Presentation is loading. Please wait.

Presentation is loading. Please wait.

Chapter 3B: INDOOR AIR QUALITY

Similar presentations


Presentation on theme: "Chapter 3B: INDOOR AIR QUALITY"— Presentation transcript:

1 Chapter 3B: INDOOR AIR QUALITY
Agami Reddy (rev-Dec 2018) Importance of IAQ Indoor air contaminants Air quality standards Types of ventilation methods and control Ventilation standard- ASHRAE Standard 62.1 Ventilation of fully mixed spaces Air distribution efficiency Filtration cleaning of air Sick Building Syndrome HCB-3 Chap 3B: IAQ

2 Importance of IAQ Poor IAQ has large associated costs
- Productivity loss due to decreased comfort - Health costs - Litigation Article by Fisk, ASHRAE Journal May 2002 US national health and productivity benefits from improved IEQ (air, thermal, lighting) Health: $17 – 48 billion per year (respiratory diseases. Allergies, asthma,…) Productivity loss: $20 – 160 billion/yr (US GDP in 2003 was $10.4 trillion) HCB-3 Chap 3B: IAQ

3 Indoor Air Contaminants
Building material emissions Equipment emissions Dust Human, animal and insect by-products Toxins and allergens from microbial growth Airborne pathogens Chemicals, household, industrial Outdoor contaminants drawn into building HCB-3 Chap 3B: IAQ

4 http://www.kaycee.net/mold/index.html http://www.epa.gov/iaq/molds/
moldresources.html HCB-3 Chap 3B: IAQ

5 Outdoor Air Quality Standards
EPA: National Ambient Air Quality Standards NIOSH and OSHA NIOSH- National Institute for Occupational Safety and Health OSHA- Occupational Safety and Health Organization HCB-3 Chap 3B: IAQ

6 Fig. 3.15 Characteristics of particulate matter
and cleaning equipment suitable for removing it HCB-3 Chap 3B: IAQ

7 Indoor Quality Standards
HCB-3 Chap 3B: IAQ

8 Types of Ventilation Methods (Dilution)
Local ventilation preferred for point source contamination - Results in lower airflow requirements - Source is better contained General ventilation preferred for distributed contamination - Provides simultaneous control of temp., humidity, odor - Usually done by all-air or air-water air-conditioning systems HCB-3 Chap 3B: IAQ

9 General Ventilation: Two limiting cases
Dilution ventilation Ventilation air mixes “perfectly’ With air in space Displacement ventilation Plug flow (i.e., like a piston from inlet to outlet) - Air is freshest near inlet Gradually gets contaminated Lower space is the breathing zone HCB-3 Chap 3B: IAQ

10 HCB-3 Chap 3B: IAQ

11 ASHRAE Standard 62.1-2013 (Dilution ventilation)
The purpose of this standard is to specify minimum ventilation rates and indoor air quality that will be acceptable to human occupants and minimize the potential for adverse heath effects This standard is intended for regulatory application (new, existing buildings) This standard is intended to be used to guide the improvement of indoor air quality in existing buildings HCB-3 Chap 3B: IAQ

12 ASHRAE Standard 62.1 Two methods for compliance
- Ventilation rate procedure (prescriptive) OA intake rates determined based on space/application, occupancy level and floor area for typical contaminant sources and strengths - IAQ procedure (performance) requires monitoring certain contaminants, ventilation modulated accordingly for control (additional costs: sensor, control accuracy) Potential for saving energy (demand ventilation based on CO2) HCB-3 Chap 3B: IAQ

13 ASHRAE Standard 62.1 (2013) Required outdoor air needed to be supplied to breathing space Breathing zone (region between 3 – 72 inches above the floor and more than 2 ft from walls or fixed A/C equipment) where breathing zone airflow rate (cfm or L/s) RP and Ra air flow rates per person and per floor area PZ and AZ number of occupants and total floor area HCB-3 Chap 3B: IAQ

