Download presentation
Presentation is loading. Please wait.
1
April 2000 RTU S900
2
S900 Remote Terminal Unit RTU S900
The S900 is also available on Sequence of Event Recorder (SER) version.
3
RTU S900 S900 view. All the module are plugged by the front of the rack.
4
FUNCTIONAL DESCRIPTION CONFIGURATION HARDWARE DESIGN FEATURES TOOLS
RTU S900 OBJECT GENERAL ARCHITECTURE FUNCTIONAL DESCRIPTION CONFIGURATION HARDWARE DESIGN FEATURES TOOLS
5
RTU S900 GENERAL
6
Transmission and distribution applications Medium to large systems
RTU S900 MARKETS Transmission and distribution applications Medium to large systems Generation (local control - data logging) Digital control command for substations
7
Process control (programmable logic)
RTU S900 MAIN FUNCTIONS SCADA Local control Data logging Process control (programmable logic)
8
Distributed architecture (hardware and software) Open ended
RTU S900 MAIN FEATURES Powerful Distributed architecture (hardware and software) Open ended Compliance with international standards Modularity Flexibility (hardware is customised through software) Low power consumption
9
RTU S900 TECHNOLOGY
10
MAIN TECHNOLOGY CHOICES
RTU S900 MAIN TECHNOLOGY CHOICES 68020 Microprocessors in each CPU VME bus FIP Field Bus Real time Multitask Operating System : VRTX32 Data Base Management using ORACLE Performing automatic controls based on ISaGRAF Generalisation of Personal Computer for customer's tools Each rack is equip with 1 CPU unit. The CPU unit managed all the RTU functions Data acquisition Communication with SCADA / IEDs Automatism
11
RTU S900 SYSTEM ARCHITECTURE
12
RTU S900 SYSTEM ARCHITECTURE Main Rack S 900
13
RTU S900 S 900 Field Bus FIP Distributed Racks Main Rack
The maximum rack number is 32 The maximum distance between the first and last rack is 4 km The Main rack is master the secondary are slave The master show the information from all the racks The slave can control only the local data (by module or communication acquisition)
14
RTU S900 S 900 Field Bus FIP Distributed Racks Main Rack Substation
Each rack can supervise IEDs Substation Substation IEDs IEDs IEDs
15
RTU S900 Control centre 1 S 900 Field Bus FIP Distributed Racks
Main Rack S 900 The control centre1 is always connected the the main rack Substation Substation IEDs IEDs IEDs
16
RTU S900 Control Control centre 1 centre 2 S 900 Field Bus FIP
Distributed Racks Main Rack S 900 The control centre1 and 2 are always connected to the main rack Substation Substation IEDs IEDs IEDs
17
RTU S900 Local Control Control Control centre 1 centre 2 S 900
Data Base Generation Graphical Control Field Bus FIP Distributed Racks Main Rack S 900 The local control is managed by the RTU like the 2 remote control centre The local control can be replace by a third remote control centre ALSTOM T&D Protection& Control provide for the local control the software PROCETT 5000W Substation Substation IEDs IEDs IEDs
18
RTU S900 Local Control Control Control centre 1 centre 2 S 900
Data Base Generation Graphical Control Field Bus FIP Distributed Racks Data logging Main Rack S 900 The main rack can supervise up to 2 printers The Alphanumeric control provide the following functions: Data control Event file access RTU status Command The Alphanumeric control can be used in local by by PSTN Substation Substation Alphanumeric. Control IEDs IEDs IEDs
19
