Presentation is loading. Please wait.

Presentation is loading. Please wait.

installations and assemblies

Similar presentations


Presentation on theme: "installations and assemblies"— Presentation transcript:

1 installations and assemblies
ATEX ad-hoc group on installations and assemblies

2 Comparison of the general terms
Manufacturer 2014/34/EU Component Equipment Protective System Putting into service Manufactoring for own use Assembly Putting into service Manufactoring for own use Installation 99/92/EC Putting into service User

3 Example1: Emergency Shower for Ex (Cat. 2)
Product consists of 2 parts: 1: Ex-Heating device - Supplier - Certificate 2: Metal construction Case A: Manufacturer buys a heating device from a supplier, build the metal construction, put the 2 parts together and place the product on the market under his name. Case B: User buys a heating device from a supplier, build the metal construction, put the 2 parts together and use it. Question: What is the correct conformity assessment procedure of the manufacturer and the user? What are the criteria? What is an installation?

4 Example 2: Heat Transfer Unit for Ex (Cat. 2)
Product consists of more than 2 parts: 1: Ex-Heating device - Supplier - Certificate X other devices (panel, motor, pump) - Supplier - Certificate Metal construction Case A: Manufacturer buys ex-devices from suppliers, build the metal construction, put the parts together and place the product on the market under his name. Case B: User buys ex-device from suppliers, build the metal construction, put the parts together and use it. Question: What is the correct conformity assessment procedure of the manufacturer and the user? What are the criteria? What is an installation/facility/plant?

5 Other Directives possible
General Approach ATEX-Equipment ATEX-Equipment Risk Assessment Additional Ex-Risk? No User? No Yes Yes New ATEX- Equipment 99/92/EU (Installation) Other Directives possible (like MD, LVD, 2001/95/EC, …)

6 Other Directives possible
General Approach ATEX-Equipment Additional Ex-Risk Yes New ATEX- Equipment Risk Assessment ATEX-Component Other Directives possible (like MD, LVD, 2001/95/EC, …) Definition of additional risks: Modification of the type of protection New ignition sources identified

7 Example1: Emergency Shower for Ex (Cat. 2)
Product has no component Product has no additional Ex-risk => Case A: Manufacturer: 2001/95/EC or Case B: User: Installation (99/92/EG)

8 Example 2: Heat Transfer Unit for Ex (Cat. 2)
Product has no components and Product has no additional Ex-risks => Manufacturer: MD or User: Installation (99/92/EC) B: Product has components or Product has additional Ex-risks => New ATEX Product + MD