Presentation is loading. Please wait.

Presentation is loading. Please wait.

Lab # 5: Convection Heat Transfer Max Tenorio

Similar presentations


Presentation on theme: "Lab # 5: Convection Heat Transfer Max Tenorio"— Presentation transcript:

1 Lab # 5: Convection Heat Transfer Max Tenorio
14:650:432:02 Lab # 5: Convection Heat Transfer Max Tenorio

2 Purpose Convection Heat Transfer occurs almost everywhere
Examine characteristics of heat transfer to turbulent air flow through a uniformly heated pipe Measure temperature distribution for two air flow rates and two power settings to calculate the heat transfer coefficient, Reynolds, Stanton, and Prandtl numbers and friction factor.

3 Setup

4 Specifications Total 5.75 feet long Insulation thickness: 0.813”
13 total thermocouples (1 broken) Connected to labview

5 Raw Data Units Run - 1 2 3 4 Current A 2.5 Voltage V 140 210 135
Run - 1 2 3 4 Current A 2.5 Voltage V 140 210 135 Pa fan inH2O 13.2 3.9 Pb plate 3.5 0.9 Pc test sec 2.7 3.1 1.1 T1 C 49.284 98 T2 51.681 77.642 T3 53.486 T4 54.358 83.922 T5 55.261 71.821 123.37 T6 56.692 T7 66.038 T8 72.319 T9 24.662 T10 T11 T12 74.716 T13 25.035 Ttest section 37 48.5 38 39 Tamb 20 Pbarom atm

6 Mass Flow Rate Run 1 Run 2 Run 3 Run 4 Mass Flow Rate (kg/s)
Volume Flow Rate (L/s) Run 1 Run 2 Run 3 Run 4

7 Heat Flux Method 1 q" in q"loss avg q" heat flux Run W/m^2 1 1949.11
460.94 2 986.90 3 533.59 4

8 Thermal Profile

9 Heat Flux Method 2 Requires Thermal Profiles
Discussion b: The heat flux values in b and d are different because b uses raw experimental values to perform the heat balance and assumes that for q”out, the maximum heat loss is uniform for the entire circumference for the pipe, when in reality the heat loss is most likely not uniform through a cross section. Additionally, d assumes laminar flow and relies on a constant specific heat capacity for air and a constant flow rate. dTs(x)/dx q" (b) q" in (b) q"(d) assuming b is correct Run °K/m W/m^2 % error 1 5.2741 2 12.672 3 9.1567 1879.5 4 21.183 Although the percent error is somewhat high, it is worth noting that the heat flux from d is close to the q”in from b. The difference is most likely equipment error and incorrect values

10 Bulk Air Temperature The Bulk Air temperature is the average temperature of air in a section of pipe. Tx x (m) 1 2 3 4 0.3175 38.25 51.60 40.07 44.24 39.81 55.48 42.66 50.78 1.0287 41.05 58.55 44.70 55.97 41.72 60.20 45.80 58.74 42.38 61.84 46.90 61.52 43.04 63.49 47.99 64.29 1.7018 43.71 65.13 49.09 67.07

11 Heat Transfer Coefficient
1 2 3 4 h3 h4 h5 54.002 havg 154.84 55.123 Discussion a: The wall temperature is easily measured using the thermocouples and the bulk temperature is the average temperature of air in that cross section. They vary; the wall temperature will be higher because it is closer to the heating element and the temperatures are higher in general because energy is being transferred to the air as it travels. The beginning and end points are skewed because of end effects. The slopes of both are constant in the middle section because the rate at which temperature changes is the same for both the wall and air inside the tube.

12 Reynolds Number Ratio of inertial forces (Vρ) to viscous forces (μ / L) Reynolds Number Run 1 Run 2 Run 3 Run 4

13 Nusselt Number Ratio of convective to conductive heat transfer across the boundary Correlation Regular Run 1 229.13 153.48 Run 2 202.00 Run 3 141.36 71.91 Run 4 145.18 75.33

14 Friction factor Correlation Regular Run 1 0.017161 0.004274 Run 2
Run 3 Run 4

15 Stanton Number Ratio of heat transferred into a fluid to the thermal capacity of fluid Correlation Regular Run 1 Run 2 Run 3 Run 4

16 Calculated Values Re q“ (w/m^2K) Nu, exp. Nu, corr. f, exp. f, corr St, exp. St, corr. Run 1 153.48 229.13 Run 2 202.00 Run 3 71.91 141.36 Run 4 75.33 145.18 Discussion c: For the Nusselt Number and friction factor, the experimental values are much lower than the correlation values. These most likely result from equipment error, since the friction factors for runs 3 and 4 drop to zero and even go negative, meaning the pressure at the exit is higher than the entrance pressure. As far as the Stanton number goes, the values for the high speed regions (runs 1 and 2) are close, but the values for low speed are off, meaning that less energy was transferred into the air than anticipated.

17 Sample Calculations Run 1 Pa Fan Pb Plate Δh (m) A (m^2) g (m/s^2)
Air Density (kg/m^3) Water Density (kg/m^3) Flow Coefficient Mass Flow Rate (kg/s) 1 0.0889 9.8 0.6 T8 T10 T12 T9 T11 T13 ΔT1 ΔT2 ΔT3 R q" loss 1 q" loss 2 q" loss 3 q"loss avg C m^2K/W W/m^2 1 72.319 74.716 24.662 25.035 47.657 49.681 Mass Flow Rate pi cp Di dTs(x)/dx q" kg/s J/kgK m °K/m W/m^2 1 1012 5.2741 x (m) Ts Tx Ts(x) - T(x) h (W/M^2K) 0.3175 49.284 38.251 11.033 51.681 1.0287 53.486 54.358 55.261 56.692 1.7018 66.038

18 Sample Calculations Re 1 Re=QD/VA Q 0.046171197 D 0.0326136 ν 1.57E-05
Pr ν/α α 2.22E-05 7.08E-01 Nu Nu=0.023*Re^0.8*Pr^1/3 Nu=hD/k h k 0.025 Friction factor f p1 p2 air density mass flow rate L 1.7526 Equation Stanton Number Correlation St St=h/ρcpV


Download ppt "Lab # 5: Convection Heat Transfer Max Tenorio"

Similar presentations


Ads by Google