EXTERNAL ALARMS AT BTS SITES
SUBMITTED BY, NIDHIN JOY
2
INTRODUCTION Alarms are used to monitor various activities
Alarms are classified as two types. Internal alarms External alarms Externals alarms :used to monitor the activities on the sites.
3
Classification of alarms
Internal alarms external alarms
4
EXTERNAL ALARMS USED TO MONITOR THE VARIUOS ACTIVITIES ON THE SITES
VARIOUS LISTS OF EXTERNAL ALARMS ARE AS FOLLOWS SITE ON BATTERY DG FAILS TO START DG FAILS TO STOP DG RUNNING WITHOUT LOAD LOW FUEL LEVEL; LOW LUBRICATION OIL PRESSURE
5
HIGH ROOM TEMPERATURE AC-1 FAILS AC-2 FAILS AC FAILS RECTIFIER FAILS LOW BATTERY VOLTAGE DOOR OPEN FIRE AND SMOKE AT SITE SITE ON DG. FEW MORE ALARMS ARE THERE.BUT IT IS BASED ON THE BTS USED.
6
CONNECTION OF ALARMS External alarms are connected to the alarm panels. The alarm panels are connected to the ddf. According to the bts the alarms AT EACH SITE MAY differ. ALARMS ARE CONNECTED USING ALARM CABLES FOR EACH AND EVERY ALARMS 2 WIRES ARE NEEDED. ALARM CABLES USED ARE PCM CABLES.
7
CONNECTION AND CONFIGARATION OF ALARMS
FOR THCONNECTION AND CONFIGURATION OF THE ALARMS VARIOUS STEPS ARE TO BE FOLLOWED THEY ARE: TITLE/SYNTAX:NAME OF THE ALARM ALARM NUMBER:DEPENDS ON BTS ALARM TYPE: NORMALLY OPEN(NO)/NORMALLY CLOSED(NC) ALARM SEVERITY:MAJOR/MINOR/SEVERITY ALARM PORT NO/PIN NO:DEPENDS ON BTS COLOUR CODE:DEPENDS ON THE PIN CONFIGURATION ROUTE OF THE ALARM:ORIGIN OF ALARM ROOT CAUSE OF THE ALARM:WHY THE ALARM COMES? CAUSE OF THE ALARM: HOW THE ALARMS COMES?
8
LIST OF ALARMS SITE ON BATTERY:
THIS ALARM WORKS WHEN THE SITE WORKS ON THE BATTERY. TYPE OF THIS ALARM IS N ORMALLY OPEN(NO). SEVERITY OF THIS ALARM IS MAJOR ROUTE OF THE ALARM: ROOT CAUSE:ALL THE RECTIFIERS IN THE POWER PLANT GETS FAILED BTS DDF ALARM PANEL OF P.P
9
this alarms works when the mains get fails.
Mains fails this alarms works when the mains get fails. type of alarm: normally open(n o) severity of alarm: minor/major(depends) route of the alarm ROOT CAUSE:WHEN THE MAINS GETS FAILS PIU/AMF DDF BTS
10
ALARM TYPE:NORMALLYU OPEN(N O). ALARM SEVERITY:MAJOR
DG FAILS TO START THIS ALARMS WORKS WHEN THE CONTROL PANEL SENSE THERE IS NO INPUT FROM DG ALARM TYPE:NORMALLYU OPEN(N O). ALARM SEVERITY:MAJOR ROUTE OF THE ALGORITHM ROOT CAUSE:WHEN THE PIU/AMF PANEL FAILS TO START THE DG IN 3 ATTEMPT PIU/AMF DDF BTS
11
DG FAILS TO STOP THIS ALARM WORKS WHEN THE CONTROL PANEL SENSE THERE IS INPUT FROM DG AFTER MAINS COMES ALARM TYPE:NORMALLY OPEN ALARM SEVERITY:MINOR ROUTE OF THE ALARM ROOT CAUSE:WHEN PIU/AMF PANEL FAILS TO STOP THE DG IN 3 ATTEMPTS PIU/AMF DDF BTS
12
DG RUNNIGN WITHOUT LOAD
THIS ALARM WORKS WHEN THE DG IS RUNNIGN WITHOUT LOAD ALARM TYPE:NORMALLY OPEN(N O) ALARM SEVERITY:MINOR ROUTE OF THE ALARM: ROOT CAUSE:DG RUNS WITHOUT LOAD PIU/AMF DDF BTS
13
LOW FUEL LEVEL THIS ALARM WORKS WHEN THE FUEL IS EMPTY
ALARM TYPE:NORMALLY OPEN( NO) ALARM SEVERITY:MINOR ROUTE OF THE ALARM: ROOT CAUSE:WHEN THE FUEL IN THE TANK REACHES 40% OF THE TANK CAPACITY FUEL SENSOR PIU/AMF DDF BTS
14
LLO(LOW LUBRICATION OIL PRESSURE)
THIS ALARMS WORKS WHEN THE OIL PRESSURE IN ENGINE IS LESS ALARM TYPE:NORMALLY OPEN(N O) ALARM SEVERITY:CRITICAL ROUTE OF THE ALARM ROOT CAUSE:WHEN THE SENSOR SENSE THE OIL PRESSURE IN ENGINE GOES BELOW THAN SPECIFIED PRESSURE. LLOP SENSOR PIU/AMF DDF BTS
15
Alarm type: normally open(n o) Alarm severity: major
High room temperature Alarm type: normally open(n o) Alarm severity: major Route of the alarm: ROOT CAUSE:WHEN THE TEMPERATURE REACHES 45DEGREE OR TEMPERATURE REACHES ALARMING TEMP LEVEL DDF BTS MICRO CONTROLLER
16
THIS ALARMS WORKS WHEN BOTH THE A/C GETS FAILS
AC FAILS THIS ALARMS WORKS WHEN BOTH THE A/C GETS FAILS ALARM TYPE:NORMALLY OPEN(N O) ALARM SEVERITY: MINOR ROUTE OF THE ALARM: ROOT CAUSE:WHEN BOTH THE A/C GETS FAILS. DDF BTS MICRO CONTROLLER
17
THIS ALARM GET ON WHEN ANY ONE OF THE A/C GETS FAILED
AC 1 &AC 2 FAILS THIS ALARM GET ON WHEN ANY ONE OF THE A/C GETS FAILED ALARM TYPE:NORMALLY OPEN(N O) ALARM SEVERITY:MINOR ROUTE OF THE ALARM: ROOT CAUSE:WHEN AC 1 FAILS OR AC 2 FAILS DDF BTS MICRO CONTROLLER
18
WORKS WHEN ANY ONE OF THE RECTIFIER GETS FAILS.
