Presentation is loading. Please wait.

Presentation is loading. Please wait.

Objectives Finish Transformers Introduce HW5 (Pricing)

Similar presentations


Presentation on theme: "Objectives Finish Transformers Introduce HW5 (Pricing)"— Presentation transcript:

1 Objectives Finish Transformers Introduce HW5 (Pricing)
Select conductor and conduit List electrical devices

2 Transformers Change - Voltage [E] and - Current [I]
Across a transformer I1E1 = I2E2 Es/Ep = Ns/Np

3 Ref: Tao and Janis (2001)

4 Electricity Billing Electrical Use (energy) Peak Demand (power) Power factor Which is largest portion of residential bill? What about for commercial buildings?

5 Example: September cost of Electricity for ECJ
Assume ECJ is 120,000 ft2 and that it needs, on average, 8 W/ft2 for 8 hours a day, 6 W/ W/ft2 for 4 hours a day, and 4 W/ft2 for 12 hours a day Use Austin Energy Large Primary summer service rate 1.5¢/kWh, $/peak kW/month Assume no power factor charges

6 Solution large primary service $/kW $/kWh Daily $ 12.60 $ 0.015 hours
$ $ hours kW kWh 8 960 7680 demand $12,096.00 4 720 2880 energy $ 7,344.00 12 480 5760 TOTAL 16320 Total $19,440.00

7 Other Pricing Strategies
Time of use pricing Becoming more common for residential and commercial Electricity cost related to actual cost Requires meter Interruptible pricing Utility can shut off electricity for periods of time

8 Other Pricing Strategies
Time of use pricing Becoming more common for residential and commercial Electricity cost related to actual cost Requires meter Interruptible pricing Utility can shut off electricity for periods of time For Austin

9 Homework 5 Problem 1: Economical analyses of chilled water saving

10 Advantage of higher voltage
120/208 220/380 277/480

11 Neutral and 3-phase system
If system is well balanced the current through the neutral wire is 0

12 Grounding What is electrical ground?
Why do we ground electrical devices/systems? Protect equipment Lightening strike Protection of people Sometimes need ungrounded power If the hot side touches ground, it can put out of service our circuit Isolate ungrounded systems

13 Conductors Material Form Composition Voltage class Insulation Covering
Temperature rating AWG American Wire Gage

14 Wiring method –Raceways
Electric tubes Rigid conduits Wire ways Bus ducts Underflow Different variation

15 Design issues with conductors
Material (copper/aluminum) Size of conductor (pg. 365) Conduit requirements Location Residential or Commercial With or without raceways Compression fittings or set screws Threaded connections NEC and local codes

16 Current-Carrying Capacity
Ref: Tao and Janis (2001)

17 Tubing size Ref: Tao and Janis (2001)

18 Other Issues In general, no more than 40% of raceway can be filled with wiring Why? To prevent extensive heat up To prevent physical installation of wires

19 Conductor Rules Explain each of the following: In the same conduit:
No more than 4 90 ° bends are allowed between pull boxes In the same conduit: No mixing of high- and low-voltage conductors No mixing control and power conductors No mixing phone and power conductors Do place all three phases in the same conduit

20 Receptacles and switches
Receptacles (duplexes) Number Shape Voltage rating Current Rating Number of poles and wires Switches Type (NEC rating) Contact method Speed of operation Voltage rating Number of poles Method of operation Enclosure Duty Other (dimming)

21 Protective Devices What are we protecting from? Circuit breakers
Overcurrent Overvoltage Circuit breakers Switch that responds to thermal or short circuit loads Can be bimetal, magnetic, or electronic Reusable, remote control, compact, can be used as disconnect switch Fuses Melting metal Self destructive, larger

22 Why use fuses instead of circuit breakers?
Fuses can be used multiple times Fuses are more aesthetically pleasing Fuses are safer Fuses cause less damage to equipment

23 Ref: Tao and Janis (2001)

24 Emergency power systems Batteries Power generators
Motor starters ON-OFF switches are NOT for motors Motor circuit-rated switches Reduce the current during the start until the motor rich full speed Protect the motor form overload Emergency power systems Batteries Power generators

25 Summary Describe role of electrical system components
Calculate billing for an electrical system given the rate structure Size conduit and conductors given current requirements and conductor type

26 Residential Systems Very little variation between different houses
Many similarities to commercial buildings Particularly as you get close to end uses Need to be watchful for unusual circumstances

27 Procedure Analyze building needs Determine electrical loads
Select electrical systems Coordinate with other design decisions Prepare plans and specifications

28 List of needs Appliances (incl. HVAC) Receptacles Lighting
Ground fault protected (GFI/GFCI) Switched Lighting Switches Ceiling Fans

29 Example House Master Bedroom Bathrooms
Entry and Outdoor (AC compressor) Bedrooms Dining and Mechanical Closet (resistance heat) Kitchen (appliance circuits, range, oven) Family Garage/Laundry/Closet (resistance water heater, dryer)

30 Outdoor Bathroom Closet Bedroom 2 Laundry Kitchen Bathroom Mechanical closet Family room Master Bedroom Entry Bedroom 3 Dining Garage

31 Residential system sizing
Typically 3 wire 1 phase system 120/240 V Procedure defined by NEC article 220: Identify characteristic electrical loads Add lighting (3W/ft2) Add two 20 Amps circuits for kitchen Add one 20 Amps circuit for laundry Electricity for HVAC equipment based on requirement for heating or cooling

32 Reading Assignment Tao and Janis: Whole chapter 11


Download ppt "Objectives Finish Transformers Introduce HW5 (Pricing)"

Similar presentations


Ads by Google