still open, L1 is still off. S1 open, TD de-energized, TD1 open, L1 is off. L1 After 10 s, TD1 closes, L1 is switched on. 10 s 10 s OFF ON Input Output Timing Diagram

11 ? On-Delay Relay Timer Circuit (NCTO Contact) Sequence of operation
S1 closes, TD energizes, timing period starts, TD1 is still closed, L1 is still on. S1 is opened, TD de-energizes, TD1 closes instantly, L1 is switched on. S1 open, TD de-energized, TD1 closed, L1 is on. L1 After 10 s, TD1 opens, L1 is switched off. 10 s 10 s On Off Input Output Timing Diagram ?

12 Timed Contact Symbols Off Delay Symbols
Normally open, timed open contacts (NOTO). Contact is normally open when relay coil is de-energized. When relay coil is energized, contact closes instantly. When relay coil is de-energized, there is a time delay before the contact opens. Normally closed, timed closed contacts (NCTC). Contact is normally closed when relay coil is de-energized. When relay coil is energized, contact opens instantly. When relay coil is de-energized, there is a time delay before the contact closes.

13 Off-Delay Programmed Timer
The off-delay timer (TOF) operation will keep the output energized for a period after the rung containing the timer has gone false. EN DN TOF TIMER OFF DELAY TIMER T4:3 Time base Preset Accumulated I:1.0/0 O:2.0/1 T4:3/DN PL L1 L2 Input Output Ladder logic program S1 15

14 ? Off-Delay Relay Timer Circuit (NOTO Contact) Sequence of operation
S1 closes, TD energizes, TD1 closes instantly, L1 is switched on. S1 is opened, TD de-energizes, timing period starts, TD1 is still closed, L1 is still on. S1 open, TD de-energized, TD1 open, L1 is off. L1 After 10 s, TD1 opens, L1 is switched off. 10 s 10 s Input Output Off On Timing Diagram ?

15 ? Off-Delay Relay Timer Circuit (NCTC Contact) Sequence of operation
S1 is opened, TD de-energizes, timing period starts, TD1 is still open, L1 is still off. S1 closes, TD energizes, TD1 opens instantly, L1 is switched off. S1 open, TD de-energized, TD1 closed, L1 is on. After 10 s, TD1 closes, L1 is switched on. L1 10 s 10 s Input Output On Off Timing Diagram ?

16 NONRETENTIVE TIMER Is also known as TMR Has only 1 input
Timer enabled if the input logic is ON Timer reset if the input logic is OFF Non-retentive - loss of power flow to the timer causes the timer instruction to reset. TMR TIMER0 T0 K40 INPUT

17 RETENTIVE TIMER Also known as TMRA Has two inputs
Timer starts timing when ENABLE is ON Timer stops when ENABLE is OFF without resetting the current value to 0. Timer continues timing when it is enabled again. The timer resets when RESET is ON (RES instruction is true) Once RESET is OFF, timer enable to start TMRA TIMER2 T2 K50 ENABLE RESET

18 Retentive Timer A retentive timer accumulates time whenever the device receives power, and maintains the current time should power be removed from the device. Once the device accumulates time equal to its preset value, the contacts of the device change state. The retentive timer must be intentionally reset with a separate signal for the accumulated time to be reset. Electromechnical Retentive Timer Cam operated contact Motor-driven cam Once power is applied, the motor starts turning the cam. The positioning of the lobes determines the time it takes to activate the contacts. If power is removed from the motor, the shaft stops but does not reset.

19 EXERCISE

20 CASE 1 Using a timer, a toggle switch and a buzzer. Write a ladder diagram so that the buzzer will ON immediately, but OFF after 5 sec the input is OFF. Choose the type of timer necessary and assume the preset value for the timer is 0.1 sec. Off Delay Timer (NOTO contact) is used TMR TIMER0 T0 K50 X0 INPUT Y1=buzzer T0

21 When X0 ON the timer is enable, and starts timing. The buzzer starts.
CASE 2: Q: Using a 2 inputs timer, a PB and a buzzer. The buzzer is needed to buzz for 5 sec. Assume that the preset value is 0.1 sec. Write the ladder diagram. A: The ladder diagram is as below. X0= PB ENABLE TMRA TIMER2 T2 K50 T2 RESET X1 Y1=buzzer T2 Figure (b) Timer with 2 inputs When X0 ON the timer is enable, and starts timing. The buzzer starts. When X0 OFF the timer enable is off, and stop timing. But it does not reset to zero.

22 5.1.2 Cascading Timer Applications sometimes require longer time delays than one timer can accomplish. Multiple timers can then be used to achieve a longer delay than would otherwise be possible. One timer acts as the input to another. When the first timer times out, it becomes the input to start the second timer timing. This is called cascading.

23 When X0 is ON, timer will start timing. After 99 sec, Timer 1
CASE 3: Q: One maximum timer can be set for 99sec. Let say preset value is 1 sec. Time needed to set is 150. In this case cascading timer is used. X0 TMR T0 K99 T0 TMR T1 K51 Figure (a) Cascading Timer When X0 is ON, timer will start timing. After 99 sec, Timer 1 will trigger T0 to open. Then T0 will initiate Timer 1, and timing for another 51 seconds. Usually used when requirements demand more time than is available from a single timer. Therefore, two or more timers can be programmed together to get the desire time.

24 CASCADING

25 CASCADING TIMER

26 The programming of two or more timers together is called cascading.
Timers may be interconnected, or cascaded to satisfy any required control logic.

