Download presentation
Presentation is loading. Please wait.
Published byCornelius Schreiber Modified over 5 years ago
1
Objectives Finish with Practice circuits problems for
Electric Systems (protective devices) HW4 (part 2) Practice circuits problems for Next Class Quiz Exams 2 (next Tuesday) FE exam
2
Next class QUIZ Circuits Chapters 11 and 13
3
Exam 2 Tuesday (April 30th)
In class (same as the previous one) Circuits (chapter 10 & 11 & class examples) AC vs. DC; single phase vs. 3 phase Pricing (HW4 part 1) Electric systems and wiring (chapter 11 &13 HW4 part 2)
4
Protective Devices What are we protecting from? Circuit breakers
Overcurrent Overvoltage Circuit breakers Switch that responds to thermal or short circuit loads Can be bimetal, magnetic, or electronic Reusable, remote control, compact, can be used as disconnect switch Fuses Melting metal Self destructive, larger
5
Why use fuses instead of circuit breakers?
Fuses can be used multiple times Fuses are more aesthetically pleasing Fuses are safer Fuses cause less damage to equipment
6
Ref: Tao and Janis (2001)
7
Emergency power systems Batteries Power generators
Motor starters ON-OFF switches are NOT for motors Motor circuit-rated switches Reduce the current during the start until the motor rich full speed Protect the motor form overload Emergency power systems Batteries Power generators Reading Assignment: Chapter 11
8
Residential Systems (NEC Article 220-Branch Circuit, Feeder and Service Calculations)
Very little variation between different houses Many similarities to commercial buildings Particularly as you get close to end uses Need to be watchful for unusual circumstances
9
Wiring from panel to: receptacles, lighting, ceiling fan,…..
Feeders and conduit House branch circuits Electric panels
10
Electric panel - 3 wire 1 phase 120/240
11
Procedure Analyze building needs Determine electrical loads
Select electrical systems Coordinate with other design decisions Prepare plans and specifications
12
List of needs Appliances (incl. HVAC) Receptacles Lighting
Ground fault protected (GFI/GFCI) Switched Lighting Switches Ceiling Fans
13
Example House Master Bedroom Bathrooms
Entry and Outdoor (AC compressor) Bedrooms Dining and Mechanical Closet (resistance heat) Kitchen (appliance circuits, range, oven) Family Garage/Laundry/Closet (resistance water heater, dryer)
14
Outdoor Bathroom Closet Bedroom 2 Laundry Kitchen Bathroom Mechanical closet Family room Master Bedroom Entry Bedroom 3 Dining Garage
15
Residential system sizing
Typically 3 wire 1 phase system 120/240 V Procedure defined by NEC article 220: Identify characteristic electrical loads Add lighting (3W/ft2) Add two 20 Amps circuits for kitchen Add one 20 Amps circuit for laundry Electricity for HVAC equipment based on requirement for heating or cooling
17
Summary of Power Sizing
Include enough capacity for heating and cooling Work through kitchen and then other rooms Include any items that are unusual Take first 10 kVA and then 40% of remaining load
18
Panel Sizing Find panel power usage and neutral usage
Size panel conductors and associated conduit and switches
19
Electric panel - 3 wire 1 phase 120/240
20
Wiring from panel to: receptacles, lighting, ceiling fan,…..
Feeders and conduit House circuits Electric panels
21
Outdoor Bathroom Closet Bedroom 2 Laundry Kitchen Bathroom Mechanical closet Family room Master Bedroom Entry Bedroom 3 Dining Garage
22
Homework 4 - problem 2 Sizing the residential electrical system
Defined by NEC article (BOOK chapter 13) Similar to the example we worked out You need to collect the data for several characteristic consumers Includes conductor sizing
23
Item Watts Comments Air conditioner (larger than 65% of furnace) xyz W/ton + 2 × 900 W (2 fans of air handlers) lighting yyW/sq. ft. Outdoor lighting xxW × 15 Appliance Circuits Separate loop required by NEC article Laundry circuit Dishwasher Electric oven (w/ natural gas stovetop) 30 cu ft. refrigerator on appliance circuit of kitchen Electric dryer Required on separate loop Washing machine on appliance circuit of laundry 50 gallon electric water heater Garage door opener 3 ceiling fans 300W × 3 Duplex outlets 2 floors × 20 duplex × 1.5 A × 120 V Gross Load Net load 10kW + 40% remaining load =10+0.4×32200 Current Amps = Net load / 240 V Panel Size First standard larger than calculated is 100Amps
24
HW4 (problem 1) Total a) Total b) Total c)
Cost for electric energy for no cooled water storage tank electricity demand for COP=4 cooled water storage tank (chiller consumption is constant) cooled water storage optional time-of-use rate Hour Cooling load [kW] Power [kW] Price [$/kwh] Cost [$] 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Total a) Total b) Total c)
25
Circuit problems (for practicing) Start with problems that Yune provided:
26
Example problem 1 What is the potential difference (voltage) across the 20-Ω resistor? a. 3.2 V b. 7.8 V c. 11 V 5.0 V 8.6 V
27
Example problem 2
28
Example problem 3 NOTE: After t = 5t, the capacitor acts like an open circuit
29
Example problem 4 NOTE: Time constant of the circuit is t = RC = 15 ms. Time constant is the time to charge capacitor to 63%. [1- e-1]. To charge more (80%) you need more time.
Similar presentations
© 2024 SlidePlayer.com Inc.
All rights reserved.