EE 212 Passive AC Circuits Lecture Notes 2b EE 212.
Advertisements

EE369 POWER SYSTEM ANALYSIS
Chapter 11 AC Power Analysis
AC POWER CALCULATION Instantaneous, average and reactive power
Each of the circuit elements will have a different ac current response to an applied ac voltage. We need to look at each of these elements. Resistor:
Lecture 2 Complex Power, Reactive Compensation, Three Phase Dr. Youssef A. Mobarak Department of Electrical Engineering EE 351 POWER SYSTEM ANALYSIS.
Chapter 24 Three-Phase Systems.
We have been using voltage sources that send out a current in a single direction called direct current (dc). Current does not have to flow continuously.
Sinusoidal Steady-State Power Calculations
CH5 AC circuit power analysis 5.1 Instantaneous Power 5.2 Average Power 5.3 Effectives values of Current & Voltage 5.4 Apparent Power and Power Factor.
Lect19EEE 2021 AC Power Dr. Holbert April 9, 2008.
AC Review Discussion D12.2. Passive Circuit Elements i i i + -
Announcements Be reading Chapters 1 and 2 from the book
Lesson 24 AC Power and Power Triangle
Storey: Electrical & Electronic Systems © Pearson Education Limited 2004 OHT 16.1 Power in AC Circuits  Introduction  Power in Resistive Components 
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Lecture 31 Sinsuoidal steady state power Instantaneous and average (real) power Reactive power Complex power Power factor Related educational modules:
Chapter 7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
ECE 3183 – Chapter 5 – Part D CHAPTER 5 - D1 ECE 3183 – EE Systems Chapter 5 – Part D AC Power, Power Factor.
ENGR-43_Lec-09-2_Complex_Power.ppt 1 Bruce Mayer, PE Engineering-43: Engineering Circuit Analysis Bruce Mayer, PE Registered Electrical.
ECE 2300 Circuit Analysis Dr. Dave Shattuck Associate Professor, ECE Dept. Lecture Set #24 Real and Reactive Power W326-D3.
Circuits II EE221 Unit 4 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Alexander-Sadiku Fundamentals of Electric Circuits
Fundamentals of Electric Circuits Chapter 11
ECE 2300 Circuit Analysis Dr. Dave Shattuck Associate Professor, ECE Dept. Lecture Set #25 Complex Power W326-D3.
INC 112 Basic Circuit Analysis Week 12 Complex Power Complex Frequency.
Circuits II EE221 Unit 3 Instructor: Kevin D. Donohue Instantaneous, Average, RMS, and Apparent Power, and, Maximum Power Transfer, and Power Factors.
Chapter 11 AC Steady-State Power
Fundamentals of Electric Circuits Chapter 11
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
1 Chapter 11 AC Power Analysis 電路學 ( 二 ). 2 AC Power Analysis Chapter Instantaneous and Average Power 11.2Maximum Average Power Transfer 11.3Effective.
EGR 2201 Unit 13 AC Power Analysis
AC POWER ANALYSIS Instantaneous & Average Power
INC 111 Basic Circuit Analysis
Chapter 7 AC Power Analysis
Circuits II EE221 Unit 11 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
1 Alternating Current Circuits Chapter Inductance CapacitorResistor.
The V  I Relationship for a Resistor Let the current through the resistor be a sinusoidal given as Is also sinusoidal with amplitude amplitudeAnd.
Chapter 11 AC Power Analysis
Power System Fundamentals EE-317 Lecture 3 06 October 2010.
ELECTRICAL CIRCUIT CONCEPTS
Chapter 17 Power in AC Circuits.
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
1 ECE 3336 Introduction to Circuits & Electronics Set #15 Complex Power Fall 2011, TUE&TH 4-5:30 pm Dr. Wanda Wosik.
Chapter 10 Sinusoidal Steady- State Power Calculations
1  Explain and calculate average power, apparent power, reactive power  Calculate the total P, Q and S and sketch the power triangle. ELECTRICAL TECHNOLOGY.
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
AC POWER & POWER FACTOR. Lesson Objectives  Compute and define apparent, reactive, and average power for capacitors, inductors, and resistors.  Compute.
CHAPTER 2: DC Circuit Analysis and AC Circuit Analysis Motivation Sinusoids’ features Phasors Phasor relationships for circuit elements Impedance and admittance.
FUNDAMENTAL OF ELECTRICAL POWER SYSTEMS (EE 270)
Chapter 13 The Basic Elements and Phasors. Objectives Be able to add and subtract sinusoidal voltages or currents Use phasor format to add and subtract.
1 Chapter 3 AC Power Analysis. 2 AC Power Analysis Chapter 3 3.1Instantaneous and Average Power 3.2Maximum Average Power Transfer 3.3Effective or RMS.
Chapter 13 The Basic Elements and Phasors. Objectives Be able to add and subtract sinusoidal voltages or currents Use phasor format to add and subtract.
Power in AC Circuits Introduction Power in Resistive Components
Chapter 11 AC Power Analysis
Lecture 07 AC POWER & POWER FACTOR.
AC POWER & POWER FACTOR.
Sinusoidal Excitation of Circuits
EFFECTIVE OR RMS VALUES
Network Circuit Analysis
Islamic University of Gaza
STEADY-STATE POWER ANALYSIS
site.iugaza.edu.ps/ajasser
Power in AC Circuits Introduction Power in Resistive Components
2. 2 The V-I Relationship for a Resistor Let the current through the resistor be a sinusoidal given as Is also sinusoidal with amplitude amplitude.
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
The instantaneous power
E E 2415 Lecture 9 Phasor Circuit Analysis, Effective Value and Complex Power: Watts, VAR’s and Volt-Amperes.
Engineering Circuit Analysis
Presentation transcript:

