Residential Ventilation in the Pacific Northwest Field Study of Mechanical Ventilation Effectiveness in Tightly Constructed Houses David Hales Washington.

Slides:



Advertisements
Similar presentations
HVAC Equipment Efficiency Overview Building Performance Matters.
Advertisements

TOUR OF NIST MANUFACTURED RESEARCH HOUSE Andy Persily, Steve Nabinger, Steve Emmerich, Cindy Howard Reed Building and Fire Research Laboratory National.
Energy Savings Impacts of the Advanced Energy Design Guide: Small Office Buildings Bing Liu, P.E. Research Engineer Pacific Northwest National Laboratory.
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – July 2012eere.energy.gov Building Science Basics WEATHERIZATION INSTALLER/TECHNICAN FUNDAMENTALS.
IEE ECOLISH Improvement of Energy Efficiency of Low Income Housing Zoltán MAGYAR.
Chapter 8: Duct Design and Sealing To be used with the Guide to Building Energy Efficient Homes in Kentucky.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
2009 Washington State Energy Code Residential Sections
New Construction Calibration Research Results and Request for Decision Regional Technical Forum March 18, 2014.
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
Welcome to Field Controls Welcome to Field Controls Residential Ventilation Residential Ventilation Part 2 Part 2 1.
Key HVAC Design Concepts. Agenda Discuss relevance of thermal enclosure system to HVAC system. Present the three major steps to design an HVAC system.
INTD 51 human environments building systems. heating/ventilation/air-conditioning (HVAC) maintain a comfortable indoor climate control temperature and.
The Portland Street Building Back to “Select a building” Back to “Select a building” NatVent Presentation of the building Presentation of the building.
Assumptions about Indoor Environments Mark Lawton P.Eng Patrick Roppel M.A.Sc.
Ductless Heat Pumps in Residential Applications Proposed Research Plan.
Energy Rating Index Performance Path Speaker Name Speaker Affiliation.
The House as a System 1. Air Temperature and Water Vapor.
Energy Rating Index Performance Path Speaker Name Speaker Affiliation.
C A L I F O R N I A E N E R G Y C O M M I S S I O N 2013 Building Energy Efficiency Standards Residential Zoned AC Discussion August 18, 2011.
A Research Institute of the University of Central Florida FBC Mechanical Technical Advisory Committee Meeting June 25, 2014 A Review of Home Airtightness.
Station 3 ?? Air Meters Combustion Analyzer Carbon Monoxide Carbon Dioxide Particles Air Flow Vane Anemometer Exhaust Flow Box Pressures CAZ Test.
Lesson 3 How does radon enter a home?. Slide 4-1 Predicted average indoor radon levels (U.S.) This map cannot be used to determine the radon level of.
Standardized Curriculum WAP Training Plans and Resources.
NEEM Manufactured Homes Field Test Results David Baylon, Ecotope.
Welcome to S&P USA & the 2012 International Residential and Mechanical Code for Ventilation.
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Blower Door Basics WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY.
HVACR416 - Design Pressure Measurement Part 2. Pressure Measurement Several pressure measurements exist. They all measure the same things, the force of.
F LORIDA S OLAR E NERGY C ENTER A Research Institute of the University of Central Florida Assessment of Energy Efficient Methods of Indoor Humidity Control.
Massachusetts “Stretch” Energy Code Marc Breslow Executive Office of Energy & Environmental Affairs.
National Tribal Forum on Air Quality Co-Sponsored by: Institute for Tribal Environmental Professionals & National Tribal Air Association.
SEEM Tool Overview Regional Technical Forum Member Orientation January 22, 2013.
Comfortable homes that save the world Sustainable Environmental Economic Development October 27, 2007 Don Otto dpoconstruction.com Don Otto dpoconstruction.com.
Home Ventilation 1 Background: As Habitat homes are being built more tightly to reduce heat loss, there has been an increasing concern about the amount.
1 HVACR416 – Design Principles Air Exchange. 2 HRV’s (Heat Recovery Ventilators)
Part 2: Buildings as a System Lee F. Ball Jr., PhD
Residential Weatherization and Ventilation Subcommittee Seeking RTF Direction on Ventilation and IAQ Requirements May 3, 2011 Subcommittee: Residential.
Source Strength Source Strength Removal Rate Removal Rate Ventilation and IAQ.
Objectives Finish talking about ways to minimize ventilation losses Discuss role of ducts in building energy use Describe coheating test methodology Interpret.
Michael Logsdon, Ben Larson, David Baylon 13 December th Avenue NE, Seattle, WA (206)
The European Office Building S.H. Liem, A.H.C. van Paassen M.Verwaal, H.F. Broekhuizen Delft, April 1998 S.H. Liem, A.H.C. van Paassen M.Verwaal, H.F.
CALRES Update Phase 1 Progress Report April 22, 2009 Bruce Wilcox Phil Niles Ken Nittler.
ASHRAE A Ventilation Standard for Residential Structures Ventilation and Acceptable Indoor Air Quality in Low- Rise Residential Buildings.
Ben Larson 1 November th Avenue NE, Seattle, WA (206)
Residential Ventilation & IAQ Requirements for Existing Homes History, ASHRAE 62.2, and the RTF’s Role Regional Technical Forum October 13 th, 2009.
HVACR416 - Design IAQ / Ventilation / Pathways. Ventilation Most air handling units distribute a mix of outdoor air and re-circulated indoor air. Some.
The EWZ building Presentation of the building Presentation of the building The design issue The design issue The building concept The building concept.
Michael Logsdon, Ben Larson, David Baylon 13 December th Avenue NE, Seattle, WA (206)
1 NORTHWEST ENERGY EFFICIENCY ALLIANCE Combo products: Space + Water Market Drivers and Field Testing Status.
Home Ventilation 1 Background: As Habitat homes are being built more tightly to reduce heat loss, there has been an increasing concern about the amount.
Washington Residential Energy Code 2012: Overview 17 December 2013 Ben Larson, Ecotope 1.
-Too little or too much ventilation -Insufficient ventilation results in excessive indoor humidity -Uncontrolled ventilation can cause exhaust leaks within.
Objectives Finish air cleaner problem Measure ventilation rates Focus on smaller buildings.
Air quality made simple A Balanced Approach Whole House Ventilation and IAQ Airflow Control Make-up Air Solutions Application by Geographic Region.
Session 3 Domestic Energy Uses. Recording from utility bills, use schedules and unusual observations Inventory domestic all energy use systems such as:
Where did it go? Lost savings found in real-world data SEEM Calibration for the Northwest Power and Conservation Council’s Regional Technical Forum (RTF)
1 1 Weatherization & Indoor Air Quality Impacts of Weatherization on Air Quality and Comfort Inside Your Home Prepared with the assistance of Jed Harrison,
VENTILATION AND FENESTRATION
Design What is the first step in designing a high-performance building? Would it be: Identify synergies Select the correct HVAC system Design around human.
Sustainable Energy Systems Engineering Peter Gevorkian Ch 12: Geothermal Energy Brevard Community College ETP1420 Bruce Hesher.
Day 1 Part 4 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
1 How good are building simulation models? Comparing simulated and actual building energy consumption at the circuit level Brock Glasgo, PhD Student Engineering.
The Indoor Air Quality in a Multi-garage
Chapter 6: INFILTRATION
Prof. Chris Hendrickson
Better Student Performance So, What Are We Waiting For?
Energy Innovations in Residential Buildings
Things you need to know before you play the game
A Ventilation Standard for Residential Structures
Chapter 6B: INFILTRATION CALCULATION
Presentation transcript:

