© 2003 Eaton Corporation. All rights reserved. Understanding Harmonics Richard Molloy Technology Sales Manager, Power Quality.

Slides:



Advertisements
Similar presentations
ACTIVE POWER FILTER FOR POWER COMPENSATION
Advertisements

POWER QUALITY BACKGROUND & ELEC-SAVER TVSS
Copyright© Voltimum Experts – not to be reproduced without prior consent of Voltimum UK Voltimum Expert Topic – Power Harmonics.
QUALITY & TECHNOLOGY HARMONIC PROBLEMS IN CAPACITOR BANKS.
1 POWER QUALITY -- Bhanu Bhushan -- June, How close is the supply voltage waveform to sinusoidal, and how close are the supply voltage and frequency.
Mike Thornton National Sales Manager
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
QUALITY AND TECHNOLOGY
Siemens Building Technologies Building Technologies Variable Frequency Drives Harmonics Overview.
Chapter 4 DC to AC Conversion (INVERTER)
EMC in Electrical Power Systems Frithiof Jensen Power System Engineer November 12, 2013.
VARIABLE SPEED DRIVES HARMONIC EFFECTS & EFFECT OF USE WITH LONG CABLES (100 – 300m) Electric Motors & Drives ….OUR VISION, YOUR SOLUTION ……. TOGETHER.
2010 ASHRAE Rocky Mountain Chapter VFD Fundamentals April 16, 2010 Jeff Miller - ABB © ABB Month DD, YYYY | Slide 1 1.
VARIABLE SPEED DRIVES AND FILTERS CLASSIFICATION AND APPLICATION.
Introduction to ElectroFlow TM System Dhaka, March 8, 2003 Mahmuduzzaman Khan Green Power Canada.
EXPERIMENTAL STUDY AND COMPARATIVE ANALYSIS OF TRANSFORMER HARMONIC BEHAVIOUR UNDER LINEAR AND NONLINEAR LOAD CONDITIONS.
ISSBN, Electronic faculty of Niš, November Use of distortion power for side identification of the harmonic polution Dejan Stevanović, Electronic.
Dry type transformers Zaragoza Traction application
Understanding of Harmonics in Power Distribution System
Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc.
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Chapter 8 Inverters AC Power • Inverters • Power Conditioning Units • Inverter Features and Specifications.
PRODUCTS TRANSFORMERS ENERGY SAVING TRANSFORMERS (EST) TRANSFORMER RECTIFIER UNITS 3 rd HARMONIC REJECTION TRANSFORMERS (HRT) ULTRA HIGH ISOLATION TRANSFORMERS.
Power Electronics Lecture-11 Inverters Dr. Imtiaz Hussain
Unit 29 Three-Phase Transformers. Objectives: Discuss the construction of three-phase transformers. Discuss the formation of a three-phase transformer.
ISA Northern California Section, South Bay October 14, 2003 Craig Chidester
/1 Testing Harmonics and Flicker /1 Harmonics & Flicker Two different test standards: EN & EN EN controls.
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
Power Distribution Harmonics Case Study of 285-3F Chiller Plant Michael W. Harmon Principle Engineer Savannah River Nuclear Solutions, LLC Savannah River.
Protection Against Transient Overvoltages
Frankfurt (Germany), 6-9 June 2011 Economic assessment of PQ solutions Helge SELJESETH – Norway – RT 2b – Economic assessment of PQ solutions.
Power Quality Partnership
By A.D.Thirumoorthy Tamil Nadu Electricity Board India.
PQSynergy TM 2011 Harmonic Assessment of PEA North1, Chiangmai’s Customers in North Industrial Estate Chotepong Pongsriwat. M.Eng(EE) Chief of Power.
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
7154 VFD Presentation #2 May 2002 Paul Weingartner.
Applied Harmonics Control of Harmonics
VLT ® Low Harmonic Drive. | Property of Danfoss Drives A/S | Tuesday, 15 September 2015 | 2 Acoustic noise Planes, trains, automobiles, busses, construction.
1 Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro Organized by Task Force on Harmonics Modeling & Simulation.
Electrical Distribution Systems
POWER QUALITY.
Chapter 3 Power System Harmonic Mitigation. INTRODUCTION Power system harmonic issues have existed since the early 1900 ’ s. The earliest discovered issues.
Voltimum Expert Topic – Power Harmonics. What are Harmonics? They are waveforms with frequencies that are multiples of the fundamental frequency (Typically.
Harmonics and PFC The love story By Pol Nisenblat.
IEEE PES General Meeting, Tampa FL June 24-28, Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro.
1 POWER QUALITY -- Bhanu Bhushan -- April, Simple examples around us : Ceiling fan regulators Tube lights Lap-tops & peripherals Domestic inverters.
Lecture # 16 &17 Complementary symmetry & push-pull Amplifiers
Electromagnetic Compatibility Test for CMS Experiment. Authors C. Rivetta– Fermilab F. Arteche, F. Szoncso, - CERN.
Understanding Power Quality Monitoring
1 Power Quality EKT 451 CHAPTER 8. 2 Introduction Utilities transmit electricity over power lines into home as an alternating current (AC) wave. This.
Introduction  Utilities transmit electricity over power lines into home as an alternating current (AC) wave.  This is how power travels through wiring.
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
Signal Analyzers. Introduction In the first 14 chapters we discussed measurement techniques in the time domain, that is, measurement of parameters that.
7/08/2002PP.AFD.07 Harmonic Quality1 of 49 Yaskawa Electric America Harmonic Currents, Voltages and Your Building Power System.
Power Analyser Fundamentals Power Analysis and Harmonics.
Power supply.
A DSP based on on-line UPS R.Padamaja G.Mamatha Reddy EEE EEE S.V.C.E S.V.C.E BY.
J.PRAKASH.  The term power quality means different things to different people.  Power quality is the interaction of electronic equipment within the.
Power Quality Issues Power Electronics Group.
DC Machine & Transformer
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
REVIEW OF CFL AND ITS HARMONIC IMPACT ON ELECTRICAL DISTRIBUTION SYSTEM Guide: Mr. Rijo Rajan, prepared by: Merin Lukose Lecturer, S7 EEE EEE department.
UPS Training: The Online UPS
Effects of Harmonics on Capacitors Electrical System
HARMONIC MITIGATION USING PASSIVE FILTERS
Power System Harmonics
Electromechanical Systems
ECE 333 Green Energy Systems
Power quality management for induction furnace foundry
Presentation transcript:

