ELL100: INTRODUCTION TO ELECTRICAL ENGG.

Slides:



Advertisements
Similar presentations
“Power Factor” In Transmission System
Advertisements

Chapter 11 AC Power Analysis
Since Therefore Since.
Chapter 12 RL Circuits.
Sinusoidal Steady-State Power Calculations
The average ac power (P av ) is the power dissipated on the load resistor. 0  cos  1, dependent on the complex load. ideal power factor: cos  =1,
Filter & Transfer Function Z1Z1 Z2Z2 V in V out To determine filter type, look how H V as a function of frequency Z 1 and Z 2 could include multiple components.
Announcements Be reading Chapters 1 and 2 from the book
Power Factor Correction Most domestic loads (such as washing machines, air conditioners, and refrigerator) and industrial loads (such as induction motors)
Copyright © 2013 The McGraw-Hill Companies, Inc. Permission required for reproduction or display. 1 Chapter 11 AC Circuit Power Analysis.
Lesson 24 AC Power and Power Triangle
Storey: Electrical & Electronic Systems © Pearson Education Limited 2004 OHT 16.1 Power in AC Circuits  Introduction  Power in Resistive Components 
Power Factor and Power Factor Correction
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Chapter 7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
AC Electricity Why AC? Distribution. Winter 2012 UCSD: Physics 121; Getting Power to Our Homes Let’s power our homes with DC powerLet’s power our.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Alexander-Sadiku Fundamentals of Electric Circuits
Fundamentals of Electric Circuits Chapter 11
Chapter 11 AC Power Analysis
Chapter 11 AC Steady-State Power
Fundamentals of Electric Circuits Chapter 11
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
10A R 20Ω 100V 100Ω Q.1 For the given circuit the value of R such that the same amount of power is supplied to the 100Ω by the current and voltage source.
FOWLER CHAPTER 9 LECTURE 9 POWER IN AC CIRCUITS. POWER IN RESISTIVE CIRCUITS, CHAP 9 WITH A RESISTIVE LOAD, CURRENT AND VOLTAGE ARE IN PHASE. F.9.1 THIS.
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Fourth Edition, by Allan R. Hambley, ©2008 Pearson Education, Inc. Lecture 16 Phasor Circuits, AC.
1 Chapter 11 AC Power Analysis 電路學 ( 二 ). 2 AC Power Analysis Chapter Instantaneous and Average Power 11.2Maximum Average Power Transfer 11.3Effective.
AC POWER ANALYSIS Instantaneous & Average Power
Chapter 7 AC Power Analysis
Chapter 11 AC Power Analysis
Lecture19 Examples Presented by Robert Trajkovski.
ELECTRICAL CIRCUIT CONCEPTS
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
1  Explain and calculate average power, apparent power, reactive power  Calculate the total P, Q and S and sketch the power triangle. ELECTRICAL TECHNOLOGY.
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
FUNDAMENTAL OF ELECTRICAL POWER SYSTEMS (EE 270)
1 Chapter 3 AC Power Analysis. 2 AC Power Analysis Chapter 3 3.1Instantaneous and Average Power 3.2Maximum Average Power Transfer 3.3Effective or RMS.
8. 3 Power Factor Correction 8.1 Power in a Sinusoidal Steady-state Circuit 8.2 Maximum Average Power Transfer Chapter 8 AC Power Analysis 交流功率分析.
EGR 2201 Unit 13 AC Power Analysis  Read Alexander & Sadiku, Chapter 11.  Homework #13 and Lab #13 due next week.  Final Exam and Lab Exam next week.
Chapter 12 RL Circuits.
Lesson 3: Ac Power in Single Phase Circuits
Power in AC Circuits Introduction Power in Resistive Components
AC Electricity Our Everyday Power Source
Chapter 11 AC Power Analysis
Electric Circuits (EELE 2312)
Lesson 22: AC Power Factor and Power Factor Correction
Lesson 21: AC Power and Power Triangle
Chapter 11 AC Power Analysis
Sinsuoidal steady state power
Chapter 11 AC Power Analysis
Sinusoidal Excitation of Circuits
EFFECTIVE OR RMS VALUES
Islamic University of Gaza
Lecture 31 Sinsuoidal steady state power Related educational modules:
site.iugaza.edu.ps/ajasser
ELECTRIC CIRCUITS EIGHTH EDITION
An {image} series circuit has {image} , {image} , and {image}
Power in AC Circuits Introduction Power in Resistive Components
11/13/2018.
Electromechanical Systems
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
Electric Circuits Fundamentals
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
ELL100: INTRODUCTION TO ELECTRICAL ENG.
Chapter 11 – Power AC Circuits
EE202 – Circuit Theory II , Spring
The instantaneous power
E E 2415 Lecture 9 Phasor Circuit Analysis, Effective Value and Complex Power: Watts, VAR’s and Volt-Amperes.
Chapter 11 – Power AC Circuits
Engineering Circuit Analysis
Presentation transcript:

ELL100: INTRODUCTION TO ELECTRICAL ENGG. Course Instructors: J.-B. Seo, S. Srirangarajan, S.-D. Roy, and S. Janardhanan Department of Electrical Engineering, IITD

Generation, Transmission, & Distribution 1. Power Plant generates 3-phase AC power 2. Transmission Substation steps the voltage up to 69,000 - 765,000 V 3. High Voltage Transmission Lines moves power over long distances on the transmission grid 6. Distribution Power Lines Moves power over distribution grid to points-of-use steps the voltage down to 4160 -36,000V 5. Distribution Substation 4. Subtransmission Steps the voltage down to 22,000 – 69,000 V

Generation, Transmission, & Distribution 1. Power Plant generates 3-phase AC power 2. Transmission Substation steps the voltage up to 69,000 - 765,000 V 3. High Voltage Transmission Lines moves power over long distances on the transmission grid 6. Distribution Power Lines Moves power over distribution grid to points-of-use steps the voltage down to 4160 -36,000V 5. Distribution Substation 4. Subtransmission Steps the voltage down to 22,000 – 69,000 V

Generation, Transmission, & Distribution 1. Power Plant generates 3-phase AC power 2. Transmission Substation steps the voltage up to 69,000 - 765,000 V 3. High Voltage Transmission Lines moves power over long distances on the transmission grid 6. Distribution Power Lines Moves power over distribution grid to points-of-use steps the voltage down to 4160 -36,000V 5. Distribution Substation 4. Subtransmission Steps the voltage down to 22,000 – 69,000 V

Generation, Transmission, & Distribution 1. Power Plant generates 3-phase AC power 2. Transmission Substation steps the voltage up to 69,000 - 765,000 V 3. High Voltage Transmission Lines moves power over long distances on the transmission grid 6. Distribution Power Lines Moves power over distribution grid to points-of-use steps the voltage down to 4160 -36,000V 5. Distribution Substation 4. Subtransmission Steps the voltage down to 22,000 – 69,000 V

Generation, Transmission, & Distribution 1. Power Plant generates 3-phase AC power 2. Transmission Substation steps the voltage up to 69,000 - 765,000 V 3. High Voltage Transmission Lines moves power over long distances on the transmission grid 6. Distribution Power Lines Moves power over distribution grid to points-of-use steps the voltage down to 4160 -36,000V 5. Distribution Substation 4. Subtransmission Steps the voltage down to 22,000 – 69,000 V

Generation, Transmission, & Distribution 1. Power Plant generates 3-phase AC power 2. Transmission Substation steps the voltage up to 69,000 - 765,000 V 3. High Voltage Transmission Lines moves power over long distances on the transmission grid 6. Distribution Power Lines Moves power over distribution grid to points-of-use steps the voltage down to 4160 -36,000V 5. Distribution Substation 4. Subtransmission Steps the voltage down to 22,000 – 69,000 V

Distribution Power Lines Small Substation Distribution Power Lines Industrial Uses 1200 A 2400 – 15,000 Volts 6. Distribution Power Lines Commercial Uses 480Y/277 Volts Moves power over distribution grid to points-of-use Residential Uses 120/240 Volts

