Risk Management State Electrical Division 2017 State Electrical Code 230.70(A)(1) - Length of Service-Entrance Conductors

2 Notice: The following illustrations are approved by the State Electrical Division of the North Carolina Department of Insurance, Office of State Fire Marshal. These illustrations are intended to demonstrate but not supersede the official written interpretations found at the following web address: Joseph Starling Chief State Electrical Engineer & Inspector Illustrated by: Danny Thomas State Electrical Inspector

3 Service-Entrance Conductors Date: June 12, 2018 2017 Electrical Code
Disconnect Date: June 12, 2018 2017 Electrical Code Subject: Length of Service Entrance Conductors Section (A)(1) Question: What is the maximum allowed distance the service-entrance conductors may enter a building or structure?

4 Date: June 12, 2018 2017 Electrical Code Subject: Length of Service Entrance Conductors Section (A)(1) Answer: Section (A)(1) states that “the service disconnecting means shall be installed at a readily accessible location either outside of a building or structure or inside the nearest point of entrance of the service conductors.” The electrical code does not define a distance for the service conductors once such conductors enter a building or structure. The language of (A)(1) has been virtually unchanged over the last several decades. What is commonly known as the “Barringer Rule” or “Five Foot Rule” has been the standard for evaluation of service-entrance conductors inside a building or structure in North Carolina for many decades. The Rule remains as the State’s position for proper evaluation in determining the maximum allowed distance service-entrance conductors may enter a building or structure.

5 Date: June 12, 2018 2017 Electrical Code Subject: Length of Service Entrance Conductors Section (A)(1) The current version of the “Barringer Rule” or “Five Foot Rule” is as follows: Service-entrance conductors shall be in compliance with the requirements of (A)(1) when routed from their point of entrance into a building or structure to the point of attachment to the service disconnect enclosure under all of the following criteria: 1. In the most direct route or at right angles; 2. Horizontally not more than twice the nominal width of the service disconnect enclosure; and 3. Vertically not more than twice the nominal height of the service disconnect enclosure or five (5) feet, whichever is greater. Service entrance conductors in excess of these specified limits will not be allowed unless specifically authorized by special permission from the electrical inspector having jurisdiction to accommodate adverse site conditions which would not reasonably allow installation with this criteria.

6 Service-Entrance Conductors
Date: June 12, 2018 2017 Electrical Code Subject: Length of Service Entrance Conductors Section (A)(1) ON OFF Service Disconnect Service-Entrance Conductors Must be: 1. In the most direct route or at right angles Meter Service-Entrance Conductors

7 Service-Entrance Conductors
Date: June 12, 2018 2017 Electrical Code ON OFF Service Disconnect Horizontal Length Cannot Exceed Width X 2 Service-Entrance Conductors Subject: Length of Service Entrance Conductors Section (A)(1) Service-Entrance Conductors Must be: Meter 2. Horizontally not more than twice the nominal width of the service disconnect enclosure

8 Service-Entrance Conductors
Date: June 12, 2018 2017 Electrical Code Vertical Length Cannot Exceed Height of Disconnect X 2 or 5 feet, Whichever is Greater ON OFF Service Disconnect Subject: Length of Service Entrance Conductors Section (A)(1) Service-Entrance Conductors Must be: Meter 3. Vertically not more than twice the nominal height of the service disconnect enclosure or five (5) feet, whichever is greater