RTU S900 Local Control Control Control centre 1 centre 2 S 900
External Clock Local Control Control centre 1 Control centre 2 Data Base Generation Graphical Control Field Bus FIP Distributed Racks Data logging Main Rack S 900 The RTU used for the external clock a serial link input on the main rack Substation Substation Alphanumeric. Control IEDs IEDs IEDs
20
RTU S900 INTERNAL ARCHITECTURE
21
RTU S900 SYSTEM ARCHITECTURE
VME BUS CPU + Power supply FIP Interface Field Main rack FIP BUS Secondary or Distributed rack It is the minimum module number to start the RTU CPU + Power supply FIP Interface VME BUS
22
RTU S900 VME BUS CPU + FIP Interface I/O I/O I/O I/O Field Main rack
Power supply FIP Interface I/O I/O I/O I/O Field Main rack FIP BUS Secondary or Distributed rack I/O I/O I/O I/O CPU + Power supply FIP Interface VME BUS
23
RTU S900 Clock Local control Data logging CONTROL CENTRES External Modem IEDs Serial Async Unit Serial Async Unit Serial Async Unit VME BUS CPU + Power supply FIP Interface I/O I/O I/O I/O Field Main rack FIP BUS Secondary or Distributed rack The communication module in the main rack assure the following functions: SCADA communication IEDs communication Printer control Alphanumeric terminal control External clock synchronisation link The communication module in the secondary racks assure the following functions: I/O I/O I/O I/O CPU + Power supply FIP Interface VME BUS Serial Async Unit IEDs
24
FUNCTIONAL DESCRIPTION REMOTE CONTROL PROTECTION SUPERVISION
RTU S900 FUNCTIONAL DESCRIPTION REMOTE CONTROL PROTECTION SUPERVISION FIP NETWORK DATA CAPTURE SEQUENCE AUTOMATION LOCAL CONTROL TIME SYNCHRONIZATION FAULT PROCESSING
25
RTU S900 REMOTE CONTROL
26
RTU S900 REMOTE CONTROL With one, two or three control centres
(SCADA) With one, two or three control centres Two links with CC can be duplicated Internal or external MODEMS Half or full duplex Point-to-point or multidrop Multi-Protocol capability IEC DNP 3 HNZ Private protocol / consult us S900 RTU
27
RTU S900 PROTECTION SUPERVISION
28
RTU S900 PROTECTIONS OR IEDs SUPERVISION Secondary Main Substation
racks Main Substation rack FIP Field Bus SAU 900 board To SAU 900 KITZ 101/201 G E C A L S T H O M T&D G E C A L S T H O M T&D OPN A9311 F + - OPN A9311 F + - RS232/485 converter The communication link to IEDs are managed by the SAU900 (4 serial link module). The maximum number of SAU900 control by the RTU (all the rack) is equal to 8 modules (32 serial links). Each rack can support many protocol in same time on the same SAU900. To connect IEDs in Modbus it is necessary to add an external converter RS232/RS485. To connect IEDs in K-Bus Courier it is necessary to add an external KITZ101 or 201. Kbus link to K relays/EPAC/MiCOM Pxxx Modbus link to MODN/MiCOM Pxxx Optical star (optional) OPN A9311 F + - OPN A9311 F + - OPN A9311 F + - G E C A L S T H O M T&D G E C A L S T H O M T&D Modbus link to MODN/MiCOM Pxxx Kbus link to K relays/EPAC/MiCOM Pxxx IEC (VDEW) link to IEDs
29
RTU S900 PROTOCOLS Communicate Protocols forward IEDs or Relays
IEC (VDEW) Maximum distance = 1.4 km IEC Maximum distance = 100 m Maximum distance > 10 km with external modem Modbus standard Maximum distance = 1.2 km Modbus with transmission of time-tagged events K-Bus Courier through external KITZ101/201 Maximum distance = 1 km Each rack can support all the protocols in same time (1 communication protocol per serial link).
