1 Interoperability Test Enumerations for IEC 61968-9
Scott Neumann December 14, 2009

2 Introduction The purpose of this presentation is to describe enumerations to be used for IEC interoperability tests Key reference is (obviously) FDIS for IEC This was revised to reflect input from 8/31/2009 conference call Revised to describe uses of ISO 8601 and add more quality codes 9/3/2009

3 Note The enumerations defined here are purposely not defined as restrictions in any XSD If an implementation encounters an unknown enumeration, it may be flagged as an error, but it should otherwise not ‘break’ the implementation

4 Reading Types 61968-9 Annex C Needed for MeterReadings message
Populated as the value for the ‘ref’ attribute in ReadingType structure Population of the ReadingTypes list in the MeterReadings stucture is optional mRID Description 15-minute Incremental IntervalData Forward Energy (kWh) 24-hour Incremental DeltaData IEEE1366MomentaryInterruption (Count) 60-minute Incremental IntervalData Energization status Indicating Voltage (V) BulkQuantity Forward Energy (kWh)

5 Quality Codes mRID Description Null Assumed valid 1.0.0 Data valid 1.4.5 Test data 2.3.4 Reverse rotation Error code 1.4.4 Skipped interval 3.0.0 Validated 3.6.0 Failed validation Known missing read 3.7.0 Manually edited 3.8.0 Generic estimated 3.10.0 Indeterminate 3.10.1 Manually accepted 3.11.0 Derived - general 3.11.1 Derived - inferred Annex D Used to populate ‘quality’ element in ReadingQualities structure Readings are assumed to be valid unless reading quality is specified Created new category 11 for ‘derived’ values

6 Event Types category Description Power off alarm Power on Low voltage Low voltage cleared High voltage High voltage cleared Unauthorized Access attempt Tamper detection Battery failed Demand reset Armed for closure Disconnected Reconnected Annex E Used to populate ‘category’ of EndDeviceEvent structure Important not to confuse event codes with reply codes

7 Control Types type Description Demand reset Load control started Load control stopped Close remote connect/disconnect switch Disable RCD Switch Open remote connect/disconnect Enable RCD switch Price signal Annex F Used to populate ‘type’ in EndDeviceControl structure

8 Time Stamps All timestamps must conform to ISO 8601
Timestamps MUST provide time zone offset or ‘Z’ for absolute time Precision to seconds is recommended but not required, as to not overstate the precision of the end device There is currently no use case requiring milliseconds ISO 8601 allows for as many decimals of accuracy as needed, so long as partners agree

9 TimeSchedules Use ISO 8610 where appropriate
See sections 5.6 and B.5 of ISO 8601 for recurring time intervals Examples for TimeSchedule/recurrencePattern: Monthly: R/P1M Daily: R/P1D Hourly: R/PT1H 15 minutes: R/PT15M Reading windows can be supported using intervals, e.g. TimeSchedule/TimePoints/absoluteTime = T04:10:00/PT1H17M12S TimeSchedule/scheduleInterval/end should be set to a time in the far future if no end is desired

10 EndDeviceAssets Need to identify a set of mRIDs for EndDeviceAssets for each metering system Allocations: ESB test objects: 1-10 Elster: Landis&Gyr: Itron: Other: …

11 Landis+Gyr Enumerations
EndDeviceAssets mRIDs M M M M M M M M M M LGRF100000 LGRF100001 LGRF100002 LGRF100003 LGRF100004 LGRF100005 EndDeviceEvent.category values Power On Event Power Off Event Register Reading Types  = kwh = Present Max kW = Instantaneous Active Demand Interval Reading Types L+G will support/send  = 15-minute Incremental IntervalData Forward Energy (kWh) EndDeviceControl.type values L+G will support/receive (tentative)

12 Other EndDeviceAsset mRIDs
Ecologic: EA001 EA002 EA003 EA004 EA005 UISOL: 1 2 3 4 5 6 7 8 9 10

13 Error Codes Used to populate message ReplyCode element
type Description 0.0 No errors 1.1 Noun element(s) not found in payload 1.3 Verb not found 2.4 Invalid meter number(s) 2.5 Invalid noun 2.6 Invalid ReadingTypeID 2.9 Invalid verb or revision number 2.10 Unable to process the request, ReadingTypeID not supported by the system 2.11 Payload mismatch 4.1 Request timed out 5.2 Unable to process the request. Transaction not attempted 5.3 Unable to process the request. Transaction attempted and failed Used to populate message ReplyCode element From IEC table B.2 Many more error codes are possible

14 More Information UISOL web site: http://uisol.com
EPRI Technical Report: ESB Implementation Profile Using IEC 61968 ISO 8601