© 2003 Eaton Corporation. All rights reserved. Understanding Harmonics Richard Molloy Technology Sales Manager, Power Quality

Agenda l Introduction l Definition of ‘Power Quality’ l Identification of power quality problems l Harmonics – causes and effects l Mitigation techniques l Conclusion

The cost of poor power quality l Cost of power quality problems to European industry & commerce is estimated at €10 billion per annum l Expenditure on preventative measures is less than 5% of this

Definition of Power Quality l ‘A supply that is always available, always within voltage and frequency tolerance, with a pure, noise free, sinusoidal wave shape’ Source – Leonardo Power Quality Initiative

How good is good enough? l No definitive answer – entirely dependant on compatibility of equipment and supply

Power standards l Power standards are defined by the electricity regulator OFGEM n Standard EN n ‘Voltage characteristics of electricity supplied by public distribution systems’

EN l Long term interruptions10 to 50 l Short term interruptions30 to 1000 l Dips30 to 1000 l Short-term over-voltage<1.5kV l Steady state voltage230V +/- 10% for 95% of time l Voltage unbalance<2% for 95% of time

EN l Total harmonic distortion </= 8% for 95% of time l Transient over-voltagesMajority <6kV l Frequency50Hz +/- 1% for 99.5% of time l Frequency50Hz +/- 2% for 100% of time

Identification of problems l Harmonic distortion l Voltage sags (‘dips’, ‘brownouts’) l Voltage swells (‘surges’) l Outages (‘power cuts’, ‘blackouts’) l Transient voltage surges (‘spikes’) l Earthing (‘grounding’) l Poor power factor

© 2003 Eaton Corporation. All rights reserved. Harmonics

Definition l Waveforms with frequencies that are multiples of the fundamental frequency (50Hz UK & Europe, 60Hz North America)

Harmonic production l Half wave rectifier l Full wave rectifier l Thyristor Switching l or t I I I I t t t

Waveforms - Fundamental Fundamental Wave, 50Hz

Waveforms – Fundamental and 2nd Harmonic 2nd Harmonic, 100Hz Fundamental Wave, 50Hz

Waveforms - Fundamental, 2nd and 3rd harmonic

Fundamental + 2nd harmonic

Fundamental + 3rd harmonic

All wave-shapes can be reduced to a sine wave plus harmonics l Even a square wave l Square wave equation

Switched mode power supply current waveform

Harmonic spectrum of SMPS

Causes of harmonics l Harmonic currents are caused by the use of non-linear loads: n Switched mode power supplies n HF fluorescent ballasts n Compact fluorescent lamps n Inverters Variable frequency drives UPS systems

Effects of harmonics l Erroneous operation of control systems l Excessive heating in rotating machines l Overloading of transformers l Overloading of switchgear and cables l Nuisance tripping of circuit breakers

Effects of harmonics l Overloading of capacitors l Damage to sensitive electronic equipment l Excessive currents in neutral conductor

Effects of Triple-N harmonics l Triple-N harmonics are odd multiples of 3 times fundamental frequency, i.e., 3 rd, 9 th, 15 th etc. l They are all in phase and sum in the neutral conductor l Switched Mode Power Supplies (SMPS) produce a lot of 3 rd harmonic - this is especially problematic in commercial buildings due to the vast number of computers, office equipment etc.

