Presentation is loading. Please wait.

Presentation is loading. Please wait.

Instantaneous power p(t) flowing into the box

Similar presentations


Presentation on theme: "Instantaneous power p(t) flowing into the box"— Presentation transcript:

1 Instantaneous power p(t) flowing into the box
SG_140122_Power_Definitions_and_Transformers_Presentation.ppt Instantaneous power p(t) flowing into the box Circuit in a box, two wires + Circuit in a box, three wires + Any wire can be the voltage reference Works for any circuit, as long as all N wires are accounted for. There must be (N – 1) voltage measurements, and (N – 1) current measurements.

2 Average value of periodic instantaneous power p(t)
SG_140122_Power_Def

3 Two-wire sinusoidal case
zero average Power factor Average power SG_140122_Power_Def

4 Root-mean squared value of a periodic waveform with period T
Compare to the average power expression compare The average value of the squared voltage Apply v(t) to a resistor rms is based on a power concept, describing the equivalent voltage that will produce a given average power to a resistor SG_140122_Power_Def

5 Root-mean squared value of a periodic waveform with period T
For the sinusoidal case SG_140122_Power_Def

6 Given single-phase v(t) and i(t) waveforms for a load
Determine their magnitudes and phase angles Determine the average power Determine the impedance of the load Using a series RL or RC equivalent, determine the R and L or C SG_140122_Power_Def

7 Determine voltage and current magnitudes and phase angles
Using a cosine reference, Voltage cosine has peak = 100V, phase angle = -90º Current cosine has peak = 50A, phase angle = -135º Phasors SG_140122_Power_Def

8 The average power is SG_140122_Power_Def

9 Voltage – Current Relationships
SG_140122_Power_Def

10 (no differential equations are needed)
Thanks to Charles Steinmetz, Steady-State AC Problems are Greatly Simplified with Phasor Analysis (no differential equations are needed) Time Domain Frequency Domain Resistor voltage leads current Inductor current leads voltage Capacitor SG_140122_Power_Def

11 Problem 10.17 SG_140122_Power_Def

12 SG_140122_Power_Def

13 SG_140122_Power_Def

14 Active and Reactive Power Form a Power Triangle
Q Projection of S on the real axis Projection of S on the imaginary axis Complex power S is the power factor SG_140122_Power_Def

15 Question: Why is there conservation of P and Q in a circuit?
Answer: Because of KCL, power cannot simply vanish but must be accounted for Consider a node, with voltage (to any reference), and three currents IA IB IC SG_140122_Power_Def

16 Voltage and Current Phasors for R’s, L’s, C’s
Voltage and Current in phase Q = 0 Resistor Voltage leads Current by 90° Q > 0 Inductor Current leads Voltage by 90° Q < 0 Capacitor SG_140122_Power_Def

17 Projection of S on the real axis Projection of S on the imaginary axis
Q Projection of S on the real axis Projection of S on the imaginary axis Complex power S SG_140122_Power_Def

18 Resistor also so , Use rms V, I SG_140122_Power_Def

19 Inductor also so , Use rms V, I SG_140122_Power_Def

20 Capacitor also so , Use rms V, I SG_140122_Power_Def

21 Active and Reactive Power for R’s, L’s, C’s
(a positive value is consumed, a negative value is produced) Active Power P Reactive Power Q Resistor Inductor Capacitor source of reactive power SG_140122_Power_Def

22 Now, demonstrate Excel spreadsheet EE411_Voltage_Current_Power.xls
to show the relationship between v(t), i(t), p(t), P, and Q SG_140122_Power_Def

23 A Single-Phase Power Example
SG_140122_Power_Def

24 A Transmission Line Example
Calculate the P and Q flows (in per unit) for the loadflow situation shown below, and also check conservation of P and Q. j0.15 pu ohms j0.20 pu mhos PL + jQL VL = 1.020 /0 VR = 1.010 / - 1 PR + jQR IS IcapL IcapR SG_140122_Power_Def