30
RTU S900 CAPACITY Up to 256 devices (numerical protections or IEDs)
Up to 32 devices per subnetwork Up to 32 subnetworks per RTU Up to baud per serial link (SAS900 and SAU900) Up to baud for the serial link velocity summation (*) Several protocols managed in the same time Signalling (RS), Controls (RC), Measurements (RM) Numerical protections synchronised by the RTU (*) per rack The maximum protection number managed by the RTU (all the rack) is equal to 256. It is possible to connect up to 32 relays per serial link. Due to the communication characteristics (polling) to assure a access time < 1s, we recommend to limit the number to 10 relays per serial link. The maximum velocity per serial link is 9600 baud. The sum of the communication links per rack shall be =< baud. It is not possible to transfer by the RTU disturbance or setting files from the relays. By using in K-Bus Courier communication protocol the KITZ201(2 separate link, 1 to the RTU and the other to a setting station) it is possible to provide a complete solution including remote setting.
31
PROTECTION SETTING FAULT ANALYSE
RTU S900 PROTECTION SETTING FAULT ANALYSE With K-Bus Courier compatible devices To SCADA S900 main rack RS232 Modem Remote Engineer Substation Setting change Configuration Disturbance Event record measurement RS232 Modem G E C A L S T H O M T&D G E C A L S T H O M T&D G E C A L S T H O M T&D KITZ 201 RS232 Solution to realise remote setting and disturbance analyse in K-Bus Courier using external KITZ201 Local Engineer Substation Setting change Configuration Disturbance Event record measurement K-Bus Address
32
PROTECTION SETTING FAULT ANALYSE
RTU S900 PROTECTION SETTING FAULT ANALYSE With VDEW compatible devices To SCADA S900 main rack RS232 Modem Remote or Local Engineer Substation Setting change Configuration Disturbance Event record measurement RS232 Modem G E C A L S T H O M T&D G E C A L S T H O M T&D G E C A L S T H O M T&D K-Bus Address
33
RTU S900 FIP BUS
34
RTU S900 FIP BUS (1) Main rack Secondary racks l1 l2 Lmax = 1km
31 secondary racks at the maximum Data rate = 1 Mbits/s Electrical network 2 m < l1 < 10 m l2 > 4m This FIP scheme is only available in case of distributed architecture. If the rack are install in a same cubicle the I1 and I2 limitation don’t exist. With a distance < 1 km it is not necessary to use network amplifier.
35
RTU S900 FIP BUS (2) Secondary racks Main rack Secondary racks
Transmitter l1 T T T l2 Lmax = 1km Lmax = 4 km By using external amplifier, it is possible to increase the distance to 4 km. 31 secondary racks at the maximum Data rate = 1 Mbits/s Electrical network 2 m < l1 < 10 m l2 > 4m
36
RTU S900 FIP BUS (3) Secondary racks Main rack Secondary racks
Electrical optical converter Transmitter l1 Optical T C C l2 Lmax = 1km Lmax = 1.6 km Lmax = 5.6 km It is possible by using external Electrical / Optical converter to include an optical part in the FIP network. 31 secondary racks at the maximum Data rate = 1 Mbits/s Mixed network (electrical / optical) 2 m < l1 < 10 m l2 > 4m
37
RTU S900 DATA CAPTURE
38
RTU S900 PROCESSED ENTITIES Digital inputs (signals)
Digital outputs (controls) Analog measurements Digital measurements Analog setpoints Digital setpoints Pulse counting (meters) Tap changer positions Internal and Grouped signals Bay and Substations
39
DIGITAL INPUTS (SIGNALS)
RTU S900 DIGITAL INPUTS (SIGNALS) TYPES Single, Double Normal, Reverse Transient FILTERING State changes Complementary faults (short & long) Fleeting points SENDING OUT Communication Archives, Logging Activation of an alarm loop Filtering State changes: Settable from 1 to 50 ms Complementary: Settable from 100 ms to 30s Fleeting: Many state changes during a fixed delay Each digital inputs can be by setting (in the database) send to the SCADA, the local HMI, store in the permanent file memory, printing and affect to an alarm loop 3 settable alarm loops are available on the CPU module
