Download presentation
1
Mars RT Pro On-Line Series UPS
2
Content Introduction of MP Series System Block Diagram
Product Features Functions Explanations Product Specifications Q&A
3
Introduction of MP Series
Mars – RT Pro Model MP 1K( X/C ) 2K( X/C ) 3K( X/C ) Capacity : 1000VA, 2000VA, 3000VA Servers in Rack / Tower Convertible Networking & VOIP Telecom Equipment Sensitive Electronic Equipment in Industrial Environment
4
True Online Double Conversion for Various Applications
System Block Diagram True Online Double Conversion for Various Applications
5
Product Features True On-line Double Conversion Topology
Fully High Performance DSP Control Flexible Rack/Tower Application Input Frequency 45-65Hz Wide Range Input Window from 120~288Vac High Input Power Factor & Low Current THD Programmable Receptacles Versatile Interfaces Options Hot-Swappable Battery Bigger Charger & Extended Battery Connector Galvanic Isolation Transformer Models are Available
6
Functions Explanations
LED Indicators: Overload Fault Site Wiring Fault Battery Weak/Bad Self-test Programmable Outlet1 Programmable Outlet2 Bypass Mode Battery Mode Line Mode Control Keypads: On Key Off Key Test & Alarm Silence Key 1 2 3 4 5 6 7 8 9 10 11 12 13
7
LED Indicators: LCD Utility Programmable Outlet1 Programmable Outlet2 Bypass Range Fault Control Keypads: ON Key &Alarm Silence Key OFF Key Function Key Down Key Up Key Enter Key
8
Real Panel Explanation (1kVA)
Real Panel Explanation (1kVA) USB Comm. Port RS-232 Comm. Port EPO External Battery Connector Socket for connection to AC-power source Input circuit breaker Slot for Communications-card option Two Programmable Outlets Outlets Fan
9
Real Panel Explanation (2kVA)
1 2 3 4 5 6 7 8 9 10 Real Panel Explanation (2kVA) 1 USB Comm. Port 2 RS-232 Comm. Port 3 EPO 4 External Battery Connector 5 Socket for connection to AC-power source 6 Input circuit breaker 7 Slot for Communications-card option 8 Outlets 9 Two Programmable outlets 10 Fan
10
Real Panel Explanation (3kVA)
1 2 3 4 5 6 7 8 9 10 11 12 Real Panel Explanation (3kVA) 1 USB Comm. Port 2 RS-232 Comm. Port 3 EPO 4 External Battery Connector 5 Socket for connection to AC-power source 6 Input circuit breaker 7 Slot for Communications-card option 8 Outlets 9 Two Programmable outlets 10 Output Breaker for two Power Programmable outlets 11 Output circuit breakers 12 Fan
11
External Communication Interface
Standard Unit : RS232 and USB interface Optional in Slot : 1. WEB/SNMP Card 2. True Relay Contact Card 3. RS485 Card
12
Communication Software
Emily UPSilon 2000
13
Emergency Power Off (EPO)
Emergency shutdown control through the EPO
14
Hot-Swappable Battery Removable Battery Bank
Battery Replacement from Front Panel Without Hazard Risk to Users Backup Time (Full Load): 1kVA > 7 min. 2kVA > 7 min 3kVA > 5 min.
15
Large Built-in Charger
Fastest Charging Internal Battery to 90% in 3 hours. 1.8A~2.7A Charger Built-in for Immediate Run Time Expansion.
16
Nominal System Voltage
Solutions for Long Runtime Increased Runtime for Critical Applications Extended Runtime Capabilities with Multiple External Battery Bank (Optional) UPS 1KVA 2KVA/3KVA Battery Bank SN BBC0007 BBC12K0009 Nominal System Voltage 36VDC 72VDC Dimensions W x D x H, mm Unit 440 x 650 x 88 Shipping 560 x 833 x 228 Weight, kg 38 44.6 46 52.6
17
Battery Run Times LOAD MP-RT 1000 1 x EXB 2 x EXB 140w 01:06:06
05:51:10 10:32:06 280w 00:27:45 03:01:28 05:26:39 420w 00:14:24 02:02:21 03:40:13 560w 00:10:19 01:32:17 02:46:06 700w 00:07:09 01:09:43 02:13:20
18
Battery Run Times LOAD MP-RT 2000 1 x EXB 2 x EXB 280w 01:06:06
03:30:42 05:51:10 560w 00:27:45 01:48:53 03:01:28 840w 00:14:24 01:09:05 02:02:21 1120w 00:10:19 00:52:07 01:32:17 1400w 00:07:09 00:33:59 01:09:43
19
Battery Run Times LOAD MP-RT 3000 1 x EXB 2 x EXB 420w 00:59:11
03:08:39 05:14:25 840w 00:19:03 01:37:09 02:41:35 1260w 00:12:11 01:01:34 01:49:02 1680w 00:08:25 00:46:25 01:17:21 2100w 00:05:26 00:30:15 01:02:04
20
Front and Rear Panel Descriptions
1.Screw Cover To replace batteries, please remove the screw covers and the screws inside the covers. 2. EXT.BAT. +/- To the DC terminal of the 2nd(or next) battery bank connected. 3. UPS BAT. +/- To the UPS DC terminal or the next battery bank. 4. DC Breaker 1. Over-current Protection Breaker 2. To easy swappable battery, please put the position of the breaker in “O” position. In case there is 2nd(or next) battery bank connected with the battery bank, the DC voltage from the UPS Bat.+/- will flow through without any interruption to the 2nd Battery Bank. 5. AC Inlet for Charger AC Inlet for Charger. Optional.