25 SG_140122_Power_Def

26 SG_140122_Power_Def

27 0.05 + j0.15 pu ohms j0.20 pu mhos PL + jQL VL = 1.020 /0 ° VR = 1.010
- 1 PR + jQR IS IcapL IcapR SG_140122_Power_Def

28 RMS of some common periodic waveforms
Duty cycle controller DT T V 0 < D < 1 By inspection, this is the average value of the squared waveform SG_140122_Power_Def

29 RMS of common periodic waveforms, cont.
Sawtooth V T SG_140122_Power_Def

30 RMS of common periodic waveforms, cont.
Using the power concept, it is easy to reason that the following waveforms would all produce the same average power to a resistor, and thus their rms values are identical and equal to the previous example V V -V V V V V SG_140122_Power_Def

31 2. Three-Phase Circuits SG_140122_Power_Def

32 Three Important Properties of Three-Phase Balanced Systems
Because they form a balanced set, the a-b-c currents sum to zero. Thus, there is no return current through the neutral or ground, which reduces wiring losses. A N-wire system needs (N – 1) meters. A three-phase, four-wire system needs three meters. A three-phase, three-wire system needs only two meters. The instantaneous power is constant Three-phase, four wire system a b c n Reference SG_140122_Power_Def

33 Observe Constant Three-Phase P and Q in Excel spreadsheet
1_Single_Phase_Three_Phase_Instantaneous_Power.xls SG_140122_Power_Def

34 SG_140122_Power_Def The p hasors are rotating counter - clockwise .
The magnitude of line to line voltage phasors is 3 times the magnitude of line neutral phas ors. V bn ab = an bc b n c cn 30° 120° Imaginary Real ca SG_140122_Power_Def

35 Conservation of power requires that the magnitudes of
delta currents I ab , I ca , and I bc are 3 1 times the magnitude of line currents I a b c . V an bn cn Real Imaginary = 30° I Vab Balanced Sets Add to Zero in Both Time and Phasor Domains + I = 0 + V n Line currents I Delta currents I SG_140122_Power_Def

36 SG_140122_Power_Def

37 (i.e., same line currents I a , I b c and phase - to phase voltages V
The Two Above Sources are Equivalent in Balanced Syst ems (i.e., same line currents I a , I b c and phase - to phase voltages V ab , V bc ca in both cases ) V + I n SG_140122_Power_Def

38 The Experiment: Opening and closing the switch has no effect because I
Z a b V ab + I c n KCL: I = I + I But for a balanced set, = 0, so I = 0 Ground (i.e., V = 0) The Experiment: Opening and closing the switch has no effect because I is already zero for a three - phase balanced set. Since no current flows, even if there is a resistance in the grounding path, we must conclude that = 0 at the neutral point (or equivalent neutral point) of any balanced three phase load or source in a bala nced system. This allows us to draw a “one line” diagram (typically for phase a) and solve a single phase problem. Solutions for phases b and c follow from the phase shifts that must exist. SG_140122_Power_Def

39 SG_140122_Power_Def Z l ine c c I c 3Z load 3Z load b a b a Z l ine I
V ab + Z l ine I b Balanced three - phase systems, no matter if they are delta connected, wye connected, or a mix, are easy to solve if you Z follow these steps : l ine a I a 1. Convert the entire circuit to an equivalent wye with a a ground ed neutral . 2. Draw the one - line diagram for phase a , recognizing that phase a has one third of the P and Q . 3. Solve th e one - line diagram for line - to - neutral voltages and + The “One - Line” line currents . Z Van load Diagram 4. If needed, compute l ine - to - neutral voltages and line currents for phases b and c using the ±120° relationships. 5. If needed, compute l ine - to - line voltages and delta currents n n using the 3 and 30 relationships. SG_140122_Power_Def

40 Now Work a Three-Phase Motor Power Factor Correction Example
A three-phase, 460V motor draws 5kW with a power factor of 0.80 lagging. Assuming that phasor voltage Van has phase angle zero, Find phasor currents Ia and Iab and (note – Iab is inside the motor delta windings) Find the three phase motor Q and S How much capacitive kVAr (three-phase) should be connected in parallel with the motor to improve the net power factor to 0.95? Assuming no change in motor voltage magnitude, what will be the new phasor current Ia after the kVArs are added? SG_140122_Power_Def