Residential Ventilation in the Pacific Northwest Field Study of Mechanical Ventilation Effectiveness in Tightly Constructed Houses David Hales Washington State University Extension Energy Program ext. 2 Research Supported by the Northwest Energy Efficiency Alliance Charlie Stephens, Project Manager WSU Contributors: Ken Eklund, David hales, Rich Prill, Luke Howard, Rick Kunkle, Adria Banks, Luke Mattheis, Marla Hacklander, Tanya Beavers, Mike Lubliner, Andy Gordon Additional Consultants: Terry Brennan and Dr. Jeff Siegel

History Mechanical whole house ventilation required in residential construction in Washington State since July 1, VIAQ Code First statewide requirement in US. Based on ASHRAE – 15 CFM/occupant or.35 ACH In 22 years about 800K homes WA State Energy Code assumed tight houses <.1 ACH “Seal all penetrations”

Ventilation System Types Integrated with Central Forced Air Exhaust Only

What Really Happened Houses didn’t get as tight as assumed. Tested average of WA Code homes since ACH. Systems often didn’t work properly, were turned off or disabled by occupants. If operated often over ventilated especially during colder seasons. Not a lot of complaints or problems.

What’s Happening Now WA Code required blower door testing to about.285 ACH since 2009 (tested av..31) WA Code.25 ACH started 7/1/ IECC requires tested 3 ACH50 (.15 ACH). It may really matter if ventilation systems actually work and are operated!

What’s Happening Now Most really tight houses (2 ACH50 or less) have HRVs. Conventional wisdom is they work but they are expensive. Super tight, high performance homes are moving away from CFA so integrated ventilation is less common option. Conventional wisdom is they work, low up front cost but high operating costs (big fan). Single point exhaust only systems are relatively low cost, economical to operate but conventional wisdom questions how well they actually work.

The Plan Let’s ask some questions and try to answer them by measuring some stuff!

Ventilation Effectiveness Field Study What questions did we want to try and answer? 1.How well do different types of ventilation systems work in really tight houses (<3ACH50) in terms of compliance with ASHRAE ? 2.What is the efficacy of different systems in terms of watts / CFM as operated? 3.How does door closure (especially in bedrooms) affect the performance of different types of systems? 4.Do trickle vents improve the performance of exhaust only systems?

