Remote access to PVSS projects and security issues DCS computing related issues Peter Chochula.

Similar presentations


Presentation on theme: "Remote access to PVSS projects and security issues DCS computing related issues Peter Chochula."— Presentation transcript:

1 Remote access to PVSS projects and security issues DCS computing related issues Peter Chochula

2 P. Chochula DCS Workshop, CERN, September 2004 2 Computing and Network Infrastructure for Controls (CNIC) – a new CERN-wide working group dealing with security and system management issues has been created ALICE nominated a contact person who will follow the CNIC progress In later phase, the CNIC membership will be expanded to include the domain managers

3 P. Chochula DCS Workshop, CERN, September 2004 3 Main points addressed by CNIC – Phase I Tools for system maintenance (NICEFC, LINUXFC) Tools for setting up and maintaining different controls domains Rules and policies for domains Rules for inter-domain communication Rules for communication between domains and CERN network

4 P. Chochula DCS Workshop, CERN, September 2004 4 CNIC decisions are important for ALICE DCS –We will provide feedback and advertise our experience –we will follow the recommendation and adopt available tools ALICE pre-installation is starting –First deliverables of CNIC are expected for the end of 2005 For the pre-installation ALICE DCS must provide own tools and define own policies, these might be later modified according to CNIC outcome

5 P. Chochula DCS Workshop, CERN, September 2004 5 Main tasks for maintaining the ALICE DCS domain Operating system and software deployment Software maintenance (upgrades and patches) Users management Computer security Remote access to systems Computer Monitoring

6 P. Chochula DCS Workshop, CERN, September 2004 6 Monitoring of DCS computers A CERN-wide effort to provide common computer supervision tools has been started LASER seems to be a system, which will be deployed in the future –ALICE DCS follows the developments and is ready to evaluate the software once it becomes available Simple version of computer monitoring tools based on Framework PCMON will be used in the starting phase of pre-installation

7 P. Chochula DCS Workshop, CERN, September 2004 7 FW PCmon tools LINUX WXP Dead PCMON connection

8 P. Chochula DCS Workshop, CERN, September 2004 8 FW PCmon tools

9 P. Chochula DCS Workshop, CERN, September 2004 9 Operating systems and standard software deployment –Computer infrastructure for pre-installation will be mostly based on Windows –Windows Server 2003 will be our server platform –ALICE DCS will operate on own Windows domain (decoupled from NICE)

10 P. Chochula DCS Workshop, CERN, September 2004 10 Software installation ALICE DCS purchased licenses for Windows Server 2003 RIS – Remote Installation Service is presently evaluated –Remote boot using the PXE protocol built-in on recent computers boot floppy available for 32 mostly used network cards –if needed –Pre-configured template operating system will be loaded from the server at installation time –Standard software will be deployed automatically after OS installation

11 P. Chochula DCS Workshop, CERN, September 2004 11 Need for standardization of software versions and target paths (see talk related to conventions, presented at this workshop) –RIS assumes a standard destination for software, relicts on target drive will be wiped out) –Automatic installation of PVSS and standard software will follow after OS deployment

12 P. Chochula DCS Workshop, CERN, September 2004 12 Software maintenance Deployment of patches is a complicated task –Possible interference with installed software must be understood in advance –Installation of patches must not harm the controls system As a consequence the NICE procedures are not applicable for DCS ALICE DCS computer will use own patch deployment policies based on SUS

13 P. Chochula DCS Workshop, CERN, September 2004 13 SUS – Software Update Services Standard software update services use the following scenario: –Update server publishes a list of available updates –Workstations connect periodically to this server and download the software ALICE DCS SUS server downloads all patches from Microsoft Only patches approved by administrator are published (become visible) for workstations in the DCS domain

14 P. Chochula DCS Workshop, CERN, September 2004 14 ALICE SUS server (pcaitdc14) Approved patch

15 P. Chochula DCS Workshop, CERN, September 2004 15 How to assure, that the patches have been correctly deployed? If for some reason patch deployment fails, this must be detected and corrected –Need for remote scanning Microsoft baseline security analyzer has been evaluated –MBSA connects to SUS server and receives a list of approved patches –MBSA scans workstations and checks the presence of required software –In addition, MBSA scans for system vulnerabilities (like opened ports, dangerous – unprotected shares, missing policies etc.)

16 P. Chochula DCS Workshop, CERN, September 2004 16 MBSA for ALICE DCS Computer to be scanned Scanning of a range is also possible SUS Server

17 P. Chochula DCS Workshop, CERN, September 2004 17 MBSA – security report

18 P. Chochula DCS Workshop, CERN, September 2004 18 MBSA – problem tracking

19 P. Chochula DCS Workshop, CERN, September 2004 19 Additional security related topics MBSA checks for existing vulnerabilities. In fact a hacker could do the same Intrusion detection is also needed –First level of protection is provided by CERN security team –Second level - network attack countermeasures will be applied for ALICE DCS SNORT – intrusion detection system is being evaluated Hardware protection (firewall), etc. are being studied –Antivirus protection will be needed (interference with running systems is studied –Deployment of user’s software will be possible only via central DCS server

20 P. Chochula DCS Workshop, CERN, September 2004 20 Remote access to controls system Windows Terminal server has been evaluated as an option Clients exist (and were tested) for different platforms including –All flavours of Windows –Linux –MAC OS Remote user will establish a secure RDP connection to Terminal Server and from here he will connect to the DCS system using PVSS Remote UI

