1 Using ASHRAE 180 To Increase Filter Sales
Robert G. Baker, ASHRAE OPMP, DL, DS BBJ Environmental Solutions Tampa, Florida

2 What we will cover Why maintenance is so important
ASHRAE’s new HVAC maintenance standard (S180) What we are trying to maintain Utilizing the standard Achieving greater energy efficiency by managing pressure drop The role of air cleaning Where the standard is going

3 The new‘Burbs’

4 The earth is flat We are competing for:
Jobs Cash Food Resources Energy

5

6 Total Energy Consumption United States
6

7 ASHRAE ‘Tips’ Demand accurate design and construction records and understand how the system works Demand accurate commissioning information; keep records up-to-date. Change things that don’t work. Check calibration of sensors against data and common sense. Look for patterns in occupant complaints and apply cause analysis. Decide whether to get to know the occupants or stay remote. Establish lines of communication.

8 Tips (contd.) Collect key data and use it to plot trends.
Establish energy baseline and sustain performance. Use qualified well-trained staff. Operations and maintenance cost will exceed construction costs over the life of the building. Read and apply ASHRAE/ACCA Standard 180, Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems. Read and apply Chapter 38 of the ASHRAE Handbook, HVAC Application. Take the test and obtain ASHRAE OPMP Certification.

9 Especially Important Collect key data and use it to plot trends.
Establish energy baseline and sustain performance.

10 Our Concentration: Air Movement system

11 Impact on Performance Adequate – high efficiency
Lacking – compromised performance

12 ASHRAE/ACCA/ANSI S-180 Title
Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems

13 Commercial Buildings (definition)
Buildings shall include, but are not limited to governmental and educational facilities, healthcare, hospitality, institutions, offices, places of assembly, restaurants, retail, and wholesale.

14 Standard 180 Purpose The purpose of this standard is to establish minimum HVAC inspection and maintenance requirements that preserve a system’s ability to achieve acceptable thermal comfort, energy efficiency, and indoor air quality in commercial buildings.

15 Standard 180 Scope This standard provides minimum requirements for the HVAC system inspection and maintenance practice in new and existing buildings. Where specifically noted in this standard, different requirements apply.

16 What Does the Standard Require?
Written Maintenance Program

17 Written Maintenance Program
May be hard copy or electronic Many building information systems will facilitate

18 What Does the Standard Require?
Written Maintenance Program Inventory of Components to be Maintained

19 Inventory of items to be inspected and maintained (4.2.1)
Components of HVAC systems that impact the building’s performance shall be inventoried…

20 Standard 180 – Airside Components
Table 5-1: Air Distribution Table 5-2: Air Handlers Table 5-12: Free Standing Coils Table 5-14: Fan Coils Table 5-15: Furnaces Table 5-16: Duct Free Splits Table 5-17(18): PTAC(PTHP) Table 5-20:Rooftops Table 5-22: Boxes (VAV etc.) Table 5-24: WSHP

21 Airside Performance Issues?
If so important, why so many: Airside Performance Issues? Air leaks Infiltration Air flow volume Restrictions (filters; coils) Fans Dampers Controls

22

23 Possible Reasons Lack of personnel Training/knowledge Data
Salesmanship People not motivated to change!

24 Standard 180 and Air Cleaning Key Tasks -
Check for particulate accumulation on filters. Clean or replace if accumulation results in pressure drop or airflow outside of established operating limits. Monthly

25 Or Use Data

26 Standard 180 and Air Cleaning Key Tasks -
Check for particulate accumulation on filters. Clean or replace if accumulation results in pressure drop or airflow outside of established operating limits. Monthly Check air filter and housing integrity. Correct as needed. At filter change

27

28

29

30 The Inside…

31 Couple Training with Resources

32

33 Standard 180 and Air Cleaning Key Tasks -
Check for particulate accumulation on filters. Clean or replace if accumulation results in pressure drop or airflow outside of established operating limits. Monthly Check air filter and housing integrity. Correct as needed. At filter change Check integrity of all panels on equipment. Replace fasteners as needed to ensure proper integrity and fit/finish of equipment. Annually

34 Standard 180 and Air Cleaning Other Related -
Visually inspect grilles, registers and diffusers for dirt accumulation. Clean as needed to remove dirt build up Simi-annually Inspect for evidence of moisture carryover beyond the drain pan from cooling coils. Make corrections or repairs as necessary. Visually inspect areas of moisture accumulation for biological growth. If present, clean or disinfect as needed. Annually Visually inspect internally lined ductwork until the first turn or up to 20 feet into the supply plenum from air handler for visible biological contamination, and take corrective action.