40
DIGITAL OUTPUTS (CONTROLS)
RTU S900 DIGITAL OUTPUTS (CONTROLS) TYPES Single, Double Transient, Continuous FILTERING Non existence in Data Base Bay or Substation under local control Control of activity from originator EXECUTION Hardware check Direct execution Select Before Operate Transient delay is settable from 0.1 to 15s
41
RTU S900 MEASUREMENTS ANALOGUES Current , Voltage
Software correction of offset, gain and linearity DIGITALS 16 or 32 bits BCD, Binary, Gray and 1-among-N acquisition TREATMENTS Threshold violation, dead band, overflow Scaling (linear or quadratic) Communication (cyclic, state change) Archives, Logging, alarm loop
42
RTU S900 SETPOINTS ANALOGUES Current DIGITALS 16 or 32 bits
BCD, Binary, Gray and 1-among-N acquisition FILTERING Non existence in Data Base Bay or Substation under local control Control of activity from originator EXECUTION Hardware check Stepless transmission or linear execution
43
RTU S900 COUNTINGS TYPES Single Double (use of a complemented input)
FILTERING Confirmation of pulse change Complementary faults for double counting TREATMENTS Storing timing cumulative periods Forcing to a preset value Freeze from Control Centre Communication Scaling, Local reports The counting inputs shall be digital states (48 to 220 Vdc). The maximum speed for the counting is 25 Hz per input.
44
RTU S900 TAP CHANGER POSITION TYPES 16 or 32 bits
BCD, 1-among-N and decimal-coded acquisition TREATMENTS Use of one tap transition position or not Checking if the Tap Changer has varied by more than 1 position Communication Archive, Logging
45
INTERNAL AND GROUPED SIGNAL
RTU S900 INTERNAL AND GROUPED SIGNAL INTERNAL SIGNALS Images of system faults Images of internal status Images of logic states GROUPED SIGNALS Logical "OR" of : Signals Other grouped signals Internal signals It is possible in the S900 Database to create internal information (binary or analogue) associated to: RTU status (modules, rack, …) System status (communication, printer, …) Programmable logic (auto-recloser in serve, ….) It is possible in the S900 database to group logical information (internal or external) by an OR logic. If the application require more complex association used the programmable logic based on ISaGRAF.
46
RTU S900 A RTU CAN MANAGE 4 SUBSTATIONS 64 BAYS SUBSTATION
BAYS AND SUBSTATIONS A RTU CAN MANAGE 4 SUBSTATIONS 64 BAYS SUBSTATION May be on local or remote control BAY A printer may be assigned to a bay under local control Each entities is affect in the database to a substation and a bay.
47
INPUT/OUTPUT CAPACITY
RTU S900 INPUT/OUTPUT CAPACITY 4 032 Signals 1 024 Controls 480 Analog inputs 60 Analog setpoints 144 Counters 51 Digital setpoints 51 Digital measurements 51 Tap changer positions Capacity including data from Dedicated input and output modules Input and output coming through serial links Internal input and output calculations (PLC programs) The capacity include data coming from dedicated modules or IEDs.
48
TIME TAGGING & SCANNING
RTU S900 TIME TAGGING & SCANNING Signals - User settable 1 ms 2 ms 5 ms 10 ms Measurement - User settable 1 second for 96 analog inputs The minimum scanning time is for the measurement per rack is equal to 1s per 96 analogue measurements. 1s for inputs < 96 2s for 96 < inputs < 192 3s for 192 < inputs < 288 ...
49
RTU S900 SEQUENCE AUTOMATION
50
RTU S900 Interlocking Load shedding Energy management VAR compensation
FUNCTIONS Interlocking Load shedding Energy management VAR compensation Tripping Auto-recloser Switching sequences Busbar transfer Switchgears control Alarms We recommend to don’t use the programmable logic for reflex automatism (cycle < 100 ms).