21 P. Chochula DCS Workshop, CERN, September 2004 21 Windows Server 2003 Example: Remote access to temperature monitoring system Simplified panel for remote monitoring DCS Device Access Complex panel for DCS operator Secure (ssh) connection between PVSS managers Secure (RDP) connection Firewall

22 P. Chochula DCS Workshop, CERN, September 2004 22 Evaluation of the Terminal Server technology Extensive tests have been performed this summer –Naomi van der Kolk – DCS summer student Influence of remote UI on performance of the Terminal Server and Master DCS project has been studied Involved computers were monitor via modified Framework PCMON tool

23 P. Chochula DCS Workshop, CERN, September 2004 23 Terminal server test setup Powerful computer (2x Xeon 2.8 GHz, 3 GB RAM) running Windows 2003 Server has been used as a terminal server Master project was running on P-IV 3 GHz equipped with 1 GB RAM A number of P-IV computers were used as remote user stations In test we studied impact of remote connections on CPU utilization and memory allocation on Terminal Server, remote user station and Master Project

24 P. Chochula DCS Workshop, CERN, September 2004 24 Windows Server 2003 Windows Server 2003 Windows XP Pro Windows XP Pro Windows XP Pro Computer Infrastructure for Remote Access Tests DCS Private Net. 192.168.39.0 CERN Net. Terminal serverRouter PVSS Master Project Remote User Windows XP Pro

25 P. Chochula DCS Workshop, CERN, September 2004 25 Performed tests Master project generated 50000 datapoints and updated 3000 of them each second Remote user displayed 50 or 200 of them Tests were performed for –Different number of remote sessions –Different number of datapoints updated on remote screen Connections were made to a busy and “idling” master project

26 P. Chochula DCS Workshop, CERN, September 2004 26 Terminal Server Load Master project stopped Master project running Remote panel displays 50 values Remote panel displays 200 values Master project generated 50000 datapoints and updated 3000 /s

27 P. Chochula DCS Workshop, CERN, September 2004 27 Load of the workstation running the master project Remote client disconected Remote client connected Master project stopped Master project running

28 P. Chochula DCS Workshop, CERN, September 2004 28 Computer loads for large number of remote clients Terminal Server #clients Average CPU load [%] Mem [kB] 6011.2 2781282 5511.0 2788719 4513.8 2790181 3512.0 2672998 259.7 2067242 157.2 1448779 54.2 934763 04.9 666914 Workstation running the DCS project #clients Average CPU load [%] Mem [kB] 6085.1579666 5586.6 579829 4584.9579690 3581.3579405 2580.9 579384 1581.4 579463 583.0580003 083.7579691 Master project generated 50000 datapoints and updated 3000 /s. Remote client displayed 50 values at a time

29 P. Chochula DCS Workshop, CERN, September 2004 29 Conclusions on TS tests No performance problems were observed for master project TS load depends on number of external connections. –CPU of TS easily supported up to 60 external connections (no tests were made beyond this number) – Memory consumption was measured to be ~80MB per remote session. Memory paging did not cause observable drop of remote display performance ALICE DCS will deploy TS in pre-installation phase and communicate results to CNIC

30 P. Chochula DCS Workshop, CERN, September 2004 30 Standard services provided by ALICE server(s) DCS domain controller RIS patch deployment security scans and intrusion detection DIM name service WEB service, Internet name service Remote access to PVSS projects Tools for deployment of user’s software TFTPD – for CAEN firmware upgrades … please express you needs …

31 P. Chochula DCS Workshop, CERN, September 2004 31 This slide is important All software needs to be carefully tested before its deployment on DVS network –Unlike the other online systems, the DCS need to use a large number of third-party software –Some components (DIM servers, OPC servers) may badly interfere with software patches A test setup in the DCS lab will be used to test the software We need your software well in advance

32 P. Chochula DCS Workshop, CERN, September 2004 32 Conclusions Computing infrastructure is getting ready for pre- installation Windows Server 2003 will be our server platform Provided services will cover RIS, software updates and security scans, DCS related services and remote access Computer monitoring will be based on FW PCMON, possibility for transition to other tools (e.g. Laser) will be evaluated Quality of service depends on user’s feedback – we cannot prepare for “secret” requests

33 P. Chochula DCS Workshop, CERN, September 2004 33 Computing related questions CO1: Which operating systems do you plan to use in your DCS. Please specify also the OS versions and the hardware platforms. Present standards are Windows XP SP1 and CERN RedHat 7.3.4 –Longhorn and CEL3 will be the successors –SP2 will be deployed soon – presently it is being tested with PVSS We need to know your requirements, especially if you need to install some non-standard systems (but this is strongly discouraged)

34 P. Chochula DCS Workshop, CERN, September 2004 34 Computing related questions CO2: which applications besides the PVSS-II do you need to run on your computers? (Please list all software packages, also the obvious ones (like root, MS Office etc.)) The list is essential for preparation of software deployment policies The software must be tested with the rest of the DCS We need to understand the dangers (e.g. even a harmless installation of C++ compiler could cause a serious security risk – flaw in embedded SQL server)

35 P. Chochula DCS Workshop, CERN, September 2004 35 Computing related questions CO3: what are your requirements for remote access to the DCS system (please give details on number of remotely monitored parameters, frequency of their updates, and number of simultaneous remote sessions). You input is needed for correct infrastructure planning

36 P. Chochula DCS Workshop, CERN, September 2004 36 Computing related questions CO4: What are the requirements for additional data storage on DCS computers? CO5: Which remote systems (located at CERN) do you need to access from the DCS network? (e.g LXPLUS etc.) We need to define archiving (backup) policies Secure access to remote systems has to be provided