41 Now Work a Delta-Wye Conversion Example
Part c. Draw a phasor diagram that shows line currents Ia, Ib, and Ic, and load currents Iab, Ibc, and Ica. SG_140122_Power_Def

42 3. Transformers SG_140122_Power_Def

43 Transformer Core Types
SG_140122_Power_Def

44 High-Voltage Grid Transformers, 100’s of MW
SG_140122_Power_Def

45 Single-Phase Transformer
Turns ratio 7200:240 (30 : 1) (but approx. same amount of copper in each winding) Φ Rs jXs Ideal Transformer 7200:240V Rm jXm 7200V V SG_140122_Power_Def

46 (but approx. same amount of copper in each winding)
Short Circuit Test Short circuit test: Short circuit the 240V-side, and raise the 7200V-side voltage to a few percent of 7200, until rated current flows. There is almost no core flux so the magnetizing terms are negligible. + Vsc - Isc Rs jXs Ideal Rm jXm Transformer 7200:240V 7200V V Turns ratio 7200:240 (but approx. same amount of copper in each winding) Φ SG_140122_Power_Def

47 (but approx. same amount of copper in each winding)
Open Circuit Test Ioc Rs jXs + Voc - Ideal Rm jXm Transformer 7200:240V 7200V V Open circuit test: Open circuit the 7200V-side, and apply 240V to the 240V-side. The winding currents are small, so the series terms are negligible. Turns ratio 7200:240 (but approx. same amount of copper in each winding) Φ SG_140122_Power_Def

48 1. Given the standard percentage values below for a 125kVA transformer, determine the R’s and X’s in the diagram, in Ω. 2. If the R’s and X’s are moved to the 240V side, compute the new Ω values. Single Phase Transformer. Percent values are given on transformer base. Winding 1 kv = 7.2, kVA = 125 Winding 2 kv = 0.24, kVA = 125 %imag = 0.5 %loadloss = 0.9 %noloadloss = 0.2 %Xs = 2.2 Load loss Xs No load loss Magnetizing current Rs jXs Ideal Transformer 7200:240V Rm jXm 7200V V 3. If standard open circuit and short circuit tests are performed on this transformer, what will be the P’s and Q’s (Watts and VArs) measured in those tests? SG_140122_Power_Def

49 X / R Ratios for Three-Phase Transformers 345kV to 138kV, X/R = 10
Substation transformers (e.g., 138kV to 25kV or 12.5kV, X/R = 2, X = 12% 25kV or 12.5kV to 480V, X/R = 1, X = 5% 480V class, X/R = 0.1, X = 1.5% to 4.5% Rs jXs Ideal Transformer Rm jXm SG_140122_Power_Def

50 Saturation – relative permeability decreases rapidly after 1.7 Tesla
Relative permeability drops from about 2000 to about 1 (becomes air core) Magnetizing inductance of the core decreases, yielding a highly peaked magnetizing current Linear Scale Log10 Scale SG_140122_Power_Def

51 Transformer Core Saturation
No DC Log10 Scale Magnetizing Current for Single-Phase 25 kVA. 12.5kV/240V Transformer. THDi = 76.1%, Mostly 3rd Harmonic. No DC With DC Linear Scale SG_140122_Power_Def

52 Apply a DC Voltage to a Transformer and Watch It Saturate
Where there is a DC current, there is a DC voltage, and vice-versa Voltage Current Saturates SG_140122_Power_Def

53 B-H Curve Constructed from V-I Measurements Shows Linear Region, Saturation, Hysteresis, and Residual Magnetism Shape of normal hysteresis path Severe saturation Severe hysteresis Residual magnetism SG_140122_Power_Def

54 Distribution Feeder Loss Example
Annual energy loss = 2.40% Largest component is transformer no-load loss (45% of the 2.40%) Modern Distribution Transformer: Load loss at rated load (I2R in conductors) = 0.75% of rated transformer kW. No load loss at rated voltage (magnetizing, core steel) = 0.2% of rated transformer kW. Magnetizing current = 0.5% of rated transformer amperes 54