Distribution Power Lines Small Substation Distribution Power Lines Industrial Uses 1200 A 2400 – 15,000 Volts 6. Distribution Power Lines Commercial Uses 480Y/277 Volts Moves power over distribution grid to points-of-use Residential Uses 120/240 Volts

Distribution Power Lines Small Substation Distribution Power Lines Industrial Uses 1200 A 2400 – 15,000 Volts 6. Distribution Power Lines Commercial Uses 480Y/277 Volts Moves power over distribution grid to points-of-use Residential Uses 120/240 Volts

Power Dissipated in an Electricity Distribution System AC Electricity Why high voltage? Power Dissipated in an Electricity Distribution System 150 miles 120 Watt Light bulb Power Plant on Colorado River 12 Volt Connection Box Estimate resistance of power lines: - say 0.001 Ohms per meter, times 200 km = 0.001 W/m  2105 m = 20 Ohms The current required by a single bulb using P = VI so I = P/V = 120 Watts/12 Volts = 10 Amps (!) Power in transmission line: P = I2R = 102  20 = 2,000 Watts!! “Efficiency” is e = 120 Watts/4120 Watts = 0.3%!!! Lecture 7

Power Dissipated in an Electricity Distribution System AC Electricity Why high voltage? Power Dissipated in an Electricity Distribution System 150 miles 120 Watt Light bulb Power Plant on Colorado River 12 Volt Connection Box Estimate resistance of power lines: - say 0.001 Ohms per meter, times 200 km = 0.001 W/m  2105 m = 20 Ohms The current required by a single bulb using P = VI so I = P/V = 120 Watts/12 Volts = 10 Amps (!) Power in transmission line: P = I2R = 102  20 = 2,000 Watts!! “Efficiency” is e = 120 Watts/4120 Watts = 0.3%!!! Lecture 7

AC Electricity Why high voltage? The thing that kills us most is the high current through the (fixed resistance) transmission lines Need less current to reduce power: I2R But our appliance needs a certain amount of power P = VI so less current demands higher voltage Solution is high voltage transmission Repeating the previous calculation with 12,000 Volts delivered to the house draws only I = 120 Watts/12 kV = 0.01 Amps for one bulb, giving P = I2R = (0.01)220 = 2010-4 Watts, so P = 0.002 Watts of power dissipated in transmission line Efficiency in this case is e = 120 Watts/120.004 = 99.996% Lecture 7

AC Electricity Why high voltage? The thing that kills us most is the high current through the (fixed resistance) transmission lines Need less current to reduce power: I2R But our appliance needs a certain amount of power P = VI so less current demands higher voltage Solution is high voltage transmission Repeating the previous calculation with 12,000 Volts delivered to the house draws only I = 120 Watts/12 kV = 0.01 Amps for one bulb, giving P = I2R = (0.01)220 = 2010-4 Watts, so P = 0.002 Watts of power dissipated in transmission line Efficiency in this case is e = 120 Watts/120.004 = 99.996% Lecture 7

three-phase “live” wires AC Electricity Why high voltage? three-phase “live” wires to house 500,000 230,000 138,000 69,000 7–13,000 long-distance neighborhood But having high voltage in each household is a recipe for disaster sparks every time you plug something in/risk of fire/not cat-friendly Need a way to step-up/step-down voltage at will can’t do this with DC, so go to AC Lecture 7

Instantaneous and average power  Instantaneous power absorbed by the element: where

Instantaneous and average power  Average power absorbed by the element: and

Instantaneous and average power  Average power absorbed by the element: and

Instantaneous and average power Inductive load: current lags 90 degree behind voltage

Average power for a general impedance load

Example Find the power absorbed by each element and The average power at the voltage source

Example Find the power absorbed by each element and The average power at the voltage source

Example Find the power absorbed by each element and The average power at the voltage source

Example Find the power absorbed by each element  The voltage across the resistor The average power at the resistor  The voltage across the current source The average power at the current source