27 Cascading Timers For sequencing Relay Schematic Diagram
Three motors started automatically in sequence with a 20-s time delay between each motor startup. Relay Schematic Diagram

28 Cascading Timers For Longer Time Delays 30000
12000 30000 T4:1 max of seconds + T4:2 of seconds = seconds/ 700 minutes

29 COUNTER Electronic counters can count up, count down, or be combined to count up and down. They are dependent on external sources, such as parts traveling past a sensor or actuating a limit switch for counting.

30 COUNTER APPLICATIONS

31 Block-Formatted Counter Instruction
Type of counter Preset value Accumulated value Count line Reset line Output line PLC counters operate or count on the leading edge of the input signal. The counter will either increment or decrement whenever the count input transfers from an "off" state to an "on" state. The counter will not operate on the trailing edge, or on-to-off transition of the input condition.

32 Counter Counting Sequence
PLC counters are normally retentive. Whatever count was contained in the counter at the time of a processor shutdown will be restored to the counter on power-up. The counter may be reset, however, if the reset condition is activated at the time of power restoration. PLC counters can be designed to count up to a preset value or to count down to a preset value.

33 Counter Counting Sequence
The up-counter is incremented by 1 each time the rung containing the counter is energized. Counter Counting Sequence The counter will increment until the accumulated value is equal to or greater than the preset value, at which time an output will be produced.

34 Counter Counting Sequence
The down-counter decrements by 1 each time the rung containing the counter is energized. Counter Counting Sequence A counter reset is always provided to cause the counter accumulated value to be reset to a predetermined value.

35 UP- COUNTER

36 Simple Up-counter Program
7

37 Up-counter Program Timing Diagram

38 PLC-5 And SLC 500 Count-Up Counter Instruction

39 ControlLogix Count-Up Counter Instruction
The counter address in the PLC-5 and SLC 500 is a data table address, whereas in the ControlLogix it is a predefined structure of the data type. In the PLC-5 and SLC 500, the max value for the preset and accumulated values is 32,767 and the min value is –32,768; for the ControlLogix controller the max value is 2,147,438,647 and the min value is –2,147,438,648.

40 RSLogic Counter Commands
CTU Count-Up Increments the accumulated value at each false-to-true transition and retains the accumulated value when power cycle occurs CTD Count-Down Decrements the accumulated value at each false-to-true transition and retains the accumulated value when power cycle occurs RES Reset Resets the accumulated value and status bit of the counter HSC High-Speed Counter Counts high-speed pulses from a fixed controller high-speed input Command Name Description

41 Parts Counting Program
Counter C5:2 counts the total number of parts coming off an assembly line for final packaging Each package must contain 10 parts When 10 parts are detected, counter C5:1 sets bit B3/1 to initiate the box closing sequence Counter C5:3 counts the total number of packages filled per day A pushbutton is used to restart the total part and package count from zero daily

42 Parts Counting Program
10 1 15 5 9

43 DOWN- COUNTER

44 Down-Counter The down-counter output instruction will count down or decrement by 1 each time the counted event occurs. Each time the down-count event occurs, the accumulated value is decremented. Normally the down-counter is used in conjunction with the up counter to form an up/down counter. Generic up/down counter program

45 Up/Down Counter Timing diagram
Preset Value = 3

46 Parking Garage Counter Program
As a car enters, it triggers the up-counter output instruction and increments the accumulated count by 1. As a car leaves, it triggers the down-counter output instruction and decrements the accumulated count by 1. Since both the up- and down-counters have the same address, the accumulated value will be the same in both. Whenever the accumulated value equals the preset value, the counter output is energized to light up the Lot Full sign.

47 Parking Garage Counter Program
150 38 50

48 Count-Down Counter Instruction
PLC-5 And SLC-500 Count-Down Counter Instruction If the accumulation value is below the minimum range then the underflow (UN) bit will be true.

49 Up/Down-Counter Program
When the CTU instruction is true, C5:2/CU will be true causing output A to be true 1 When the accumulated value is greater than or equal to the preset value, C5:2/DN will be true, causing output C to be true 10 When the CTD instruction is true, C5:2/CD will be true causing output B to be true Input C going true will cause both counter instructions to reset

50 In-Process Monitoring System
Before start-up, the system is completely empty of parts, and the counter is reset manually to zero. When the operation begins, raw parts move through the in-feed sensor, with each part generating an up count. After processing, finished parts appearing at the out-feed sensor generate down counts, so the accumulated count of the counter continuously indicates the number of in-process parts.

51 In-Process Monitoring System
5 8

52 Counting Beyond The Maximum Count
15000

53 Counter Speed The maximum speed of transitions you can count is
determined by your program's scan time. Any counter input signal must be fixed for one scan time to be counted reliably. If the input changes faster than one scan period, the count value will become unreliable because counts will be missed. When this is the case you need to use a high-speed counter.

54 CASCADING COUNTER

55 Cascading Counters Depending on the application, it may be necessary to count events that exceed the maximum number allowable per counter instruction. One way of accomplishing this is by interconnection, or cascading, two counters.

56 Counting Beyond The Maximum Count
The output of the first counter is programmed into the input of the second counter The status bits of both counters are programmed in series to produce an output These two counters allow twice as many counts to be measured

57 Cascading Counters For Extremely Large Counts
500 1 The output light turns on after 500 x 500, or 250,000 transitions of the count input Whenever counter C5:1 reaches 500, its done bit resets counter C5:1 and increments counter C5:2 by 1


Download ppt "FUNCTION OF OUTPUT CONTROLLER AND APPLICATION"

Similar presentations


Ads by Google