Presentation is loading. Please wait.

Presentation is loading. Please wait.

2008 AQV, EH, DH and FJM Inverter Application, Installation,

Similar presentations


Presentation on theme: "2008 AQV, EH, DH and FJM Inverter Application, Installation,"— Presentation transcript:

1 2008 AQV, EH, DH and FJM Inverter Application, Installation,
Samsung Mini Splits 2008 AQV, EH, DH and FJM Inverter Application, Installation, Sept

2 General Indoor & Single Zone Outdoor Installation

3 High Wall Installation Requirements
Standard Mini Split Mantras about unit location still apply Indoor units MUST be installed a minimum of 5ft from the floor – these units are NOT PTAC’s Allow the airflow to spread throughout the room Remote control has a range of about 20ft NO NO

4 Install unit on Wall Use mounting templates provided
Drill a 3” hole at approx 5° slant down towards the outside Remove Wall Bracket from unit and attach to the wall – make sure it is level Once bracket is attached slightly bend unit mounting tabs outwards to help in attaching the unit

5 Installing High Wall Indoor Unit
Gently rotate line set stubs to the required (vertical) position Locate condensate hose and tape it to line set BELOW refrigerant lines Feed both electrical wires in from Outside and run through connection into the unit – keep on opposite sides of the line set as much as possible

6 Installing High Wall Indoor Unit
Tape electric wires to line stubs Lift unit, feed line sets & wire through the hole and attach unit to the mounting bracket On outside of building then bend line set stubs to desired direction towards Outdoor unit Ensure that line set is not kinked Condensate hose connection fits a 5/8” ID or ¾” OD clear vinyl hose – use this to transition to rigid (per local codes) – Always use rigid for horizontal slope 1” in 12” towards building drain

7 Installing Ducted Indoor Unit
Template to mark position of threaded rods to support unit is provided with the unit Ensure rods are capable of supporting unit weight Ensure that the unit is slightly pitched (1/4”) towards the drain to help condensate removal Make sure that a minimum of ¼” clearance exists between the top of the drop ceiling and the unit to prevent noise issues

8 Installing Ducted Indoor Unit
All refrigerant piping, drain & electrical connections are on the RHS of the unit Condensate drain connection uses the provided flexible connector – an 1 1/4” clear vinyl hose can be used to adapt to rigid condensate piping Gravity drain is standard, Condensate pump is an option – Samsung pump fits inside the unit

9 Installing Ducted Indoor Unit
Return air ductwork can be either free or ducted to the rear or bottom as required – ductwork added to the return will need to be subtracted from total length of ducting on the system Free return recommended Filtration is not supplied with the unit Field installed filtration must be installed - either at the unit or field installed at the return air grille

10 Installing EH/MH Indoor Unit
Supply Air Duct Connection EH035 6” x 33 ¾” EH 052/ /16” x 31 ½” Flange provided to adapt a transition piece from unit to duct trunk TOTAL Static pressure available EH ” WC EH 052/ ” WC Equals 15ft to 20ft of 8” trunk with 4 x 6ft runs of 6” flex with ceiling registers (assuming free return)

11 Installing DH Indoor Unit
Supply Air Duct Connection DH ” x 35 1/2” DH140 10” x 39 3/8” Flange provided to adapt a transition piece from unit to duct trunk TOTAL Static pressure available DH105 & ” WC Factory set to 0.3” WC, fan speed can be set for higher or lower static pressures using option codes Equals 40ft of 8” trunk with 6 x 6ft runs of 6” flex with ceiling registers (assuming free return)

12 Single Zone Outdoor Installation
Maximum line set lengths and lifts must be respected Line set sizing CANNOT be altered AQV 09/12 ¼” & 3/8” 50ft Total inc 25ft Lift AQV 18 ¼” & ½” 100ft Total inc 65ft Lift AQV 24 ¼” & 5/8” 100ft Total inc 65ft Lift AQV 36 ¼” & 5/8” 162ft Total inc 98ft Lift EH 035 ¼” & 3/8” 65ft Total inc 39ft Lift EH 052 ¼” & ½” 100ft Total inc 65ft Lift EH ¼” & 5/8” 100ft Total inc 65ft Lift DH /8” & 5/8” 246ft Total inc 98ft Lift DH140 3/8” & ¾” 246ft Total inc 98ft Lift No Brazing please, Flare connections If lifting greater than 25ft – trap for oil return is required Both line sets MUST be insulated No Sight Glasses or Filter Driers

