1 Feasibility Demonstration of a Mechanically Pumped Two-Phase CO 2 Cooling Loop for the AMS-2 Tracker Experiment Conference on Thermophysics in Microgravity.

Similar presentations


Presentation on theme: "1 Feasibility Demonstration of a Mechanically Pumped Two-Phase CO 2 Cooling Loop for the AMS-2 Tracker Experiment Conference on Thermophysics in Microgravity."— Presentation transcript:

1 1 Feasibility Demonstration of a Mechanically Pumped Two-Phase CO 2 Cooling Loop for the AMS-2 Tracker Experiment Conference on Thermophysics in Microgravity Space Technology & Applications International Forum Albuquerque, NM, USA, 3-7 February 2002 B. Verlaat & H. Boer Rookhuizen 1, A.A.M. Delil & A.A. Woering 2, E. Perrin & M. Pohl 3, R. Battiston 4 1 National Institute for Nuclear and High-Energy Physics, Netherlands, +31 20 5922095, bverlaat@nikhef.nlbverlaat@nikhef.nl 2 National Aerospace Laboratory NLR, Netherlands, +31 527248229, adelil@nlr.nladelil@nlr.nl 3 University of Geneva, Switzerland, 4 INFN Perugia, Italy

2 2 AMS-Experiment overview AMS is a space born particle detector originating from the international high energy physics community. AMS is financed by NASA/DOE and the collaborating institutes. AMS is seeking for cosmic anti-matter, dark matter and missing matter originating from distance galaxies. The AMS-mission consists of a completed precursor flight (STS-91, may 1998) and a planned 5 years mission as attached payload on the International Space Station, scheduled to be launched on Space Shuttle flight UF-4 (march 2004)

3 3 AMS-1 situated in the back of Discovery’s cargo bay on STS-91 (May 1998) as a precursor flight. AMS-1 Payload AMS’ final mission as attached payload on the ISS (STS Mission UF4, March 2004) AMS Missions

4 4 Cosmic Particles Alpha Magnetic Spectrometer Detector overview Particle track detection in the Tracker Space Shuttle Cargo Bay

5 5 detection surface The AMS-2 Silicon Tracker 112 individual Electronic assemblies producing each 1-3 Watt of heat Radiators for the Tracker (2x1.3m 2 ) 192 Watt Tracker Thermal Control System (TTCS)

6 6 TTCS main design constrains: The AMS-1 Tracker will be re-used for the AMS-2 mission. The TTCS need to fit the existing hardware. 112 individual heat sources spread over the outer periphery of the Tracker All 112 heat sources must be controlled on the same temperature level (<1°C) between 0°C and 10°C, with limited orbital variations (<3°C). Low TTCS mass allowed in the Tracker. (Field of view disturbance) Low thermal gradient to the radiators, due to the limited radiator area.

7 7 1.Capillary Pumped Systems (LHP or CPL). Too many spread heat sources (=>112 evaporators!). Severe amount of mass in the Tracker Serious integration problems 2.A two-stage concept, using a collecting heatpipe and CPL/LHP for transport to the radiators. Better choice than the single CPL system. Heatpipe (Ø10mmx1500mm) is large and difficult to integrate. 3.Serial mechanically Pumped loop (Single/two-phase). The only serious option for a multiple heat input system like the Tracker TTCS investigated concepts and trade-off: Heat colleting heat pipe with CPL connection to the radiators

8 8 MPL concept in the Tracker Detection surface Electronics (Heat Sources) cooling tube 2 loops of 10 m length

9 9 TTCS-MPL baseline concept: A redundant series loop with Carbon dioxide as working fluid. Why Carbon dioxide? Hardly no safety related problems, not toxic! Very low Liquid/Vapour density ratio O(1-10), crucial for a series 2-phase system. (Ammonia O(100-1000)) High evaporative heat transfer coefficients (2-20 kW/m 2 K) Good refrigerant around 0ºC evaporation temperature. In the case of the AMS-Tracker: –Small tube dimensions (3 mm OD) in case of 2 parallel loops »Low mass in the Tracker field of view. –Possibility of following the stepped orientation of the heat sources. »Direct thermal contact (Efficient heat transfer). »No foreseen integration problems. »No CTE problems –Very low temperature gradients (<1ºC) over the evaporator length (ca. 10m). –Possibility of implementing a fully redundant system.

10 10 CO 2 phase diagram TTCS operating area

11 11 Feasibility demonstration of the TTCS serial evaporator using CO 2 Test Set-Up schematic CO 2 Feasibility Test Set-Up. Pressure gauges Expansion valve CO 2 Bottle 99.995% DAQ Tube 1 Tube 2 Tube 3 Tube 4 To gas heater, spring relieve valve and flow meter Pressure drop and temperature gradient measurements using a venting test.

12 12 Feasibility Test Results. Evaporator length (9.3m) Flow direction Nominal condition Specified maximum gradient

13 13 Mechanical circulation pump in the liquid line. Loop pressure/evaporation temperature control using a two- phase accumulator. Heat exchangers between the in and outlet of the evaporator for efficient preheating of the sub- cooled liquid. Orbital load damping using out of phase WAKE and RAM radiators. Heatpipe radiators to minimize debris puncture risk of the TTCS pressurized volume. TTCS CO 2 circulation system overview: (Preliminary)

14 14 The complete TTCS integrated in AMS Artists impression of the TTCS CO 2 evaporator in AMS Detailed view of the TTCS evaporator connection to the Tracker hybrids TTCS CO 2 loop design overview

15 15 TTCS Evaporator prototyping

16 16 Schematic of the prototype CO 2 loop at NIKHEF. On going TTCS research activities: Evaporator research: Pressure drop measurements Heat transfer coefficients Thermal control: Heat exchanger feasibility

17 17 Photos of the TTCS Test Loop at NIKHEF. Heat exchanger AMS-like evaporator Pump Thermal control reservoir Condenser in thermostat bath Transparent section for flow pattern study Level indicator

18 18 Power dependent pressure/temperature drops for a 10 m long, 2.5 mm ID evaporator at 0°C

19 19 Vapour quality and power dependence of the heat transfer coefficient and observed flow patterns, for a 2.5 mm ID tube at a flow rate of 2.7 g/s and a temperature of 5°C 0 0.1 0.2 0.3 0.4 0.5 0.6 Vapour quality (-)

20 20 Heat exchanger performance at nominal conditions (100 Watt, 2.7 g/s, 5ºC) Flow direction

21 21 TTCS response on a varying condenser temperature with a heat exchanger.

22 22 Conclusions The TTCS evaporator concept with CO 2 as working fluid fulfills the thermal specifications of AMS-Tracker The discussed TTCS evaporator concept is fully compatible with the rest of the AMS experiment hardware. The presence of a heat exchanger between the in and outlet of the evaporator show a positive impact on the dynamic behavior of the TTCS Based on this feasibility demonstration the AMS- collaboration decided to accept the discussed TTCS proposal as base-line cooling system for the AMS- Tracker (Nov. 2001)