General Dilution Ventilation. 2 The supply and exhaust of air in a building Types of general dilution ventilation:  Type1: dilution ventilation (D.V.)

Similar presentations


Presentation on theme: "General Dilution Ventilation. 2 The supply and exhaust of air in a building Types of general dilution ventilation:  Type1: dilution ventilation (D.V.)"— Presentation transcript:

1 General Dilution Ventilation

2 2 The supply and exhaust of air in a building Types of general dilution ventilation:  Type1: dilution ventilation (D.V.)  D.V. Is the dilution of contaminated air with uncontaminated air for controlling potential airborne health hazards, fire and explosive conditions, odors and nuisance type contaminants  D.V. Also includes the control of airborne contaminants such as vapors, gases and particulates generated within tight buildings  D.V. Is not as satisfactory for health hazard control as is local exhaust ventilation  Type 2 : heat control ventilation  It is the control of indoor atmospheric conditions found in hot industrial environments. The purpose is to prevent discomfort or injury to workers

3 General Dilution Ventilation3 Dilution Ventilation for Health Dilution ventilation is generally used to control the vapors from organic liquids with a TLV of 100 ppm or higher. The limiting factors for D.V. For health are:  The quantity of contaminant generated must not be too great or the air flow rate necessary for dilution will be impractical.  Workers must be at an appropriate distance from the contaminant source or the exposed contaminant must be in sufficiently low concentrations so that workers will not have an exposure in excess of the established TLV.  The toxicity of the contaminant must be low.  The emission rate of contaminants must be reasonably uniform.

4 General Dilution Ventilation4 Parameters Required for Determination of Dilution Ventilation Rates  Solvent vapor per minute (i.E. Evaporation rate )  Specific gravity of liquid  Molecular weight  Acceptable health standard (threshold limit value i.E. TLV)  K factor for incomplete mixing

5 General Dilution Ventilation5 General Dilution Ventilation Equation Rate of accumulation = Rate of generation – Rate of removal Vdc = Gdt – Q’Cdt Where V = Volume of room G = Rate of generation Q’ = Effective volumetric flow rate C = Concentration of gas or vapor in ppm t = time For steady state condition, change in concentration, dC = 0 Gdt = Q’Cdt For constant concentration C and uniform generation rate G, the above equation may be integrated as Q’ = G/C Now, G = (403 * SG * ER)/MW

6 General Dilution Ventilation6 General Dilution Ventilation Equation Q’ = (403 * 10 6 * SG * ER)/MW * C Where SG = Specific gravity ER = Emission rate in pints/minute MW = molecular weight G = Rate of generation in cfm C = Concentration of gas or vapor in ppm Actual Ventilation Rate Q = Q’ * K Where K = factor for incomplete mixing and lies between 1 and 10 and depends on:  Efficiency of mixing  Toxicity of chemicals  Duration of the process

7 General Dilution Ventilation7 Contaminant Concentration Build Up Vdc = Gdt - Q’Cdt Rearranging the terms and integrating from time t 1 to t 2 and concentration C 1 to C 2, we get ln[(G-Q’C 2 )/ [(G-Q’C 1 ) = -Q’/V(t 2 -t 1 ) Δt = t 2 - t 1 Δt = -V/Q’ * ln [(G-Q’C 2 )/ [(G-Q’C 1 ) If initial concentration C 1 = 0 and Q’ = Q/K then Δt = K(V/Q)ln [G )/ [G-((Q/K)C 2 )] Note: C is in parts /10 6

8 General Dilution Ventilation8 Rate of Purging For this case, rate of contaminant generation G = 0 VdC = -Q’Cdt dC/ C = (-Q’/V)dt Integrating from time t 1 to t 2 and concentration C 1 to C 2, we get ln(C 2 / C 1 ) = -Q’/V(t 2 -t 1 ) t 2 - t 1 = -(V/Q’) ln(C 2 / C 1 ) If initial time t 1 =0 then t 2 = -(V/Q’) ln(C 2 / C 1 ) = -(V/Q’) ln(C 1 / C 2 ) Q’= Q/K t 2 = K(V/Q) ln(C 1 / C 2 ) Where t 2 =time, minutes

9 General Dilution Ventilation9 Mixtures-dilution Ventilation for Health When two or more hazardous substances are present, then their combined effect known as the additive effect should be given primary consideration If (C 1 /TLV 1 ) + (C 2 /TLV 2 ) +……… (C n /TLV n ) > 1 then the threshold limit of the mixture is considered to be exceeded Where C = observed atmospheric concentration TLV = corresponding threshold limit

10 General Dilution Ventilation10 Ventilation for Heat Control History of heat stress  Steel industry  Glass industry  Mining industry  Paper industry Heat load on a person  Metabolism  Conduction  Convection  Radiation  Evaporation

11 General Dilution Ventilation11 Heat Balance and Exchange delta s = (M – W) + C + R - E delta s = change in body heat content (M-W) = total metabolism C = convection heat exchange R = radiative heat exchange E =evaporative heat loss C and R are positive if delta s increases in heat Data required: Measurement of metabolic heat production Air temperature Air water vapor pressure Wind velocity Mean radiant temperature

12 General Dilution Ventilation12 Methods of Heat Exchange  Convection  Radiation  Evaporation Convection C = 0.65V a 0.6 (t a -t sk ) Where C = convective heat exchange, Btu/h V a = air velocity, fpm t a = air temperature, F t sk = mean weighted skin temperature, usually assumed to be 95 F

13 General Dilution Ventilation13 Methods of Heat Exchange Radiation R = 15.0 (t w - t sk ) Where: R = radiant heat exchange, Btu/hr t w = mean radiant temperature,F t sk = mean weighted skin temperature(usually 95 F)

14 General Dilution Ventilation14 Methods of Heat Exchange Evaporation E = 2.4V a 0.6 (ρ sk - ρ a ) Where: E = evaporative heat loss, Btu/h V a = air velocity, fpm ρ a = water vapor pressure of ambient air,mm Hg ρ sk = water vapor pressure on the skin, (assumed to be 42 mm Hg at a 95 F skin temperature)

15 General Dilution Ventilation15 Acute Heat Disorders 1. Heat stroke  A major disruption of central nervous function  Lack of sweating  Rectal temperature > 41 0 C Treatment  Placing the patient in a shady area  Removing the outer clothing  Wetting the skin  Increasing air movement  Professional help

16 General Dilution Ventilation16 Acute Heat Disorders 2. Heat exhaustion Causes  Lack of acclimatization  Failure to consume sufficient water Symptoms  Clammy, moist skin  Weakness or extreme fatigue  Giddiness  Nausea  Head ache  Low weak pulse Treatment  Resting in a cool environment where there is free flowing, dry air usually remediates the symptoms quickly.

17 General Dilution Ventilation17 Acute Heat Disorders 3. Heat cramps  Characterized by spasms in skeletal muscles  Occurs in people when body water and electrolyte levels have not been restored after extended periods of heavy sweating during exercise and/or heat stress Old Treatment  Use more salt at meal times and provide 0.1% salt in drinking water  Salt tablets can also be used Recommended Treatment  Use of electrolytes (Mg, Ca, K)

18 General Dilution Ventilation18 Acute Heat Disorders 4. Heat rash  It is an acute inflammatory skin disease  Occurs commonly in areas of skin folds or where there is abrasive clothing Treatment  The infected areas should be kept dry, unabated and open to free flowing, dry air

19 General Dilution Ventilation19 Heat Strain Measurement The severity of heat strain will vary greatly among people exposed to the same level of heat stress. Acute heat strain is indicated by:  Visible sweating  Discontinued sweating  Elevated heart rate  Elevated deep body temperature  Decreased systemic arterial blood pressure  Personal discomfort  Infrequent urination

20 General Dilution Ventilation20 Heat Stress Measurement Dry-Bulb temperature Temperature as registered by a thermal sensor Natural Wet-Bulb temperature Temperature measured by a thermometer whose bulb is covered by a wetted wick and exposed to natural air movement unshielded from radiation Psychrometric Wet-Bulb temperature Temperature as registered by psychrometer Globe temperature It is the infrared radiant heat transfer measured by a temperature sensor at the center of a 6 inch hollow copper sphere which is painted both on the inside and outside

21 General Dilution Ventilation21 WBGT Index Indoors When radiant heat transfer is negligible WBGT = 0.7(Wet Natural Bulb Temperature) + 0.3(Globe Temperature) Outdoors When there is no source of radiant heat transfer WBGT = 0.7(Wet Natural Bulb Temperature) + 0.2(Globe Temperature) +0.1 (Dry Bulb Temperature)

22 General Dilution Ventilation22 Dilution Ventilation for Fire and Explosion It is necessary that the concentration of vapor in the work area should be below the lower explosive limit (LEL) (preferably<25% LEL). This is for fire and explosion only and not for health hazard Q = 403 * SG *100 *ER * S F /MW * LEL *B Where LEL = lower explosive limit, parts per 100 SG = specific gravity ER = emission rate, pints/min S F = safety factor MW = molecular weight B = constant ( 1 for temperatures up to 250 0 F 0.7 for temperatures > 250 0 F)