13 Outdoor Installation Requirements
Unit clearances 6” Behind and on LHS 24” In Front and on RHS (Service access) Units can be stacked but easiest service access is to take the top panel off Check breaker size required Raise up Outdoor unit 4 to 6” from the pad/ground to help drain the unit after a defrost

14 Electrical Power AQV 09 - 208/230V-1Ph-60Hz, 15A
EH /230V-1Ph-60Hz, 20A EH /230V-1PH-60Hz, 25A EH /230V-1Ph-60Hz, 30A DH /230V-1Ph-60Hz, 35A DH /230V-1Ph-60Hz, 40A Units are sensitive to power issues, minimum voltage 197V, Maximum voltage 253V, low voltage to the unit can cause error codes Units MUST be grounded otherwise it could cause error codes

15 Wiring Requirements Power Wiring
Wire Breaker to L, N and Ground (Earth) even though it is 230V Outdoor unit powers Indoor unit use 14-3 Wire Wire 1 to 1 and 2 to 2 and Ground MUST USE A SEPARATE WIRE FOR POWER & CONTROL BETWEEN OUTDOOR AND INDOOR UNITS

16 Out to In Wiring Requirements
Control Wiring Use 16AWG Shielded wire for controls Wire F1 to F1 and F2 to F2 No J Boxes Keep control wiring away from light fittings and other high voltage equipment to prevent interference and possible communication issues

17 Ducted Unit Wiring to Remote
Wiring to RMC V1 – V2 is 12VDC power for the wired controller F3 – F4 is the communication to the wired remote Use 2 Sets of wires, one for power and one for communication Rotary Switches LEAVE BOTH ALONE!!! – factory default settings are used Dip Switches 1 OFF Wired Remote 4 OFF Condensate Pump 7 OFF Hot Water Coil 11 OFF Remote start/stop

18 EH Wiring - Controller MWR-TH01 Wired Controller
Use 16AWG Shielded wire 4 wire connection Wire F3 to F3 and F4 to F4 for communication V1 – V2 is 12VDC power for the wired controller Can be mounted up to 1000ft away from the unit, does not sense temperature (done at the unit) Leave Rotary Switch at 0 Dip switches standard settings 1 OFF Heat Pump 2 OFF F3-F4 3 OFF DegF 4 ON Wired Remote only

19 DH Wiring - Controller MWR-WS00 Wired Controller
Use 16AWG Shielded wire 2 sets of 2 wire connection Wire F3 to F3 and F4 to F4 for communication Red = F3, Blue = F4 V1 – V2 is 12VDC power for the wired controller Yellow = V1, Orange = V2 Dip switches standard settings 1 OFF Heat Pump 2 ON Wired Remote 3 OFF Master 4 ON DegF 5 OFF Indoor unit temp 6 OFF 7 OFF 8 OFF Monitor fault codes

20 Evacuation Requirements
Units are all R410A NEED 5/16” GAUGE ADAPTOR to attach gauges to the single Schrader connection Recommend 200 Micron minimum with double evacuation, break with Nitrogen or other dry gas Keep system open time to a minimum to prevent moisture problems

21 AQV Charging Requirements
All Units are charged for 25ft line set as standard Add NO R410A to AQV 09/12 up to the max line set length of 50ft Add 0.15oz/ft for AQV 18 line sets over 25ft Add 0.15oz/ft of R410A for AQV24 line sets over 25ft UNIT LINE SET RUN 25’ 40’ 50’ 60’ 80’ 100’ AQV N/A N/A N/A AQV N/A N/A N/A AQV AQV AQV ADDITIONAL R410A MUST BE WEIGHED IN – USE A DIGITAL SCALE

22 EH/DH Charging Requirements
All Units are charged for 25ft line set as standard Add NO R410A for EH 035 up to 50ft line set then add 0.15oz/ft up to 65ft line set maximum length Add 0.2oz/ft for EH 052 Add 0.1oz/ft for EH 070 Add 0.4oz/ft for DH 105/140 UNIT LINE SET RUN 25’ 40’ 50’ 60’ 65’ 80’ 100’ EH N/A N/A EH EH DH105/ ADDITIONAL R410A MUST BE WEIGHED IN – USE A DIGITAL SCALE

