Major Event Fire on batteries of UPS ESS118/5CX

Similar presentations


Presentation on theme: "Major Event Fire on batteries of UPS ESS118/5CX"— Presentation transcript:

1 Major Event 76537 Fire on batteries of UPS ESS118/5CX
Date of event: Saturday 25th May 2019, 22H42 Davide Bozzini, on behalf of EN-EL

2 Calendar of LS2 activities
Major event – 22h42

3 Sequence of events 22h42 Fault on UPS ESS118/5CX and fire alarm in SDX5 23h10 Fire detected and extinguished in SCX5 in room 3562/R-403 Finding that UPS ESS118/5CX battery rack is completely destroyed 23h45 EN-EL stand-by on site 00h10 UPS ESS118/5CX isolated, EOD2/CX5 reconfigured in by-pass mode 07h00 Detector Safety System (DSS system) back to nominal conditions 09h00 Electrical network hooked on DSS system back to nominal 09h30 End of EN-EL intervention More details available here:

4 Location (SCX5) 3562/R-403 CMS – Control room
Room hosting UPS ESS118/5CX SDX5 – Fire detection triggered

5 Single line diagram LHC-EB500-LV
UPS ESS118/5CX CMS control room CMS DAQ servers room

6 Damaged batteries in 3562/R-40

7 Consequences EN-EL next steps
Supply of CMS DAQ Servers room supplied through EOD2/5CX in by-pass mode (No UPS) Request from CMS to avoid any power cut on EOD2/5CX AUG tests planned at point LHC-5 for Monday 27th May have been cancelled CMS control room severely impacted EN-EL next steps Root cause of fault to be investigated with the contribution of UPS manufacturer and systems experts Contribution and support to HSE investigation Temporary/alternative UPS sources under study in collaboration with CMS AUG tests at point LHC-5 to be rescheduled