51
RTU S900 Software logic interface ISaGRAF
PLC PROGRAMMATION Software logic interface ISaGRAF five defined IEC languages SFC Sequential Function Chart FBD Function Block Diagram LD Ladder Diagram ST Structured Text IL Instruction List ISaGRAF is available on PC with Windows. The PLC program are develop/test on the PC and download in the RTU to be executed every cycle (settable) It is possible to realise an On-line debugging on the RTU by using a serial link between the PC and the S900.
52
RTU S900 User programmable
PERFORMANCES User programmable Centralised automatic functions in the main rack Distributed automatic functions in the secondary racks Cycle : Settable from 10 ms The automatism loading in the main rack can used all the data (main and extended rack). The automatism loading in the extended rack can only used local data. To optimise performance we recommend to distributed the automatism in all the rack For a cycle < 100ms, it is necessary to test all the application to verify the other functionality (CPU charge).
53
RTU S900 LOCAL CONTROL
54
RTU S900 Events (RS,RM,RCT,TP,RC,SP)
DATA ARCHIVES Events (RS,RM,RCT,TP,RC,SP) Faults (communication and hardware) Pulses counting Sorting criteria Sending archives to control centre Possibility to freeze archives from control centre Sequence of events
55
RTU S900 Events file 2000 Faults file 200
DATA ARCHIVES Events file Faults file Accumulator freeze (all counters) The events are store in permanent memory (RAM with battery back up)
56
RTU S900 Possibility to connect up to 2 printers and 1 VDU
DATA LOGGING Possibility to connect up to 2 printers and 1 VDU User friendly MMI on VDU Printing of : Status changes (all entities) Threshold violation Non validity (entities and couplers) Reports of : Entities System faults Sorting criteria
57
RTU S900 LOCAL CONTROL First possibility:
Connection to an alphanumeric terminal : status of system commands controls maintenance information Second possibility: Connection of a personal computer with graphic representation of the substation (Procett 5000W) The alphanumeric terminal can be used in local or in remote for a back-up link (on PSTN).
58
GRAPHIC SUBSTATION CONTROL POINT
RTU S900 GRAPHIC SUBSTATION CONTROL POINT The RTU S900 can be associated to a graphic substation control point: Local graphic Human Machine Interface for electrical substations Real-time multitasking PC-based product Advanced HMI in WINDOWS environment Autonomy of the user (database, graphics) Software & hardware modularity It is possible to use 2 screen This IHM based on PROCETT 5000W can easily evolve in SCADA by adding communication modules in the PC to control remote RTU
59
RTU S900 TIME SYNCHRONISATION
60
RTU S900 SYNCHRONISATION Several possibilities for the time synchronisation of MiCOM S100 By the SCADA By the Local Control Station (serial link) By the RTU (serial link) Each equipment The main rack synchronises the secondary racks by FIP-bus Accuracy: s The RTU synchronises the numerical protections Accuracy: up to 1 ms The Substation Local Control synchronises the RTU Accuracy: 3 ms SCADA RTU secondary racks RTU main rack The RTU use a serial link for the synchronisation with the following protocol: EH90 Broadcast ASCII mode GPS/Others Local Control OPN A9311 F + - OPN A9311 F + - OPN A9311 F + - Numerical protections
61
RTU S900 FAULT PROCESSING & MAINTENANCE
62
RTU S900 Main faults detected are:
FAULT PROCESSING Main faults detected are: Coupler faults (main and secondary racks) IEDs faults (communication or internal failure) Remote control fault (communication) Synchronisation fault Printer faults Complete and permanent control Faults archiving The RTU S900 realise a complete control in less than 2s
63
RTU S900 FAULT SIGNALLING On SCADA On remote maintenance station
On printer The affectation choice (except led) is settable on the Database On local maintenance station On sound alarms LEDs on CPU module
64
RTU S900 CONFIGURATION
65
RTU S900 CONFIGURATION (1) Direct link between S900
