Presentation is loading. Please wait.

Presentation is loading. Please wait.

EE4503 Electrical Systems Design

Similar presentations


Presentation on theme: "EE4503 Electrical Systems Design"— Presentation transcript:

1 EE4503 Electrical Systems Design
Load Calculation

2 Topics Load Calculation (E.I.T.)
Load Calculation by Adding Branch Circuit Load Calculation for condominium Load Estimation

3 Load Calculation (E.I.T.) lighting
Building Lighting (VA) Demand Factor (%) Residential Area  2,000 > 2,000 100 35 Hospital  50,000 > 50,000 40 20 Hotel, Condominium  20,000 20,001 – 100,000 > 100,000 50 30 Warehouse  12,500 > 12,500 Other

4 Load Calculation (E.I.T.) receptacles
Total Load from Receptacle Demand Factor (%) Non residential area  10kVA 100 > 10kVA 50 Residential area 𝐿 𝑚𝑎𝑥 +0.4 𝐿 𝑟

5 Load Calculation (E.I.T.) Demand Factor of Appliances
Building Lighting (VA) Demand Factor (%) Residential Area Kitchen Hot Water Air Condition 10A+30% of extra first two + 25% of other 100 Office, Store First maximum device + 80% of the second max. + 60% of the rest 100% of the largest + 25% of the rest Hotel, Other Same as Office 75

6 Load Calculation by Adding Branch Circuit
Add of all branch circuit Then multiply by the demand factor Number of Panels Demand Factor (%) 1 2-3 4-6 7-10 > 10 100 90 80 70 60

7 Load Calculation for Condominium
Load: common area + individual room Type Number of Rooms Coincident Factor (%) Residential 1-10 11-20 21-30 31-40 > 41 90 80 70 60 50 Non residential > 11 100 85

8 Load Estimation Quick estimate of the load
Many common tables, just refer to one

9 Load Estimation

10 Load Estimation

11 Load Estimation (E.I.T.) lighting
Type VA/m2 School 25 Computer Center, Meeting Room, Kitchen 20 Walk way, Balcony 8 Cafeteria 18 Hospital – Operation Room 100 Hospital – Patient Room 14 Office, Shopping Store 30 Drawing Room 60 Laboratory 50

12 Load Estimation (E.I.T.) receptacles
Type VA/m2 Auditorium, Cafeteria, Church, Sport Complex 2 Drawing Room 7 Hospital 10 Machine Room 15 Office School

13 Load Estimation (E.I.T.) air condition
Type VA/m2 Bank 80 Department Store 50 Hospital 70 Office Grocery Store 90 Cafeteria

14 Reference Electrical Systems Design: ประสิทธิ์ พิทยพัฒน์
Depend on the area, end-user can connect to the “meter” of the authority in three ways.


Download ppt "EE4503 Electrical Systems Design"