Long Line Modeling Issues Rev. 2.1 TSS Meeting January 20, 2011 R. Peter Mackin, P.E. DRAFT.

Slides:



Advertisements
Similar presentations
Chapter 6: The Standard Deviation as a Ruler and the Normal Model
Advertisements

Principles & Applications Small-Signal Amplifiers
6-4 Percent of a Number Do Now Multiply   15
ENE 428 Microwave Engineering
Chapter 4 Systems of Linear Equations; Matrices
1 Lecture 2 Transmission Line Characteristics 1. Introduction 2. Properties of Coaxial Cable 3. Telegraph Equations 4. Characteristic Impedance of Coaxial.
Pre-Calculus Chapter 6 Additional Topics in Trigonometry.
Area Of Shapes. 8cm 2cm 5cm 3cm A1 A2 16m 12m 10m 12cm 7cm.
Direct-Current Circuits
` Cumulative Frequency How to draw a cumulative frequency graph.
What is motion? An object is in motion when it’s distance from another object changes. What is a reference point? It is an object or place used to determine.
Sorting It All Out Mathematical Topics
Chapter 6 Equations 6.1 Solving Trigonometric Equations 6.2 More on Trigonometric Equations 6.3 Trigonometric Equations Involving Multiples Angles 6.4.
Multiple Regression and Model Building
Area Of Shapes. 8cm 2cm 5cm 3cm A1 A2 16m 12m 10m 12cm 7cm.
EE 369 POWER SYSTEM ANALYSIS
Copyright © Cengage Learning. All rights reserved.
Series Circuits: Other examples:. Series circuits - ________________________________________ _________________________________________ Assume: 1. _____________________________________________________.
Announcements Be reading Chapters 9 and 10 HW 8 is due now.
Chapter 4 Systems of Linear Equations; Matrices
INTRODUCTION With this chapter, we begin the discussion of the basic op-amp that forms the cornerstone for linear applications; that is, the signal is.
ENE 428 Microwave Engineering
Index Student Activity 1: Me and my shadow
UNIVERSITI MALAYSIA PERLIS
Introduction The use of the coordinate plane can be helpful with many real-world applications. Scenarios can be translated into equations, equations can.
6.7 Applications of Rational Expressions. Objective 1 Solve problems about numbers. Slide
Wes Marshall, P.E. University of Connecticut January 2007 CE 276 Site Design Chapter 2 – Interpolation & Slope.
Physics and Measurements.
ECE 333 Renewable Energy Systems Lecture 13: Per Unit, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
CHAPTER 9 Electrical Design of Overhead Lines
Ch. 3.1 – Measurements and Their Uncertainty
Introduction The use of the coordinate plane can be helpful with many real-world applications. Scenarios can be translated into equations, equations can.
Chapter 4 Systems of Linear Equations; Matrices
Multiples 1 X 2 = 22 X 2 = 43 X 2 = 6 4 X 2 = 8 What do you call 2,4,6,8 ?Multiples of 2 Why?
Christopher Dougherty EC220 - Introduction to econometrics (chapter 7) Slideshow: weighted least squares and logarithmic regressions Original citation:
Copyright © Cengage Learning. All rights reserved.
Integrals 5.
Check it out! : Working with Ratio Segments.
ENE 428 Microwave Engineering
Basic Electrical Engineering Lecture # 04 Simple Resistive Circuits Course Instructor: Engr. Sana Ziafat.
EKT 441 MICROWAVE COMMUNICATIONS
1 ECE 480 Wireless Systems Lecture 3 Propagation and Modulation of RF Waves.
Transmission Line “Definition” General transmission line: a closed system in which power is transmitted from a source to a destination Our class: only.
ENE 490 Applied Communication Systems Lecture 3 Stub matching, single- and two-port networks DATE: 27/11/06.
CHAPTER 4 TRANSMISSION LINES.
MULTIPLYING WITH FRACTIONS.
116/11/50 ENE 490 Applied Communication Systems Lecture 2 circuit matching on Smith chart.
Yi HUANG Department of Electrical Engineering & Electronics
Section 1.1 Rectangular Coordinates; Graphing Utilities; Introduction to Graphing Equations.
Instructor :Kashif Mehmood
1 HETEROSCEDASTICITY: WEIGHTED AND LOGARITHMIC REGRESSIONS This sequence presents two methods for dealing with the problem of heteroscedasticity. We will.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ENE 428 Microwave Engineering
 Scientific notation is simply a method for expressing, and working with, very large or very small numbers. It is a short hand method for writing numbers,
ANTENNA THEORY : Analysis and design Third edition
1.1: Objectives Properties of Real Numbers
Microwave Engineering by David M. Pozar Ch. 4.1 ~ 4 / 4.6
Module T1 Transmission Work problems 1, 2, 3, 6, 7, 8, 9 at end of Module T1. Turn in on Tuesday, Oct 24.
SWAMI VIVEKANAND COLLEGE OF ENGINEERING,INDORE(M.P)
Matrix Equations Step 1: Write the system as a matrix equation. A three-equation system is shown below. First matrix are the coefficients of all the.
Introduction The use of the coordinate plane can be helpful with many real-world applications. Scenarios can be translated into equations, equations can.
ECE 333 Green Electric Energy
ENE 429 Antenna and Transmission lines Theory
ENE 429 Antenna and Transmission lines Theory
Microwave Engineering
x/÷ Numbers Year 3-4 – Multiply and divide a multiple of 10
angle of elevation of the sun. OUTSIDE
Power System Analysis (EELE 4351)
4th Week Seminar Sunryul Kim Antennas & RF Devices Lab.
ENE 428 Microwave Engineering
Presentation transcript:

Long Line Modeling Issues Rev. 2.1 TSS Meeting January 20, 2011 R. Peter Mackin, P.E. DRAFT

Basic Transmission Line Models (from Stevenson, Elements of Power System Analysis, 4 th Edition) Short Transmission Line: –Up to 50 miles Background Z = R + jX

Medium-length Transmission Line: –50 miles to 150 miles Background Z = R + jX Y2Y2 Y2Y2

Long Transmission Line: –Greater than 150 miles –Lumped parameters cannot be used accurately to represent these lines –Accurate representation requires the use of hyperbolic functions Background Y tanh(γl/2) 2 γl/2 Y2Y2 = sinh(γl) γl Z = Z Y2Y2

The Issue For long transmission lines (greater than say 150 miles), using the per mile impedance times the line length in miles can result in an inaccurate representation of the transmission line. For these long lines, it is better to use the long line equations that involve hyperbolic functions to calculate the line impedance. A couple of examples that illustrate the problem are given below.

Example #1 Assume a new 500 kV line with the following parameters –200 miles long –Horizontal conductor configuration 32 phase spacing, 35 minimum clearance to ground 3 – 1780 ACSR 84/19 Chukar conductors per phase 18 triangular bundle

Example #1 The table below shows the impedances for this line calculated using either the PowerWorld Transmission Line Parameter Calculator (TLPC) ver. 1.0 or Aspen Line Constants. The PowerWorld TLPC uses Long Line equations to calculate more accurate values of impedance and admittance for longer lines. Aspen Line Constants calculates a per mile impedance and then multiplies this value by the line length in miles to determine the line impedance and admittance.

Example #1 The example below shows the effects of the different impedance assumptions on the flow on this hypothetical line. The first power flow plot shows the flows on the line when using the long line impedance and admittance. The second power flow plot shows the flows on the line in the first plot when a new bus is added 60% of the total line distance from TESTBUS1. The third power flow plot shows the flows on the line when using inaccurate per mile impedance and admittance method used by Aspen Line Constants. The fourth power flow plot shows the flows on the line in the third plot when a new bus is added 60% of the total line distance from TESTBUS1.

Example #1 This power flow plot shows the flows on the line when using the long line impedance and admittance. Long Line Parameters

This power flow plot shows the flows on the line in the first plot when a new bus is added 60% of the total line distance from TESTBUS1. Long Line Parameters Example #1

Per Mile Line Parameters This power flow plot shows the flows on the line when using inaccurate per mile impedance and admittance method used by Aspen Line Constants. Example #1

This power flow plot shows the flows on the line in the third plot when a new bus is added 60% of the total line distance from TESTBUS1. Per Mile Line Parameters Example #1

Example #1 Conclusions As shown, long line impedance and admittance values provide the most accurate results for long lines. This conclusion can be observed by noting that the line flows before and after adding an intermediate bus to a line are almost exactly the same. Using per mile impedance and admittance values are not as accurate. This fact is demonstrated by the addition of an intermediate bus to the line using these parameters. As shown in the third and fourth power flow plots, the flow on the line is not the same in both cases (even though it should be).

Example #2 The first power flow plot shows the line flows on a 200 mile long 500 kV line that is modeled as 5 series pi sections of 40 miles each. The second power flow plot shows the line flows on a 200 mile long 500 kV line that is correctly modeled as 1 long line compensated segment (i.e., using PowerWorld Transcalc). The third power flow plot shows the line flows on a 200 mile long 500 kV line modeled as 1 Pi segment (incorrectly modeled using per mile impedances times line length in miles). The fourth power flow plot shows the line flows on a 200 mile long 500 kV line that was originally modeled using long line compensated impedances (Example #2, Plot #2), but is now split into two equal segments without recalculating the segment impedances. (This example is different than Example #1 in that the long line compensated impedances were simply divided in half. In example #1 the long line impedances were recalculated when adding the intermediate bus.)

200 Miles of 500 kV line modeled as 5 series Pi sections of 40 Miles each The first power flow plot shows the line flows on a 200 mile long 500 kV line that is modeled as 5 series pi sections of 40 miles each.

200 Miles of 500 kV line modeled as 1 long-line compensated segment The second power flow plot shows the line flows on a 200 mile long 500 kV line that is correctly modeled as 1 long line compensated segment (i.e., using PowerWorld Transcalc).

200 Miles of 500 kV line modeled as 1 Pi segment (Incorrectly Modeled) The third power flow plot shows the line flows on a 200 mile long 500 kV line modeled as 1 Pi segment (incorrectly modeled using per mile impedances times line length in miles).

200 Miles of 500 kV line split into two segments without recalculating the long line impedances The fourth power flow plot shows the line flows on a 200 mile long 500 kV line that was originally modeled using long line compensated impedances (Example #2, Plot #2), but is now split into two equal segments without recalculating the segment impedances. (This example is different than Example #1 in that the long line compensated impedances were simply divided in half. In example #1 the long line impedances were recalculated when adding the intermediate bus.)

Example #2 Conclusions GE PSLF properly corrects impedances for long lines if the line is split into multiple short segments (compare Plots #1 and #2). Incorrectly modeling a long line using per mile impedances times line length in miles results in slightly different (and incorrect) flows on the modeled line. If you add an intermediate bus to a long line, you must recalculate the new line impedances. You cannot just multiply the impedances by the ratio of the distance to the next bus divided by the total line length. This conclusion applies whether the original impedance was calculated using long line compensated impedances or per mile impedances.