Since Therefore Since

You can see that that the frequency of the Instantaneous power is twice the frequency of the voltage or current

The instantaneous power real (or average) power (Watts) Which is the actual power absorb by the element Examples Electric Heater , Electric Stove , oven Toasters, Iron …etc reactive power Which is the reactive power absorb or deliver by the element Reactive power represents energy stored in reactive elements (inductors and capacitors). Its unit is Volt Ampere Reactive (VAR)

The instantaneous power real (or average) power (Watts) reactive power (Volt Ampere Reactive (VAR) )

Complex Power Previously, we found it convenient to introduce sinusoidal voltage and current in terms of the complex number the phasor Definition Let the complex power be the complex sum of real power and reactive power

Advantages of using complex power - We can compute the average and reactive power from the complex power S - complex power provide a geometric interpretation were The geometric relations for a right triangle mean the four power triangle dimensions ( , P, Q,  ) can be determined if any two of the four are known

Power Calculations were Is the conjugate of the current phasor Circuit Since Similarly

Power Calculations Summery Circuit

This implies that in any circuit, conservation of average power and In any circuit, conservation of complex power is achieved This implies that in any circuit, conservation of average power and Conservation of reactive power are achieved However, the apparent power (the magnitude of the complex power) is not conserved

Ex:6.13 Determine the average and reactive power delivered by the source. The phasor current leaving the source is The average power delivered by the source is:

The reactive power delivered by the source is: And the complex power delivered by the source is

The voltage across the elements are: Determine the average power and reactive power delivered to each element The voltage across the elements are: Thus the complex power delivered to each element is

show that conservation of complex power, average power, and reactive power is achieved.

6.6.1 Power Relations for the Resistor The voltage and current are in phase so Average power is: Reactive power is zero for resistor

6.6.1 Power Relations for the Inductor The voltage leads the current by 90 so that

6.6.1 Power Relations for the Capacitor The current leads the voltage by 90 so that

Recall the Instantaneous power p(t) The power factor Recall the Instantaneous power p(t) The angle qv - qi plays a role in the computation of both average and reactive power The angle qv - qi is referred to as the power factor angle We now define the following : The power factor

The power factor Knowing the power factor pf does not tell you the power factor angle , because To completely describe this angle, we use the descriptive phrases lagging power factor and leading power factor Lagging power factor implies that current lags voltage hence an inductive load Leading power factor implies that current leads voltage hence a capacitive load

6.6.2 Power Factor Since

Circuit

Circuit

EX:6.15 Determine the average and reactive powers delivered to the load impedance and the power factor of the load Average power

Average power

reactive powers

reactive powers OR

EX:6.15 Determine the average and reactive powers delivered to the load impedance and the power factor of the load OR

This could also be calculated from the complex power delivered to the load The power factor of the load is: The load is lagging because the current lags the voltage

A typical power distribution circuit The consumer is charged for the average power consumed by the load The load requires a certain total apparent power

The powers consumed in the line losses Ex 6.16 Suppose that the load voltage figure is 170V The line resistance is 0.1 ohm The load requires 10KW of average power. Examine the line losses for a load power factor of unity and for a power factor of 0.7 lagging. The load current is obtained from For unity power factor this is For power factor of 0.7 The powers consumed in the line losses 720 W extra power to be generated if pf is 0.7 to supply the load

Power Factor Correction Ex: 6.17: in Ex 6.16 determine the value of capacitor across the load to correct the power factor from 0.7 to unity if power frequency is 60Hz. From Ex 6.16 For power factor of 0.7 power factor 0.7 lagging The current through the added capacitor is: Hence the total current Unity power factor Imaginary component of the line current is zero

