Presentation is loading. Please wait.

Presentation is loading. Please wait.

D - connection DELTA 3-phase distribution system

Similar presentations


Presentation on theme: "D - connection DELTA 3-phase distribution system"— Presentation transcript:

1 D - connection DELTA 3-phase distribution system
400 V (= nominal voltage), 50 Hz N L2 L3 Phase Voltage = 230 V Phase to Phase Voltage = √3 * 230 V = 400 V L1 Peak voltages = √2 * Nominal voltages Y - Connection WYE D - connection DELTA Symmetric 3-phase load: P = √3 * Uphase-phase * I * cosΦ S = √3 * Uphase-phase * I = 3 * Uphase * I * cosΦ S = 3 * Uphase * I Q = √3 * Uphase-phase * I * sinΦ S2 = P2 + Q2 = 3 * Uphase * I * sinΦ

2 Single Phase 50 Hz Supply Voltage
Vpeak = √2 * 230 V Amplitude of the voltage Voltage Current T = 1/f = 1/50 Hz = 20 ms

3 Resistive - Inductive load: Voltage and current
Inductive load, Voltage * Current S = U * I - Negative Power Power/Watts

4 N L1 L2 L3 PE Phase Voltage = 230 V Ground SOCKET
Phase wires: L1 L2 L3 Neutral wire: N Protective wire: PE N L2 L3 L1 PE SOCKET 230 V FUSE Ground

5 Power triangel Inductive load Apparent Power (VA) S = U * I
Reactive Power (VAr) Q phase angle φ True Power (W) P sine φ = Q/S Power factor = cos φ = P/S S2 = P2 + Q2 P = U * I * cos φ Power factor = 1...0 Smaller power factor means more reactive power.

6

7

8 Example

9 Solution: Powers: cosφ = 0,7 φ = 45,57 0
S = 2200 VA/cos45,570 = 3143 VA Q = 3143 * sin45, = 2244 Var Solution: φ P = 2200 W Q = 2244 Var S = 3143 VA Current: S = U * I I = 3143 VA/230 V = 13,66 A Impedances: Z = U/I = 230 V/13,66 A = 16,83 Ω R = 0,7 * 16,83 Ω = 11,78 Ω XL = sin 45,570 * 16,83 Ω = 12,02 Ω Capacitor to correct power factor: QC = QL = U2/XC XC = 1/(2∏*f*C) C = Q/(2∏*f*U2) = 2244 VA/(2∏*50s-1*(230 V)2) = 135 uF Current with capacitor: I = P/U = 2200 VA/230 V = 9,57 A Hence the current is reduced 4,09 A

10 Detection of insulation faults
An insulation fault may be the consequence of insulation deterioration: c between two live conductors, c between a conductor and the ECPs or the protective conductor, c on a single live conductor, making the conductor accessible to touch. An insulation fault between live conductors becomes a short-circuit. In all other cases, a fault (in common mode) causes current to flow to earth. This current, which does not flow back via the live conductors, is called the earth-fault current. It is the algebraic sum of the instantaneous values of the currents flowing in the live conductors, hence the name "residual current". Remark: If the currents are sinusoidal, Fresnel vector representation may be used and it is possible to speak of the "vector sum" of the currents. However this representation is not relevant in the presence of harmonic currents and the term "algebraic sum" is therefore more generally applicable. This current may be due to an insulation fault between a live conductor and the ECPs (risk of indirect contact) or to a failure of the measures used to insulate or isolate live parts (risk of direct contact). These situations are shown in figure 7 next page. Similarly, in all cases of direct contact, the fault current is low and cannot be detected and cleared by standard overcurrent protective devices. This is also the case for leakage currents that constitute fire hazards. Under these conditions, the fault current must be detected and cleared by a special device, i.e. a residual-current device (RCD), discussed in the next section.

11


Download ppt "D - connection DELTA 3-phase distribution system"

Similar presentations


Ads by Google