and SCADA (Procett 5000W) PROCETT 5000W Remote control station Distance or local link Capacity Up to 32 racks Up to 5000 I/Os Local control station OPN A9311 F + - OPN A9311 F + - OPN A9311 F + - IEDs FIP BUS Standard RTU application OPN A9311 F + - OPN A9311 F + - OPN A9311 F + -
66
RTU S900 CONFIGURATION (2) With a S900 in concentrator Capacity
PROCETT 5000W Remote control station Capacity Up to 9 Sub-RTU Up to 32 racks per Sub-RTU Up to 5000 I/Os Distance or local link S900 Concentrator Application in using a S900 in concentrator It is possible on the concentrator to connect a local control station OPN A9311 F + - OPN A9311 F + - OPN A9311 F + - Local control station FIP BUS Local control station IEDs OPN A9311 F + - OPN A9311 F + - OPN A9311 F + - S900 Sub-RTU n°2 S900 Sub-RTU n°1
67
RTU S900 CONFIGURATION (3) With a concentrator ITE29 Capacity
PROCETT 5000W Remote control station With a concentrator ITE29 Capacity Up to 8 RTU Up to 32 racks per RTU Up to I/Os ITE29 Distance or local link ITE29 Application in using ITE29 concentrator OPN A9311 F + - IEDs OPN A9311 F + - Local control station Local control station OPN A9311 F + - S900 RTU n°3 FIP BUS S900 RTU n°2 S900 RTU n°1
68
RTU S900 HARDWARE DESIGN FEATURE
69
RTU S900 21 slots available per rack Up to 32 racks
S900 Remote Terminal Unit The slot number available for I/O and communication modules is per rack equal to: 21 (total number) - 2 (power supply) - (1 main CPU) = 18 The communication link are available in front face by Subd 9pts 21 slots available per rack Up to 32 racks Communication links on the front face
70
RTU S900 Connection through rear panel DIN connectors
The female DIN connector are fixed to the rack. Connection through rear panel DIN connectors Female connector (96 points DIN to solder)
71
RTU S900 PCU 900- Power Converter Unit 24Vdc:±20% (PCU910)
Output voltage supplied: +5V and ±12V for the VME bus Switched and fused protected Module width: two slots
72
RTU S900 CPU 930- Main CPU Module 32-bit 68020 microprocessor
Clock frequency: 33 MHz 8 MB static RAM with lithium battery backup Real-time clock Lithium battery backed-up clock/calendar Watchdog timer with automatic restart + alarm loop Six signal loops Eight front-panel status lamps Module width: one slot The battery is guaranty 10 years (with out discharge) The battery is guaranty 1 year (with discharge) If a CPU900 is used in spare part, it is possible by strap to disconnect the battery to guaranty the availability latter.
73
RTU S900 SAU 900- Serial Asynchronous Unit
Four isolated V.24/V.28 serial asynchronous links Baud rate from 50 to baud per channel Insulation between interface circuit and ground: 1.4kV peak at 50Hz Four front-panel 9-pin CANNON connectors Module width: one slot
74
RTU S900 FBS 910- FIP bus communication unit VLSI FULLFIP chip
FIPLD1 medium driver (twister pair) Line insulation: 2.1kV peak at 50Hz Line speed: 1Mbit/s Front-panel 9-pin connector Module width: plugged on CPU 900 The FBS 910 is only available (1 per rack) in case off using extended racks.
75
RTU S900 DAU 900- Digital Acquisition unit
48 opto-isolated digital inputs 24Vdc, 48/60Vdc, 110/125Vdc, 220/250Vdc Dielectric insulation: 2.8kV peak at 50Hz One common point for eight inputs Input voltage 24 Vdc (DAU901): 10 mA 48 Vdc (DAU900): 5 mA 60 Vdc (DAU904): 3 mA 110/125 Vdc (DAU902): 3 mA 220/250 Vdc (DAU903): 2 mA Module width: one slot The DAU900 module is available to acquire: Digital inputs Digital measurements (16 or 32 bits) Counting Tap changer position
76
RTU S900 DOU 900- Digital Output unit 32 digital relay outputs
One common for two points Dielectric insulation: 2.8kV peak at 50Hz Watchdog timer Output control chain self-monitored Relays de-energised on fault condition Breaking capacity: 2A-250V-250VA/600W Three modes for execute command Remote Select Before Operate Local Select Before Operate Immediate operate Module width: one slot The DOU900 with the option Local Select Before Operate use 2 relays for a command (1 for the command, 1 for the execution).
