Micro Design
System Capacity
Crop Water Needs Example Calculate capacity required for a proposed 1 ac. Micro irrigation system on Vegetables. Using drip tape with a flow of 0.45 gpm/100’ and 12” emitter spacing, 200 ft rows, 5 ft row spacing, and 10 fields of 0.1 ac each. Q = 453*DA T D =.2” / system efficiency A = Area T = 22 hrs
Crop Water Needs Example Answer Q = 453*DA T =453 x (.2”/.9) x 1 ac 22 hrs =4.5 gpm
Each field will have a capacity of 4.5 gpm. ◦ 200 ft rows with a 0.45 gpm/100’ drip tape flow will give you 0.9 gpm per row. ◦ At 5 ft row spacing, 1 ac will have approximately 10 fields, each of these fields will have 5 rows, 200 ft long. ◦ 5 rows times 0.9 gpm/row is 4.5 gpm per field. Minimum water requirement is 4.5 gpm for 1 ac, we only need to run 1 field at a time to meet the crop water demand.
Hours of irrigation per day to apply.2” (1 field of 0.1 ac each) T = 453*DA Q =453 x (.2”/.9) x 0.1 ac 4.5 gpm =2 hrs and 15 minutes
WELL 8:00 a.m. field 1 2 hrs and gpm 10:15 a.m. field 2 2 hrs and gpm 12:30 p.m. field 3 2 hrs and gpm 2:45 p.m. field 4 2 hrs and gpm 5:15 p.m. field 5 2 hrs and gpm 7:30 p.m. field 6 2 hrs and gpm 9:45 p.m. field 7 2 hrs and gpm 12:00 a.m. field 8 2 hrs and gpm 2:15 a.m. field 9 2 hrs and gpm 4:30 a.m. field 10 2 hrs and gpm
When you get to the field you discover that the well only produces 2.7 gpm. gpm/row water 3 rows and have15 sets
Hours of irrigation per day to apply.2” (given a well capacity of 2.7 gpm and fields of 3 rows each) T = 453*DA Q =453 x (.2”/.9) x 0.07 ac 2.7 gpm =2 hrs and 40 minutes
WELL 8:00 a.m. Field 1 2 hrs and gpm At 6:00 a.m. the pump has been running for 22 hrs and at 8:00 a.m. we need to go back to Field 1 but we haven’t irrigated all the fields!!!! 10:40 a.m. Field 2 2 hrs and gpm 1:20 p.m. Field 3 2 hrs and gpm 4:00 p.m. Field 4 2 hrs and gpm 6:40 p.m. Field 5 2 hrs and gpm 9:20 p.m. Field 6 2 hrs and gpm 12:00 a.m. Field 7 2 hrs and gpm 2:40 a.m. Field 8 2 hrs and gpm 5:20 a.m. Field 9 2 hrs and gpm
Watering strategies Select emitter based on water required Calculate set time
Adjust flow rate or set time If Ta is greater than 22 hr/day (even for a single- station system), increase the emitter discharge If the increased discharge exceeds the recommended range or requires too much pressure, either larger emitters or more emitters per plant are required.
Select the number of stations If Ta ≈ 22 h/d, use a one-station system (N = l), select Ta < 22 hr/day, and adjust qa accordingly. If Ta <11 h/d, use N = 2, select a Ta <11, and adjust qa accordingly. If 12 < Ta < 18, it may be desirable to use another emitter or a different number of emitters per plant to enable operating closer to 90 percent of the time and thereby reduce investment costs.
Pressure flow relationship (P a ) Where: q a = average emitter flow rate (gph) P a = average pressure (psi) x = emitter exponent K = flow constant
Start with average lateral
Standard requires Pipe sizes for mains, submains, and laterals shall maintain subunit (zone) emission uniformity (EU) within recommended limits Systems shall be designed to provide discharge to any applicator in an irrigation subunit or zone operated simultaneously such that they will not exceed a total variation of 20 percent of the design discharge rate.
Design objective Limit the pressure differential to maintain the desired EU and flow variation What effects the pressure differential ◦ Lateral length and diameter ◦ Manifold location ◦ slope
Four Cases
Allowable pressure loss (subunit) This applies to both the lateral and subunit. Most of the friction loss occurs in the first 40% of the lateral or manifold D P s =allowable pressure loss for subunit P a = average emitter pressure P n = minimum emitter pressure
Emission Uniformity
Q is related to Pressure
Hydraulics Limited lateral losses to 0.5 D P s Equation for estimating ◦ Darcy-Weisbach(best) ◦ Hazen-Williams ◦ Watters-Keller ( easiest, used in NRCS manuals )
C factorPipe diameter (in) 130≤ 1 140< 3 150≥ 3 130Lay flat Hazen-Williams equation hf =friction loss (ft) F = multiple outlet factor Q = flow rate (gpm) C = friction coefficient D = inside diameter of the pipe (in) L = pipe length (ft)
Watters-Keller equation hf = friction loss (ft) K = constant ( for pipe 5”) F = multiple outlet factor L = pipe length (ft) Q = flow rate (gpm) D = inside pipe diameter (in)
Multiple outlet factors Number of outlets F F >
Adjust length for barb and other minor losses
Adjusted length L’ = adjusted lateral length (ft) L = lateral length (ft) Se = emitter spacing (ft) fe = barb loss (ft)
Start with average lateral
Pressure Tanks
Practice problem