Presentation is loading. Please wait.

Presentation is loading. Please wait.

New Conventional AV.

Similar presentations


Presentation on theme: "New Conventional AV."— Presentation transcript:

1 New Conventional AV

2 EN54-23 Standard Visual Alarm Devices

3 The purpose of EN 54-23 is to:
EN54-23 Standard The purpose of EN is to: Standardize the requirements, test methods and performance criteria of VADs Ensure light output is now measured in a uniform manner throughout Europe. Timelines – EN54-23 becomes mandatory from 1ST January 2014 across Europe. Ensuring Safe Evacuation For All

4 EN54-23 VAD Categories Wall Category Ceiling Category Open Class
The coverage volume code W – x – y, where W is for Wall, x is the maximum mounting height and y is the width & length of the coverage area in metres Ceiling Category The coverage volume code C – x – y, where C is for Ceiling, x is the maximum mounting height and y is the diameter in metres of the cylindrical coverage volume. Open Class Open class allows the manufacturer to specify the coverage volume and coverage shape does and not restrict mounting height. The required illumination of 0.4 lux still applies. y x Ensuring Safe Evacuation For All

5 Compliance to EN54-23 Standard
Required illumination of 0.4 lux or lm/m2 on a surface perpendicular to the direction of the light emitted from the VAD The room size must be stated on the product or supporting documentation Flash rate must be between 0.5Hz and 2Hz Flash light must be red or white Ensuring Safe Evacuation For All

6


Download ppt "New Conventional AV."

Similar presentations


Ads by Google