2182 D - Timber Framing Code Wall Bracing Class Exercise 2.

Similar presentations


Presentation on theme: "2182 D - Timber Framing Code Wall Bracing Class Exercise 2."— Presentation transcript:

1 2182 D - Timber Framing Code Wall Bracing Class Exercise 2

2 Floor Plan Class Exercise 2 Wind Direction 1 Wind Direction 2 Use Bracing Type ‘G’ Method B (p 144)

3 Length of Building Width of Building Roof Pitch Rise of Roof Floor to ceiling height Wind Classification Permanent Wind Bracing Using the Plan & previous information from Roof and Wall framing Calculations fill in the above information 22.910 8.150 18 0 2.700m N3 1.275m

4 Floor Plan Class Exercise 2 Wind Direction 1 Wind Direction 2 Use Bracing Type ‘G’ Method B (p 144)

5 Side elevation (Wind direction 1) Aream 2 Wind Pressure KPa (table 8.2 p 118) Total Racking ForceKN Nominal BracingKN Bracing RequiredKN 61.7 0.95 58.6 28.1 30.5

6 End elevation (Wind direction 2) Aream 2 Wind Pressure kPa (table 8.1 p 116) Total Racking ForceKN Nominal BracingKN Bracing RequiredKN 17 1.4 23.8 Too Much 18 > 50% 11.9

7 For wind classifications greater than N2, spacing shall be in accordance with Table 8.20 and Table 8.21 for the relevant wind classification, ceiling depth and roof pitch. NOTE: Ceiling depth is measured parallel to the wind direction being considered. 8.3.6.7 Spacing of bracing walls in single storey or upper storey of two storey Refer page 148 of 1684.2 (2006) NOTE: 8.3.6.6 Location and distribution of bracing Bracing shall be approximately evenly distributed and shall be provided in both directions (see Figure 8.5). Bracing shall initially be placed in external walls and where possible at the corners of the building.

8 Refer page 150 of 1684.2 (2006) Wind Speed Ceiling Width Roof Pitch Spacing of Bracing

9 Select Bracing Bracing Type ‘h’ Method B (p 144) Method B = 6.0 KN/m x 1.2m (sheet width) 1 Sheet = 7.2KN Braces need to be at every corner and also at 9.000m maximum Spacings to Wind Direction 1 Mark braces on floor plan. Note: 900mm minimum width for ply brace

10 Floor Plan Class Exercise 2 Wind Direction 1 Wind Direction 2 Mark Plan for Required Bracing

11 Exercise 2 Completed