55 Single-Phase Transformer Impedance Reflection from High-Side (H) to Low-Side (L) by the Square of the Turns Ratio Rs jXs Ideal Transformer 7200:240V Rm jXm 7200V V Faraday’s law Conservation of power Ideal Transformer 7200:240V 7200V V SG_140122_Power_Def

56 Now Work a Single-Phase Transformer Example
Open circuit and short circuit tests are performed on a single - phase, 7200:240V, 25kVA, 60Hz distribution transformer. The results are: Short circuit test (short circuit the low - voltage side, energize the high - voltage side so that rated current flows , an d measure P s c and Q s c ). Measure d P s c = 400W, Q s c = 200VAr . Open circuit test (open circuit the high - voltage side, apply rated voltage to the low - voltage side , and measure P oc and Q oc ). Measure d P oc = 100W, Q oc = 250VAr . Determine the four impedance val ues (in ohms) for the transformer model shown. Turns ratio 7200:240 (30 : 1) (but approx. same amount of copper in each winding) Φ Rs jXs Ideal Transformer 7200:240V Rm jXm 7200V V SG_140122_Power_Def

57 A three-phase transformer can be three separate single-phase transformers, or one large transformer with three sets of windings Rs jXs Ideal Transformer N1 : N2 Rm jXm Wye-Equivalent One-Line Model A N N1:N2 N1:N2 Reflect side 1 wye ohms to side 2 wye ohms by multiplying by [N2 / N1]^2 N1:N2 Standard 345/138kV autotransformers, GY - GY, with a tertiary 12.5kV Δ winding to provide circulating 3rd harmonic current Y - Y SG_140122_Power_Def

58 For Delta-Delta Connection Model, Convert the Transformer to Equivalent Wye-Wye
Ideal Transformer A N Wye-Equivalent One-Line Model N1:N2 Reflect side 1 delta ohms to side 2 delta ohms by multiplying by [N2 / N1]^2 Convert side 2 delta ohms to wye ohms by dividing by 3 Convert side 1 delta ohms to wye ohms by dividing by 3 Above circuit results in the proper reflection. Note that N2/Sqrt3 divided by N1/Sqrt3 is the same as N2 divided by N1 N1:N2 N1:N2 Δ - Δ SG_140122_Power_Def

59 For Delta-Wye Connection Model, Convert the Transformer to Equivalent Wye-Wye
Standard building entrance and substation transformers. Δ high side/ GY low side Ideal Transformer A N Wye-Equivalent One-Line Model N1:N2 Reflect side 1 delta ohms to side 2 wye ohms by multiplying by [N2 / N1]^2 Convert side 1 delta ohms to wye ohms by dividing by 3 Above circuit results in the proper reflection N1:N2 N1:N2 Δ - Y SG_140122_Power_Def

60 For Wye-Delta Connection Model, Convert the Transformer to Equivalent Wye-Wye
Ideal Transformer A N Wye-Equivalent One-Line Model N1:N2 Reflect side 1 wye ohms to side 2 delta ohms by multiplying by [N2 / N1]^2 Convert side 2 impedances from delta ohms to wye ohms by dividing by 3 Above circuit results in the proper reflection N1:N2 N1:N2 Y - Δ So, for all configurations, the equivalent wye-wye transformer ohms can be reflected from one side to the other using the three-phase bank line-to-line turns ratio SG_140122_Power_Def

61 But there is no phase shift in any of the individual transformers
For wye-delta and delta-wye configurations, there is a phase shift in line-to-line voltages because the individual transformer windings on one side are connected line-to-neutral, and on the other side are connected line-to-line But there is no phase shift in any of the individual transformers This means that line-to-line voltages on the delta side are in phase with line-to-neutral voltages on the wye side Thus, phase shift in line-to-line voltages from one side to the other is unavoidable, but it can be managed by standard labeling to avoid problems caused by paralleling transformers SG_140122_Power_Def


Download ppt "Instantaneous power p(t) flowing into the box"

Similar presentations


Ads by Google