21
Optional External Bypass Switch
Easy Installation with ready-to-go inlets & outlets. Break before Make Switch(3ms)
22
Operating Illustration
23
Programmable Receptacles Current Monitoring
Output Receptacles Enable/Disable Ablerex own-developed software for Windows Platform Increased runtime for critical applications: Load shedding with programmable outlets.
24
Setting Software User Personalization Output Voltage Configurations UPS Modes Output Voltage Fine Tuning Bypass Voltage Tolerances Synchronized Frequency Window Company Name UPS Model UPS Capacity Calibration Setting (Manufacturing setting only)
25
Programmable Outlet Setting
Outlet Turn On After Turn on UPS Outlet Turn Off After AC Failure Outlet Turn On After AC Recovered Outlet Turn Off When Battery Lower than Outlet Turn Off When Overload Manual Control Switch Programmable Outlet On/Off
26
Internal structure(1kVA)
[B1]加入 Internal structure (2/3kVA) Internal structure(1kVA) 1/1.5KVA 2KVA 3KVA Driver Board(1) 110V MPAD2XX MPCD2XX 220V Driver Board(2) N/A MPCD1XX MPCD3XX Control Board MPAI0XX EMI filter Board MPAF2XX MPCF2XX LED Display MPAM2XX
27
MPAD2XX PCB (1/1.5KVA)
28
MPCD2XX PCB(2K/3KVA) Work power Charger circuit Inverter IGBT
Inverter choke Charger circuit Work power Feedback Relay MPCD2XX PCB(2K/3KVA)
29
MPCD3XX PCB (2/3KVA -220V System)
Boost MOSFET PFC IGBT PFC choke Boost Transformer +BUS
30
Product Specifications
INPUT Model MP-RT 1000 MP-RT 1500 MP-RT 2000 MP-RT 3000 Voltage Window 120/140/160~288Vac 60/70/80~144Vac Frequency 45~65Hz Phase/Wire Single, Line + Neutral + Ground Power Factor Up to 0.99 at 100% Linear Load OUTPUT Rated Voltage 200/208/220/230/240Vac Selectable 100/110/115/120/127Vac Selectable Voltage Regulation ≦ +/-1% until low battery warning Capacity (VA/W) 1000/700 1500/1050 2000/1400 3000/2100 Rated Power Factor 0.7/0.8* Lagging Wave Form ≦3% THD at linear load; ≦ 7% at Non-linear load Frequency [Synchronized Range] 1Hz or 3Hz Transfer Time 0ms Crest Factor 3:1 Efficiency (AC to AC, Normal) Up to 85% Up to 88% Efficiency (DC to AC) Up to 83% DC Start Yes
31
Sealed Lead Acid Maintenance Free
BATTERY Model MP-RT 1000 MP-RT 1500 MP-RT 2000 MP-RT 3000 Backup Time >7 min. >5 min. Type Sealed Lead Acid Maintenance Free Quantity 3pcs 6pcs Capacity 7.2AH 9AH Voltage 36Vdc 72Vdc Recharge Time 3 hours to 90% Charger Current 1.8A 2.1A 2.7A
32
PHYSICAL Model MP1000X/MP1000C MP2000X/MP2000C MP3000X/MP3000C Dimensions ( W x D x H ) mm/inch 440 x132 x405/ 17.3x5.2x16 440 x176 x520/ 17.3x7.0x20.5 Input Connection (230Vac Only) IEC IEC320-C14 IEC320-C20 Output Connection 6 x IEC320-C13 4 x IEC320-C13 1 x IEC320-C19 Weight (Kgs/lbs) w/o transformer w/batteries 15.5/34.2 32.0/70.5 33.0/72.7 w/o transformer w/200W 7.9/17.4 16.7/36.8 17.7/39.0 w/transformer w/batteries 22.0/48.6 42.0/92.6 46.0/101.4 w/transformer w/200W 14.4/31.8 26.7/58.9 30.7/67.7
33
Q & A
Similar presentations
© 2024 SlidePlayer.com Inc.
All rights reserved.