14 HCB-3 Chap 3B: IAQ

15 637 L/s HCB-3 Chap 3B: IAQ

16 Ventilation of Fully Mixed Spaces
Co Vo Ci Vo Npol HCB-3 Chap 3B: IAQ

17 Case (i) Air Distribution Efficiency- Single Zone
Air Distribution or air mixing in a room is usually not perfect - One way of treating this for a room with overhead air distribution is to assume the room to be stratified vertically into two uniformly mixed zones Certain fraction S of the supply air stream bypasses the occupied zone (this factor is also called the “occupied zone by-pass factor” or the “stratification factor”) Because of stratification some of the outdoor air is exhausted without performing any useful reduction in the contaminants of the occupied zone HCB-3 Chap 3B: IAQ

18 Ventilation effectiveness is the fraction of outdoor supply air which is “utilized” by occupants
HCB-3 Chap 3B: IAQ

19 Expression for ventilation effectiveness in terms of bypass
fraction S and recycle fraction R when no filters present: HCB-3 Chap 3B: IAQ

20 Case (ii) Building with two zones served by a single VAV HVAC system
Another correction to the minimum ventilation air amount is suggested by ASHRAE standard for VAV systems Multiple spaces may have different ventilation requirements. Further, the thermal loads in these spaces would vary over the year and often by different amounts. Since the single duct supply systems carries the entire supply air amount (ventilation plus recycle), supply air to the individual zones may not contain the required ventilation air amount One would have to increase the amount of outdoor air so as to meet the needs of the most critical zone, This results in large energy penalty due to over-ventilation of the other zones. HCB-3 Chap 3B: IAQ

21 Removing Contaminants from Air-Stream
Gaseous elements: - Absorption - Physical adsorption (activated charcoal) Particulate: Filtering Particulates or suspended particles come in a wide range of sizes, shapes and concentration. Different types of filters used. Three operating characteristics of filters: - Efficiency- ability to remove particles - Air flow pressure drop- affects fan power and energy consumption - Dust holding capacity- determines how often a filter should be cleaned or replaced HCB-3 Chap 3B: IAQ

22 Figure 3.17 Efficiency of removing particles versus particle size, for several filter types. These curves are approximations based on manufacturers' data. They do not correspond to results of tests recognized by ASHRAE and should not be used for HVAC design. (Courtesy of ASHRAE, Standard : HCB-3 Chap 3B: IAQ

23 Sick Building Syndrome (SBS)
Definition: Significant fraction of building occupants experience acute discomfort and health related ailments (sensory irritation of eyes, nose, throat and skin), Linked to time spent in a building (symptoms diminish when not in building), but no specific illness or cause can be identified HCB-3 Chap 3B: IAQ

24 Sick Building Syndrome (SBS)
Causes: Internal chemical contaminants: usually air pollutants (indoor/outdoor) Volatile organic compounds, including formaldehyde, cleaning products, manufactured plastic and wood products Ozone from photocopiers and printers Carbon monoxide, carbon dioxide and other inorganic oxides given off as combustion products in heating systems Small fibers from furnishings, regularly agitated into the air by frequent sweeping. Also, asbestos in older buildings Tobacco smoke Poor ventilation Moisture: High humidity, molds, spores Personal: gender, allergic Psychological: mass psychology, job dissatisfaction/stress HCB-3 Chap 3B: IAQ

25 HCB-3 Chap 3B: IAQ

26 Figure 3.18 Predicted trends in illness or sick leave as a function of ventilation rate.
HCB-3 Chap 3B: IAQ

27 Sick Building Syndrome Resolution
Proper material selection (avoid VOC) Increase ventilation Proper smoking policy Proper location of exhausts and air intakes Resolve moisture problems Replace contaminated materials Remove contaminant traps (carpet) Implement proper maintenance practices Education of occupants HCB-3 Chap 3B: IAQ

28 Outcomes Understanding importance of indoor air quality
Familiarity with possible sources and effects of indoor air contaminants Familiarity with outdoor and indoor air quality standards Knowledge of different types of ventilation methods, both local and general, and how they dilute and limit contaminants Knowledge of the different types of air filters Be able to calculate ventilation requirements based on ASHRAE 62 standard Understanding of analysis methods involving one-zone and two-zone models of indoor spaces Understand concept of ventilation effectiveness Familiarity with causes and remedies of sick building syndrome HCB-3 Chap 3B: IAQ


Download ppt "Chapter 3B: INDOOR AIR QUALITY"

Similar presentations


Ads by Google