Matrix of ACH 50 and Vent Systems System Type House < 1 ACH50 House < 2 ACH50 House < 3 ACH50 Exhaust Only142 Exhaust Only with Trickle Vents 134 Integrated with CFA * 2 HRV631 HRV Integrated with CFA * 2 1.Sample selected from ~ 900 homes built 2006 or newer (final sample 29 sites). 2.Screened out occupants with respiratory problems. 3.Single family detached or multi-family with no more than 1 common wall. 4.Roughly ½ sites marine climate zone 4 and ½ cold climate zone 5. 5.Occupants agreed not to open windows during test cycles. *Central Forced Air

House Characterization General: size; volume; bedrooms, occupancy; stories; type heating/cooling; type ventilation; ventilation operation; foundation type; garage. Inventory of all exhaust appliances: type; location; flow (cfm); power draw of ventilation equipment. House tightness; duct leakage to exterior. Pressure mapping: incremental depressurization induced by exhaust air flows and CFA operation. Pressure induced across closed bedroom doors when whole house ventilation operated. Tracer gas decay on 90% of sites; ventilation off/on; bdrm doors open/closed.

Monitoring Monitored CO2, temp. & %RH in master bdrm, secondary bdrm and core living area (15 min data). Monitored door closure of master and secondary bdrms. Monitored run times of whole house ventilation systems.

Door logger CO2, Temp, RH%

Test Cycles 7 day test cycle periods (included weekends) Occupants provided with detailed test calendar and Journal* WSU weekly reminders via phone/ Test configurations: Whole house ventilation on/off Bedroom doors open/closed Trickle vents open/closed (as applicable) Heating and Spring season The test cycles at each house performed in cold winter conditions and repeated during mild spring *Occupants logged system and house & exhaust appliance operation, activities, changes in occupancy

Data and Analysis

What is Effective Ventilation? Really complex Dynamic interaction of: – Structural characteristics of the house – Different mechanical systems & operation – Outside environment – Occupants & occupancy patterns – Pollutant sources & strengths

Our Analysis Assumed that ventilating to ASHRAE was the goal. Used C02 levels generated by occupants as a tracer gas to estimate CFM/occupant at steady state. Focused on occupied bedrooms at night

Outside Air cfm/p cfm/p cfm/p cfm/p cfm/p Unacceptable Poor ASHRAE Standard 62 Outdoor Carbon Dioxide (ppm) 2,400 1,400 1, (and above) Carbon Dioxide vs. Ventilation Rate

CO 2 Estimate of Ventilation Over- Ventilated Ideal Under-Ventilated 800 1, ,000 1,500 2,000+ Carbon Dioxide Carbon Dioxide parts-per million (ppm) (energy issue) (multiple issues !! ) IdealIAQ CO 2

LONG TERM CO2 TESTING

CO2 Level Distribution with Ventilation On or Off Ventilation Works

CO 2 Level Distribution by Ventilation Type with Ventilation On or Off

4-5,000 ppm 3-4,000 ppm 2-3,000 ppm 1-2,000 ppm < 1,000 ppm Vent Off Door Closed Vent Off Door Open Vent On Door Open Vent On Door Closed

Hourly CO2 Level Distribution with Ventilation On or Off

Master Bedroom Mean Night Time CO2 > 1000 PPM

TRACER DECAY TESTING

CO2 Tracer Decay Integrated CFA System Vent Off Doors Open

Tracer Decay Test ACH by Test Condition Sorted by Ventilation Type Vent On Doors Open Vent On Doors Closed Vent Off Doors Open Master Bedroom

Induced ACH by Ventilation System Weighting ACH 2B (A-C) ACH MB (A-C) ACH ML (A-C) Weighted Average (A- C) Measured CFMAreaVolume Measured ACHDifference Ventilation Type E Exhaust E HRV E Exhaust E CFA E HRV E Exhaust E Exhaust E CFA E Exhaust E HRV E HRV E Exhaust W HRV W HRV W HRV W HRV W Exhaust W Exhaust W Exhaust W Exhaust W Exhaust W Exhaust W Exhaust

ACH NAT

RELATIVE HUMIDITY

Relative Humidity by Room, Eastside (E) or Westside (W), Heating (Winter) or Milder (Spring) Season, and Ventilation System Operation (On or Off)

Relative Humidity Levels by Room, Ventilation System, and Ventilation Operation

Hourly Distribution of Relative Humidity by Room

Relative Humidity in Individual Houses by Room and Ventilation System Operation

Some Conclusions Without ventilation these houses have very low ACH rates (<0.1) potentially allowing significant build up of pollutant concentrations. Operation of the ventilation system increased the ACH rate by a factor of 4 on average. Door closure has a larger impact on ACH rates in zones without direct distribution or active mixing.

Other Areas of Study Not Discussed Here Monitored door closure data Fan energy used by ventilation systems As found system condition Ventilation performance as found Occupant knowledge of the ventilation system and its operation and maintenance Performance of trickle vents