Effects of Triple-N harmonics

l A 3-phase star connected system with a balanced linear load has no current flowing in the neutral l Where a lot of 3 rd (or other triple-N) harmonics are present, neutral currents can be considerably in excess of phase currents l This causes overheating of neutral conductors. Note these may only be 50% rated in older buildings l Neutrals do not normally have over-current protection

Limits on Harmonic Distortion l Harmonic currents flowing back to the supply cause harmonic voltage distortion due to the supply impedance l Governed by Engineering Recommendation G5/4 l Title : ‘Limits for Harmonics in the U.K. Electricity Supply System’. l Guidance ONLY

Mitigation measures l Neutral up-sizing l Passive filters l Active harmonic conditioners l Transformer based solutions

Neutral up-sizing l All neutrals in the system, including switchgear etc., must be rated for the neutral current as well as phase currents l A 4 or 5 core 3 phase cable is rated for current flowing in the phase conductors only. Current in the neutral can cause overheating of the cable l Above 7 th harmonic (350 Hz), skin effect should be considered l Cables should be de-rated in accordance with IEC / BS 7671 (Appendix 4)

Passive filters l Capacitor and reactor combination l Tuned to specific frequency l Requires higher voltage capacitors l Designed for a fixed system requirement

Harmonic production IHIH ILIL

Harmonics and capacitors IHIH ILIL ICIC

Effects of Resonance

Effect on power factor capacitors l Increase in current loading l Increase in dielectric loss n Dielectric Loss = l Increase in Dielectric Stress n Dielectric Stress =

Avoiding resonance with PFC capacitors l Calculate the Resonant Frequency

Adding reactors

Effect of adding reactors Current flowing into supply in A Series Reactor Tuned to the frequency shown below

Voltage across the capacitor at various tuning frequencies

Filters l Single Frequency Filter l Double Tuned Filter l 2nd Order High Pass Filter |z| f (Hz) |z| f (Hz) |z| f (Hz)

Harmonics In Practice Sub- Station

When others add to your system Sub- Station

Active harmonic conditioner l Harmonic current compensation, 2 nd to 25 th l Harmonic neutral current compensation l Global or selective harmonic current compensation l Site adjustable compensation parameters

Active harmonic conditioner AHC

AHC points of connection SUB BOARD 1 DIS BOARD SUB BOARD 2 INCOMING SUPPLY

AHC points of connection SUB BOARD 1 DIS BOARD SUB BOARD 2 AHC GLOBAL INCOMING SUPPLY

AHC points of connection SUB BOARD 1 DIS BOARD AHC PARTIAL SUB BOARD 2 AHC GLOBAL INCOMING SUPPLY

AHC points of connection SUB BOARD 1 AHC LOCAL DIS BOARD AHC PARTIAL SUB BOARD 2 AHC GLOBAL INCOMING SUPPLY

AHC advantages l Continued guaranteed effective harmonic compensation l Easy to use and install l Auto configures l NOT susceptible to harmonic overload l Expandable l Compatible with electric generators l Connected anywhere

Transformer based solutions l 3rd Harmonic rejection transformers l Phase shifting transformers l Isolation or harmonic suppression transformers

© 2003 Eaton Corporation. All rights reserved. Conclusions

l As more electronic equipment is used in industry and commerce, harmonics have become a major power quality problem – more harmonics are generated, and more equipment is adversely affected by these harmonics l A combination of good design practice and effective harmonic mitigation measures is required

Conclusions l The power quality required will be dependant upon the equipment to be operated at any given location l A holistic approach to power quality is required – one solution is unlikely to address all the problems – a combination of equipment will be required to achieve the quality required.

Power quality measurement l Most power quality problems can be measured or monitored – if you suspect a problem, we can conduct a PQ survey to identify: n Harmonic distortion n Transient voltage disturbance n Power factor n Load survey n Unbalance n Flicker

© 2003 Eaton Corporation. All rights reserved. Thank you