The average power delivered to the load is:

6.6.3 Maximum Power Transfer Source-load Configuration Determine the load impedance so that maximum average power is delivered to that load. Represent the source and the load impedances with real and imaginary parts: The load current is:

The average power delivered to the load is: Since the reactance can be negative and to max value, we choose leaving Differentiate with respect to RL and set to zero to determine required RL which is RL= RS Hence: In this case the load is matched to the source. The max power delivered to the load becomes:

6.6.4 Superposition of Average Power Average power computation when circuit contains more than one source

The instantaneous power delivered to the element is Substituting Using the identity

Using the identity

The instantaneous power becomes Average powers delivered individually by the sources Suppose that the two frequencies are integer multiples of some frequency as The instantaneous power becomes

Averaging the instantaneous over the common period THUS: we may superimpose the average powers delivered by sources of different frequencies, but we may not, in general, apply superposition to average power if the sources are of the same frequency. where

Ex 6.18: Determine the average power delivered by the two sources of the circuit Hence the average power delivered by the voltage source is This can be confirmed from average powers delivered to the two resistors

of average powers delivered individually by each source By current division: The voltage across the current source is Hence the average power delivered by the current source is This may be again confirmed by computing the average power delivered to the Two resistors: Since frequencies are not the same, total average power delivered is the sum of average powers delivered individually by each source

EX 6.19: Determine the average power delivered by the two sources Since both sources have the same frequency, we can’t use superposition. So we include both sources in one phasor circuit. The total average power delivered by the sources is equal to the average power delivered to the resistor We use superposition on the phasor circuit to find the current across the resistor

The phasor current is: Hence the average power delivered to the resistor is Note that we may not superimpose average powers delivered to the resistors by the individual sources We can compute this total average power by directly computing the average power delivered by the sources from the phasor circuit The voltage across the current source is The average power delivered by voltage source is The average power delivered by the current source is The total average power delivered by the sources is

6.6.5 Effective (RMS) Values of Periodic Waveforms Sinusoidal waveform is one of more general periodic waveforms Apply a periodic current source with period T on resistor R The instantaneous power delivered to the resistor is The average power delivered to the resistor is Hence the average power delivered to the resistor by this periodic waveform can be viewed as equivalent to that produced by a DC waveform whose value is This is called the effective value of the waveform or the root-mean-square RMS value of the waveform

Ex 6.20 Determine the RMS value of the current waveform and the average power this would deliver to resistor The RMS value of the waveform is Hence the average power delivered to the resistor is

RMS voltages and currents in phasor circuits The sinusoid has a RMS value of Hence the average power delivered to a resistor by a sinusoidal voltage or current waveform is In general, the average power delivered to an element is Therefore, if sinusoidal voltages and currents are specified in their RMS values rather than their peak values, the factor ½ is removed from all average-power expressions. However, the time-domain expressions require a magnitude multiplied by square root of 2 Since X is the peak value of the waveform. Common household voltage are specified as 120V. This is the RMS value of the peak of 170V.

Ex 6.21 Determine the average power delivered by the source and the time-domain current i(t) Phasor circuit with rms rather than peak The phasor current is Hence the average power delivered by the source is The time-domain current is

Commercial Power Distribution

Time domain representation

Using Vectors

We are going to investigate the transmission of power from 6.9.1 Wye-Connected Loads We are going to investigate the transmission of power from three phase generator to two types of load: I – WYE connected load Hence the current returning through the neutral wire is zero, and the neutral may be removed

Power calculation For a balanced wye-connected load, the voltages across the individual loads are the respective phase voltages whether the neutral is connected or not. The power delivered to the individual loads is three times the power delivered to an individual load, because the individual loads are identical. No ½ factor in power expression because values are rms

Since the line voltage is more accessible than the phase voltage Power in terms of line-to-line voltages and load current gives

Hence, the average power delivered to each load is Example 6.24 Consider a balanced, wye-connected load where each load impedance is the phase voltages are 120 V. Determine the total average power delivered to the load. The line currents are Hence, the average power delivered to each load is The total average power delivered to the load is

Example 6.25 If the line voltage of a balanced, wye-connected load is 208 V and the total average power delivered to the load is 900 W, determine each load if their power factors are 0.8 leading. Thus The phase voltage is Thus the magnitude of the individual load impedance is Since the power factor is 0.8 leading (current leads voltage; voltage lags current) Thus the individual loads are

Example 6.25 If the line voltage of a balanced, wye-connected load is 208 V and the total average power delivered to the load is 900 W, determine each load if their power factors are 0.8 leading. Thus The phase voltage is Thus the magnitude of the individual load impedance is Since the power factor is 0.8 leading (current leads voltage; voltage lags current) Thus the individual loads are