77
RTU S900 DOU 920- Digital Command Output unit 12 digital relay outputs
2 No contacts per relays 2 groups with 1 common for 4 relays 2 groups with 1 common for 2 relays Dielectric insulation: 2.8kV peak at 50Hz Watchdog timer Output control chain self-monitored Relays de-energised on fault condition Making capacity: 1000W(VA) at L/R=40ms Breaking capacity: 0.2A-250Vdc at L/R=40ms, 230Vac with cos=0.4 Overload: 30A/0.5s Module width: one slot
78
RTU S900 ACU 900- Analog to digital converter unit
12-bit A/D Converter (11 bits + sign) Conversion rate: 120 samples/second Common-mode rejection ratio: 99dB at 50Hz Accuracy including AAU: better than 0.1% (voltage), 0.2% (current) at 25° (full scale) Temperature coefficient: 30ppm/°C Module width: one slot The ACU900 module shall be associated with 1 or more AAU900 module. Only 1 ACU900 module is plugged in a rack
79
RTU S900 AAU 900- Analog Acquisition unit 24 multiplexed analog inputs
Input ranges: ±5/10/20mA; 4-20mA; ±1.25/2/5V Series-mode rejection ratio: 36dB at 50Hz Insulation voltage: 2.8kV peak at 50Hz in common mode Input impedance: 5mA-1000 Ohms; 10mA-500 Ohms; 20mA-250 Ohms Module width: one slot The AAU900 can acquire on the same module voltage and current input. The AAU900 must be associated with 1 ACU900 module
80
RTU S900 AOU 900- Analog Output Unit Six analog outputs
Output ranges: ±5/10/20mA Resolution: 11 bit + sign Accuracy: better than 0.2% at 25°C (full scale) Insulation voltage: 2.8kV peak at 50Hz in common mode Output impedance: greater than 1 MOhms Load impedance: 5mA-6000 Ohms; 10mA-3000 Ohms; 20mA-1500 Ohms Module width: one slot
81
RTU S900 OPERATING CONDITIONS Influence of temperature
cold, temperature = 0°C IEC dry, heat, temperature = 60°C IEC Damp heat, steady state IEC temperature = 40°C, relative humidity = 95%, duration = 4 days Rapid variation temperature EC variation speed = 20°C/h, limits of temperature: 0°C to 60°C Salt mist 4 days IEC Mechanical conditions : Sinusoidal vibration IEC frequency range: Hz, amplitude: 10/57Hz = ±0.035mm acceleration: 57 to 500Hz = ± 0.5g, duration = 10 cycles
82
RTU S900 OPERATING CONDITIONS Electrical security conditions :
Insulation resistance IEC 255-5 voltage = 500V, duration = 1minute, resistance > 100MW Dielectric withstand IEC 255-5 voltage : 2kV (50Hz) for I/Os voltage : 1.5kV (50Hz) for FIP link voltage : 1kV (50Hz) for asynchronous link Impulse voltage withstand IEC 255-5 impulse waveform: 1.2ms/50ms voltage : 5kV (CM) for digital input/output voltage : 2kV (CM) for analog input/output voltage : 3kV (CM) for power supply and FIP
83
RTU S900 OPERATING CONDITIONS
Immunity test magnetic disturbance IEC : 30 A/m 50/60 Hz Electrostatic discharge immunity IEC : Up to 8 kV for air discharge Up to 6 kV for contact discharge Electromagnetic perturbation immunity IEC 10 V/m for frequency range 26 to 1000 MHz Immunity tests transients and high-frequency conducted disturbances Surge susceptibility test IEC voltage : 2 kV (CM) for I/O voltage : 1kV (CM) for serial link Electrical fast transient/burst susceptibility test voltage : 2 kV peak voltage Oscillatory waves susceptibility tests voltage : 2.5 kV (CM) , 1 kV (MD) peak voltage
84
RTU S900 TOOLS
85
RTU S900 Using a Pentium personal computer
DATABASE GENERATION Using a Pentium personal computer Using relational environment (ORACLE) High flexibility User friendly Man Machine Interface Import/export of data from/to control centre Automatic generation of files to be loaded
86
RTU S900 DATABASE GENERATION
The RTU database generator is available on PC with an ORACLE software licence.
