Presentation is loading. Please wait.

Presentation is loading. Please wait.

Robicon Perfect Harmony.

Similar presentations


Presentation on theme: "Robicon Perfect Harmony."— Presentation transcript:

1 Robicon Perfect Harmony

2 Robicon Perfect Harmony
- Largest selling MV drive installed - IGBT based - 2.4 to 13.8kV A - Air or liquid cooled - Inherently low harmonics - Modular construction - Built-in redundancy - Up to 60MW

3 Robicon Perfect Harmony
THE PERFECT HARMONY CONCEPT

4 The Pefect Harmony Concept
CONVERTER SUPPLY TRANSFORMER HARMONIC FILTER DC LINK REACTOR MOTOR CONVENTIONAL DESIGN SUPPLY TRANSFORMER CONVERTER PERFECT HARMONY

5 The Ideal Variable Speed Drive
Driven Load Supply Network Variable Speed drive Motor No harmonic voltage or current distortion Near unity power factor Fault tolerant, enabling operation after component failure Small footprint Easy repair High efficiency No harmonic heating No insulation stress No additional bearing current No rotational torque oscillations

6 Voltage Source Converter
INPUT TRANSFORMER MOTOR RECTIFIER DC LINK CAPACITOR INVERTER

7 The Perfect Harmony Concept
Dedicated winding on power transformer Power Output of Cell Logic Control Power Fiber Optic Signals to and from master control Logic Control Circuits

8 Power Cell

9 The Perfect Harmony Concept
630 V 3800V 6600V These cells are in phase at zero degrees electrical These cells are in phase at 120 degrees electrical These cells are in phase at 240 degrees electrical

10 The Perfect Harmony Concept
1375 V 8000V 13800V These cells are in phase at zero degrees electrical These cells are in phase at 120 degrees electrical These cells are in phase at 240 degrees electrical

11 The Perfect Harmony Concept – Power Schematic

12 The Perfect Harmony Concept – Motor Waveform

13 The Perfect Harmony Concept – Power Cell

14 The Perfect Harmony Concept – Application Issues
- Motor compatibility - Power line immunity - Power quality - Energy saving - Reliability

15 The Perfect Harmony Concept – Motor Compatibility
No additional VFD induced motor heating Converter can safely be applied to a standard motor Compatible with both new and existing motors No insulation problems Converter creates no motor dV/dt insulation stress No common mode insulation stress Converter generates no additional bearing currents

16 The Perfect Harmony Concept – Output Waveform
Pulse Width Modulated Waveform

17 The Perfect Harmony Concept – Motor Compatibility

18 The Perfect Harmony Concept – Motor Compatibility
Effects of dV/dt on motor windings Competitor’s Waveform

19 The Perfect Harmony Concept – Motor Compatibility
Paths for bearing currents and their effect

20 The Perfect Harmony Concept – Ride Through Capability

21 The Perfect Harmony Concept – Ride Through Capability

22 The Perfect Harmony Concept – Power Quality
- Near zero supply side harmonics - Meets all new requirements of IEEE 519 for both current and voltage distortion - Eliminates the need to do harmonic analysis - Eliminates costly harmonic filters required for distortion control

23 The Perfect Harmony Concept – Power Quality

24 The Perfect Harmony Concept – Energy Saving
- Typical efficiency of 96.5% from power in to power out or better power factor over the entire speed ran - No external power factor correction capacitors required - Eliminates utility penalties - High efficiency over the whole speed range - No energy wasting harmonic filter required

25 The Perfect Harmony Concept – Cell Bypass
630 V 3800V 6600V Allows operation at reduced power/speed Automatic bypass of failed cell Neutral Shift

26 The Perfect Harmony Concept – Cell Bypass

27 The Perfect Harmony Concept – Cell Bypass
95 132.5 o A B C VAC VBA VCB A3 A2 A1 B1 B2 B3 B4 B5 C1 C2 C3 C4 C5

28 The Perfect Harmony Concept – Cell Bypass
61.6 61.1 C B A VBA VAC VCB

29 The Perfect Harmony Concept – Reliability
- Air cooled models have redundant cooling fans with automatic changeover - Water cooled models have redundant water pumps with automatic changeover

30 The Perfect Harmony Concept – The Proof
- 3.7MW Wet Gas Compressor - Refinery Duty - 5 Years Guaranteed Trip Free operation - Started End of 2000 - Three Year Expected Payback on Investment - Improved Surge Control - Maintenance extended to 6 years

31 The Perfect Harmony Concept – Ease of Maintenance
- Low voltage Power Cell construction - Modular draw-out Power Cells - Bypassed cell can be changed when convenient - Microprocessor-based diagnostics - Historical operational and fault reports

32 The Perfect Harmony Concept
Motor compatibility Power line immunity Power quality Energy saving Reliability

33 Title of the presentation
Thank you Title of the presentation Name: Renash Rampersadh Department: Drive Technology Address: 300 Janadel Ave Halfway House Phone: Mail: