Presentation is loading. Please wait.

Presentation is loading. Please wait.

ACT20X Ex isolator/ amplifier. Page 2 ACT20X (Ex isolators family) Overview - Connects to process equipment in Class/Div, or Zone 0 - Zone 2 areas - ACT20X.

Similar presentations


Presentation on theme: "ACT20X Ex isolator/ amplifier. Page 2 ACT20X (Ex isolators family) Overview - Connects to process equipment in Class/Div, or Zone 0 - Zone 2 areas - ACT20X."— Presentation transcript:

1 ACT20X Ex isolator/ amplifier

2 Page 2 ACT20X (Ex isolators family) Overview - Connects to process equipment in Class/Div, or Zone 0 - Zone 2 areas - ACT20X is not a zener barrier – it is an isolating amplifier - ACT20X is mounted in a safe area – or Zone 2, or Class 1 Div 2 area (always in a protective enclosure or panel) - Digital or analog types total 16 models - Signals are either from, or going to, the hazardous area. - PC configuration via CBX200 interface & WI-Manager software

3 Page 3 Digital types Product Definition Example description… ACT20X - 2HDI – 2SDO - S PS Digital input 1 from hazardous area Digital input 2 from hazardous area Digital output 1 to safe area - 2HDI -- 2SDO - Aux power input (19,2 – 31,2 Vdc) Screw terminals

4 Page 4 Housing Features 22,5mm wide format 1 or 2 channel variants for higher density Blue covers identify hazardous connections Function LEDs show operaring status Terminal numbers visible on front Terminal coding prevents mis-wiring Power cross - connections via the mounting rail (option coming)

5 Page 5 9 x Digital types ACT20X range PS Pulse Isolator Solenoid/Alarm Driver

6 Page 6 7 x Analog types ACT20X range PS HART input isolator IIII HART output isolator

7 Page 7 Customers Target customers:  Oil refineries – operators of hazardous processes  Oil & Gas Industry OEMs – or systems integrators supplying controls and drives  Waste Water systems integrators – sludge handling plant  Fuel handling OEMs – for power plant  Metering / gas distribution companies

8 Thank you for your interest!

9 Page 9

10 Page 10 Pulse isolator - t ypical flow application Control system Power Supply +- Hazardous AreaSafe or Div. 2 or Zone 2 Area ACT20X-HDI-SDO +24vdc PS Pulse-output (Namur) Flowmeter Process vessel Controller Frequency proportional to flow

11 Page 11 Pulse isolator - t ypical level application Control system High level switch Power Supply + - Combustable fluid Hazardous AreaSafe or Div. 2 or Zone 2 Area ACT20X-2HDI-2SDO To other isolators +24vdc Low level switch 0 1 0 1 PS

12 Page 12 ACT20X – SDI Actuator / alarm driver Control system Hazardous AreaSafe or Zone 2 or Div 2 Area ACT20X-2SDI-2HDO Ex Alarm sounder DC Power Supply 24Vdc + - Solenoid valve Valve open/close signal PS Combustable fluid Output 2 Output 1

13 Page 13 Main competitors – Phoenix Contact  MACX Analog MACX offers following functions Repeater power supply (HART Transparent) Output isolating amplifier, NAMUR switching amplifiers, ( Relay and digital output) Solenoid alarm driver Temperature converter with FDT/DTM-Software Comparing with Wm, MACX has:  12,5mm width per module  Only the temperature converter is configurable with FDT/DTM-Software  SIL2  Power Bus integrated  Only ATEX and IECEX approvals – no Class & Div  Ambient temperature -20…+60°C  No dedicated alarm output  No Universal model  Higher (20%) pricing

14 Page 14 Main competitors - Pepperl+Fuchs K – System K- System offers following functions : Isolating amplifiers (2-3 wire transmitters), 1or 2 channels, DC Converter U/I versions with HART communication NAMUR switching amplifiers, 1, 2, 4 channels (Relay and digital outputs) + options with timer relay Solenoid/alarm driver with logic input, 1,2- channels Temperature converters (Thermo, PT 100) with DIP switches and PC configurable Trip amplifiers Frequency converters / flow measurements Comparing with Wm, K-System has:  22,5 and 45mm width per module  Dip switches and PC (FDT/DTM) configuration  SIL2 available  Power bus integrated  No Universal input model  Higher (25%+) pricing

15 Page 15 Pulse isolators – input types 1kΩ Supply voltage8 – 9V (typ. 8.2V) DIN19234 Input resistance  Proximity switches (8.2V) - Position, motor speed, flow measurement  Volt-free contacts - Flow, pressure, valve limit switches  Open / short circuit detection - Resistors at the sensor 1.1mA max Signal –Low (0) 2.2mA min Signal -High (1) Hi/Lo threshold 1.6mA PS Initiator Parameters Proximity input Relay input inc. short / open circuit detection Max frequency 5kHz

16 Page 16 ACT20X Pulse isolator wiring