23 Start Up – AQV09-24 Push the K1 Button
Trial Run will start or stop as follows. 1 x PUSH START in COOLING mode 2 x PUSH START in HEATING mode 3 x PUSH STOP Once the compressor has been stopped the next start will be delayed 3 min due to the Anti Short cycle timer protection. Compressor will run following frequency during the 60 minute Trial Run mode AQV09 : 50Hz AQV12 : 74Hz AQV18 : 52Hz AQV24 : 61Hz

24 Start Up – EH Units Push the K1 Button
Trial Run will start or stop as follows. 1 x PUSH START in COOLING mode 2 x PUSH START in HEATING mode 3 x PUSH STOP Once the compressor has been stopped the next start will be delayed 3 min due to the Anti Short cycle timer protection.

25 Start Up – AQV36, DH & CH Units
Trial Run will start or stop as follows. K1 x PUSH START in HEATING mode K2 x PUSH START in COOLING mode K3 x PUSH STOP or RESET K4 x PUSH DATA VIEWER Once the compressor has been stopped the next start will be delayed 3 min due to the Anti Short cycle timer protection.

26 Free Joint Multi Installation Specifics

27 FJM 080 model REACTOR Controller sample 485 communication SMPS
Inverter Control Cycle Control IPM PFC Diode PFC IGBT Bridge Diode heatsink REACTOR Fan-motor Heat Exchanger Inverter (Control Box) BLDC Compressor Reactor CAPACITOR Shunt Resistor EMI FILTER - 27 -

28 Line Set Issues 050 Outdoor unit Maximum total line set is 100ft
Maximum Individual line set to an Indoor unit is 50ft Connection sizes 2 x 3/8” Suction 2 x ¼” Expanded Gas Both sets of lines must be insulated

29 Line Set Issues 080 Outdoor unit
Maximum total line set for all units is 225ft Maximum Individual line set to an Indoor unit is 75ft Connection sizes 1 x 1/2” Suction 3 x 3/8” Suction 4 x ¼” Expanded Gas All sets of lines must be insulated

30 Line Set Issues 080 Outdoor unit
Single Service Valve for Liquid and Suction lines Unused connections must be left untouched Always start to install from the uppermost set of connections – this is unit A, then B, C and the lower set of connections is D

31 Line Set Sizing Capacity Suction Expanded 9,000 Btu/h 3/8” ¼”
When using the 080 with 4 x 9k Indoor units, it has a ½” suction connection, so included in the Outdoor unit is a small connector to sleeve down from ½” to 3/8” piping

32 Wiring - Power 208-230V – 1Ph – 60Hz 050 uses a 20A breaker
Each Indoor unit is fed power individually, not required to be sequenced 1 on Outdoor to 1 on Indoor, 2 on Outdoor to 2 on Outdoor – this is very important

33 Wiring - Control RS485 communication
F1 & F2 communication 16AWG Shielded wire F1 to F1, F2 to F2, does not matter which unit is connected to which terminal as long as F1 to F1, F2 to F2 Try to separate the controls wiring at least 2” from the power wiring

34 Evacuation Each Indoor unit has it’s own EEV in the Outdoor
050 Outdoor unit Each Indoor unit has a separated set of Suction and Liquid service valves Both Need a R410A adaptor Evacuates the individual Indoor unit and line set connected to the service valves 400 Micron minimum

35 Evacuation Each Indoor unit has it’s own EEV 080 Outdoor unit
There is a single Suction and Liquid shut off valve Needs R410A adaptor Evacuates all Indoor units and line sets connected to the manifold assembly 400 micron minimum

36 Charging – 050 Outdoor unit
Outdoor unit is charged for 65ft total (of all line sets) Add 0.1oz R410A per foot over the 65ft total line length, it does not matter which capacity of Indoor unit is connected the total line set length only is important 60ft 70ft 80ft 90ft 100ft Add 0.1oz/ft over 65ft combined length