RECTIFIER FAILS WORKS WHEN ANY ONE OF THE RECTIFIER GETS FAILS. ALARM TYPE:NORMALLY OPEN(NO) ALARM SEVERITY:MINOR ROUTE OF ALARM: ROOT CAUSE:WHEN ANY ONE RECTIFIER FAILS DDF BTS ALARM PANEL OF P.P
19
this works only when the p p voltage reaches alarming voltage level
Low battery level this works only when the p p voltage reaches alarming voltage level Alarm type: normally open(n o) Alarm severity: critical Route of the alarm: Root cause: when the power plant voltage reaches 47v(alarming voltage level) DDF BTS ALARM PANEL OF P.P
20
THIS ALARM GETS ON WHEN THE DOOR OF THE SHELTER GET OPEN
DOOR OOPEN THIS ALARM GETS ON WHEN THE DOOR OF THE SHELTER GET OPEN ALARM TYPE:NORMALLY CLOSED(N C) ALARM SEVERITY:MAJOR/MINOR/CRITICAL(DEPENDS) ROUTE OF THE ALARM: ROOT CAUSE:WHEN THE DOOR IS OPEN DOOR SENSOR PIU/AMF DDF BTS
21
THIS ALARMS WORKS WHEN THERE IS FIRE OR SMOKE AT THE SITES
FIRE AND SAFETY ALARM THIS ALARMS WORKS WHEN THERE IS FIRE OR SMOKE AT THE SITES ALARM TYPE:NORMALLY OPEN ALARM SEVERITY:CRITICAL ROUTE OF THE ALARM: ROOT CAUSE:WHEN THERE IS FIRE OR SMOKE ATH THE SITES FIRE &SMOKE SENSOR PIU/AMF DDF BTS
22
FIRE AND SMOKE ALARMS
23
THIS ALARMS WORKS WHEN THERE IS LOAD ON DG
SITE ON DG THIS ALARMS WORKS WHEN THERE IS LOAD ON DG ALARM TYPE:NORMALLY OPEN(N O) ALARM SEVERITY:MINOR ROUTE OF THE ALARM: ROOT CAUSE:WHEN THERE IS LOAD ON DG. PIU/AMF DDF BTS
24
TYPES OF BTS AND ALRAM IT CONTAINS
NOKIA ULTRA BTS:12 ALARMS MAIN FAILS RECTIFIER FAILS LOW BATTERY VOLTAGE SITE ON BATTERY SITE ON DG LLOP LOW FUEL LEVEL DG FAILS TO START AC FAILS DOOR OPEN HIGH ROOM TEMPERATURE FIRE AND SMOKE AT SITE
25
RBS 2964:16 ALARMS SITE ON DG DG FAILS TO START MAIN FAILS
HIGH ROOM TEMPEERATURE LOW FUEL LEVEL LLOP DG FAILS TO STOP FIRE AND SMOKE AT SITES DOOR OPEN AC 1 OFF AC 2 OFF SPARE B BATTERY FUSE FAILS
26
RECTIFIER FAILS LOW BATTERY LEVEL SMPS FAILS
27
HUAWEI 3900 Intruder Ac fails High room temperature
Fire and smoke alarm Fire fighting Mains failure Dg fails to start Site on dg Rectifier high voltage Tower light failure Rectifier 2/more failure Site on battery Low battery voltage Rectifier fails Generator auto mode Low fuel level
28
ZTE ZXG-10 TEMPERATURE ALARM LOW BATTERY ALARM DG FAILSS TO START
AC MAINS FAILURE DOOR ALARMS AIR CONDITIONER ALARM SMOKE ALARM SMR MODEL ALARM DG IN OPERATION LOW FUEL TANK.
29