35

36 Standard 180 and Air Cleaning Indicators -
Check for proper operation of cooling or heating coil. Clean, restore or replace as required. Simi-annually Check coil fins for evidence of build-up or fouling. Restore if possible. Replace coil if necessary to return to proper functioning. Annually Check fan blades. Clean, repair or replace as needed to ensure proper operation. Check for fouling, corrosion or degradation. Clean or repair as needed. Inspect for evidence of moisture carryover beyond the drain pan from cooling coils. Make corrections or repairs as necessary.

37 From 8-16/”

38

39 What Does the Standard Require?
Written Maintenance Program Inventory of Components to be Maintained Condition Indicators

40 Condition Indicators Performance Objectives Allowed Variance

41 Condition Indicators Appendix A – Performance Objective Examples
Appendix B – Example indicators of unacceptable performance

42 Inventory - For each component
Task description What has to be done

43 Tasks Vary – Simple to Complex
Visually inspect grilles, registers and diffusers for dirt accumulation. Clean as needed to remove dirt build up Check control system and devices for evidence of improper operation. Repair, adjust or replace components to ensure proper operation

44 11 of 31; Avg-55

45 11 of 31; Avg-55; 40% Occ.

46 What turns it on?

47 Do they work together?

48 Inventory - For each component
Task description What has to be done Since inspection is a common theme of most tasks, access is important.

49 Access to Sensors - Measurement

50 Blocked Access

51 Inventory - For each component
Task description What has to be done Frequency How often it has to be done

52 May Need Adjustment 3 months?

53 18 months?

54 Inventory - For each component
Task description What has to be done Frequency How often it has to be done Performance objectives May be several for each task

55 Inventory - For each component
Task description What has to be done Frequency How often it has to be done Performance objectives Condition Indicators Observation related

56

57

58 Inventory - For each component
Task description What has to be done Frequency How often it has to be done Performance objectives May be several for each task Condition Indicators Observation related Performance Related

59

60 Pressure Drop – Cooling Coil
Building A 31 Floors 1 AHU/floor ∆ P High/Low/Avg /0.26/0.66 Building B 11 Floors ∆ P High/Low/Avg- 0.5/0.14/0.4

61 Annual Electric Cost High – $991.17 Average – $382.06 Low - $149.83
The High Rise (per AHU) High – $991.17 Average – $382.06 Low - $149.83 Annual savings by bringing average to low = $7,199.13

62 Energy Consumption = Q x dP x t / n / 1000
Cost Calculation Energy Consumption = Q x dP x t / n / 1000 where Q is the airflow in cubic meters per second: 2119 cubic feet per minute (cfm) dP is the average pressure drop of filter in Pascals: 249 Pascals = 1 inch water gauge t is the time in hours n is the product of the fan, motor, and drive efficiencies entered in percent format Energy Consumption is calculated in kilowatt hours. Tampa electric rate = $0.06/Kwh

63 What Does the Standard Require?
Written Maintenance Program Inventory of Components to be Maintained Performance Objectives Condition Indicators Inspection/Maintenance Tasks Documentation

64 Documentation Inventory – with performance criteria
Tasks and tracking method Verification records (implementation)

65

66

67 Maintenance Repays Costs Many Times

68 Building and Working a Plan
Identify the building Complete the inventory Select the tasks Establish condition indicators Implement Adjust frequencies Audit Revise as needed

69 Codes and Standard 180 Basis for code inclusion

70 Code Inclusion; for and against
Inconsistency Energy waste Sustainability Health Productivity Post CO Enforcement cost Building budgets Difficulty Skill sets

71 Codes and Standard 180 Basis for code inclusion How to implement

72 Code Implementation Annual inspection/w associated fee
Review of Maintenance Plan Confirmation of Inventory Spot check of inspection records (10%) Physical verification of condition No pass: 6 month re-inspection?

73 Your Opinions, Please… and Questions…

74 For Further Information