87
RTU S900 DATABASE GENERATION
88
RTU S900 DATABASE GENERATION
89
RTU S900 Using a Pentium personal computer
AUTOMATIC GENERATION Using a Pentium personal computer Using a software logic interface (ISaGRAF) Performing tool with Editor Compiler Debugger Simulator Automatic documentation Library elements The five defined IEC Languages The automatic generator is available on PC with an ISaGRAF software licence.
90
RTU S900 SFC Language Sequential Function AUTOMATIC GENERATION
The SFC language is recommended to develop sequential algorithm like: Auto reclose Tap changer regulation
91
RTU S900 FDB Function Block Diagram AUTOMATIC GENERATION
The FDB language is recommended for application like: Alarm equations Complex calculation (derived, integration, …) FDB Function Block Diagram
92
RTU S900 LD Ladder Diagram AUTOMATIC GENERATION
The LD language is recommended for application like: Alarm LD Ladder Diagram
93
RTU S900 ST Structured Text AUTOMATIC GENERATION
The ST language is recommended for application like: Interlocking
94
GRAPHICAL EDITOR (LOCAL HMI)
RTU S900 GRAPHICAL EDITOR (LOCAL HMI) Using a Pentium personal computer Using a software logic interface (ILOG) Performing tool with Professional editor Automatic link with database elements Automatic documentation Library elements The graphical editor is associated with Local Substation Control Point option.
95
GRAPHICAL EDITOR (LOCAL HMI)
RTU S900 GRAPHICAL EDITOR (LOCAL HMI) Database & graphics management Creation/modification tools provided with equipment Easy to use (no software specialists required)
96
CONTROL CENTRE SIMULATOR
RTU S900 CONTROL CENTRE SIMULATOR Using a Pentium personal computer User friendly Man Machine Interface Possibility to use RTU Data Base Display of Communication messages in : HEXADECIMAL, ASCII, Database LABELS User programmable scripts The control centre simulator is using to simulate the communication to the SCADA (in IEC ) and simplify the commissioning
97
CONTROL CENTRE SIMULATOR
RTU S900 CONTROL CENTRE SIMULATOR
98
CONTROL CENTRE SIMULATOR
RTU S900 CONTROL CENTRE SIMULATOR
99
INPUTS OUTPUTS SIMULATOR
RTU S900 INPUTS OUTPUTS SIMULATOR SIMULATION OF THE SUBTATION SIDE OF RTU 48 KEYS FOR DIGITAL INPUTS 32 LED TO DISPLAY DIGITAL OUTPUT STATE SELECTION OF 1 ANALOG INPUT THROUGH 24 OUTPUT OF 6 ANALOG SETPOINT 1 ADJUSTABLE PULSE GENERATOR INTERNAL OR EXTERNAL POWER SUPPLY The hardware simulator is using to simplify and reduce the time commissioning.
100
INPUTS OUTPUTS SIMULATOR
RTU S900 INPUTS OUTPUTS SIMULATOR
Similar presentations
© 2025 SlidePlayer.com Inc.
All rights reserved.