37 Charging – 080 Outdoor unit
Outdoor unit is charged for 131ft total (of all line sets) Add 0.1oz R410A per foot over the 131ft total line length, it does not matter which capacity of Indoor unit is connected the total line set length only is important 130ft 150ft 170ft 190ft 210ft 225ft Add 0.1oz/ft over 131ft combined length

38 Auto Addressing Mode Step 1
Rotary switch signifies # of Indoor units connected to Outdoor Set the rotary switch to the # of units, either 2, 3 or 4 Step 2 Auto Addressing Indoor units rotary switches do not need to be altered Leave all Dip switches on the Outdoor unit to the factory settings

39 Step 2 - Auto Address function
Step 2 Cont Turn on the unit, it will start a count to check communications with all Indoor units LH display will count 00 to 15 Once Indoor units are tracked it will scroll 00 as it finds the Indoors

40 Step 2 - Auto Address function
Step 2 Cont Unit will now display E199 asking for a pipe check MWR-WS00 will display E599 Press K1 switch once This starts the auto addressing mode Display will show |-5 Compressor will start and the unit will open each EEV in turn to check that the correct indoor unit is connected to the correct EEV Unit will display on other LED the results scrolling 00, 01, 02, 03 as it establish communication

41 Step 3 - Auto Address function
Once completed it will display an OK signal, now the unit can be run in test mode, either Cooling or Heating Press K2 Button ONCE for Heating Trial mode : Display will show |-1 Press K2 Button TWICE to add refrigerant : Display will now show |-2 Press K2 Button THREE times for Cooling trial mode : Display will now show |-3 Press K2 Button FOUR times for Pump Down mode : Display will now show |-4

42 Manual Addressing Mode
Step 1 Manual addressing is used when a BMS system is used or Ducted and Wall Mount units have Wired Remote controls Set the rotary switch to the # of units, either 2, 3 or 4 Step 2 Manual Addressing Set Dip Switch #1 on Outdoor unit to OFF

43 Manual Addressing Mode
Step 3 On Indoor units set SW01 the MAIN address to the following based on which set of refrigerant connections the unit is piped to Unit piped to the top set of connections = 0 Unit piped to the second set of connections from top = 1 Unit piped to the third set of connections from top = 2 Unit Piped to the lowest set of connections = 3 System can now be powered up

44 Manual Addressing Mode
Step 4 On initial power up LH display will scroll 00 Through 15 Once Indoor units are tracked LH display will show 00, 01, 02 and 03 depending how many Indoor units are installed Step 5 Press K1 for a Pipe Check, although this is not strictly necessary Use the K2 Button to put the unit into either Cooling or Heating trial mode

45 Wired Controllers Step 1
Indoor units set SW02 the RMC address to the following based on which set of refrigerant connections the unit is piped to Indoor Unit piped to the top set of connections = 0 Indoor Unit piped to the second set of connections from top = 1 Indoor Unit piped to the third set of connections from top = 2 Indoor Unit Piped to the lowest set of connections = 3 Dip Switch #1 should be in the OFF position (MANDATORY on the FECA Ducted unit)

46 MH Wiring - Controller MWR-WS00 Wired Controller
Use 16AWG Shielded wire 2 sets of 2 wire connection Wire F3 to F3 and F4 to F4 for communication Red = F3, Blue = F4 V1 – V2 is 12VDC power for the wired controller Yellow = V1, Orange = V2 Dip switches standard settings 1 OFF Heat Pump 2 ON Wired Remote 3 OFF Master 4 ON DegF 5 OFF Indoor unit temp 6 OFF 7 OFF 8 OFF Monitor fault codes

47 Maintenance - Filters AQV Silver Nano Filter is permanent and washable, clean every month AQV Electro Static and Carbon Filters are also washable – changed from previous models Suggested cleaning schedule for ALL filters is every month – only use the optional filters when cooling people, machines don’t care about smells and pollen

48 Literature Available Sales brochure (Color) Product Submittals
Basic Application and Technical Guide & Samsung 108, teaching sizing, usage and basic installation techniques Warranty Booklet – Everything about Warranty Installation and Operation Manuals Service Manuals – very important as these units are self diagnostic

49 Thanks for attending Any Questions??????????


Download ppt "2008 AQV, EH, DH and FJM Inverter Application, Installation,"

Similar presentations


Ads by Google