Example Find the power absorbed by each element  The voltage across the resistor The average power at the resistor  The voltage across the current source The average power at the current source

Example Find the power absorbed by each element  The voltage across the capacitor The average power at the inductor  The voltage across the inductor The average power at the inductor

Example Find the power absorbed by each element  The voltage across the capacitor The average power at the inductor  The voltage across the inductor The average power at the inductor

Maximum power transfer  What impedance will absorb the maximum amount of power? circuit

Maximum power transfer  

Maximum power transfer  When the load impedance is a complex conjugate of the Zth, the maximum power is transferred to the load

Maximum power transfer  What impedance will absorb the maximum amount of power? circuit

Example – 1

Example – 1

Example – 1

Example – 1

Example – 1

Example – 1

Example – 2 Find the load impedance that absorbs the maximum average power. Calculate that maximum average power.

Example – 2 Find the load impedance that absorbs the maximum average power. Calculate that maximum average power.

Example – 2 Find the load impedance that absorbs the maximum average power. Calculate that maximum average power.

Effective or RMS value  Effective value of a periodic current is the dc current that delivers the same average power to a resistor as the periodic current — Effective value of a periodic signal is its root mean square (rms) value. — For a sinusoidal , its rms value is

Effective or RMS value The average power in terms of rms value: The average power absorbed by a resistor R: Determine the rms value of the current waveform shown below If the current is passed through a 2-Ohm resistor, find the average power absorbed by the resistor

Effective or RMS value The average power in terms of rms value: The average power absorbed by a resistor R: Determine the rms value of the current waveform shown below If the current is passed through a 2-Ohm resistor, find the average power absorbed by the resistor

Apparent power and power factor (volt-amperes, VA)  Power factor (pf) Inductive element, lagging power factor (the current lags the voltage) Capacitive element, leading power factor (the current leads the voltage) Recall the impedance power factor is the angle of the load impedance

Example  Determine the power factor of the entire circuit below. Find the average power delivered by the source. Total impedance is  Power factor:  The rms value of the current:  The average power supplied by the source:

Example  Determine the power factor of the entire circuit below. Find the average power delivered by the source. Total impedance is  Power factor:  The rms value of the current:  The average power supplied by the source:

Example  Determine the power factor of the entire circuit below. Find the average power delivered by the source. Total impedance is  Power factor:  The rms value of the current:  The average power supplied by the source:

Complex power  The complex power absorbed by the ac load and with : the average power in watt delivered to a load (only useful power) : a measure of energy exchange between the source and the reactive par of the load (volt-ampere reactive: VAR)

Complex power  The complex power absorbed by the ac load and with : the average power in watt delivered to a load (only useful power) : a measure of energy exchange between the source and the reactive par of the load (volt-ampere reactive: VAR)

Complex power (p.211)  The complex power absorbed by the ac load Based on the reference voltage signal, Leading power factor (or load): Current leads voltage (capacitive load) Lagging power factor (or load): Current lags voltage (Inductive load) Apparent power Power triangle

Example – 1 A load Z draws 12 kVA at a power factor of 0.856 lagging from a 120-V rms sinusoidal source. Calculate: (a) the average and reactive powers delivered to the load, (b) the peak current, and (c) the load impedance (kW) (kVA)

Example – 2 A coil is to be represented by a linear model consisting of inductance L in series with resistance R. When a 60-Hz current of 2 A (rms) is supplied to the coil, the voltmeter across the coil reads 26 V (rms). A wattmeter indicates 20 W delivered to the coil. Determine L and R. and Reactive power

Example – 3 (p.212) An industrial load consists of the following: 30 kW of heating (resistive) and 150 kVA of induction motors operating 0.6 lagging pf. Power is supplied to the plant at 4000 V. Determine the total current and plant power factor.   From power factor we have  (kVA)

Example – 3 (p.212) An industrial load consists of the following: 30 kW of heating (resistive) and 150 kVA of induction motors operating 0.6 lagging pf. Power is supplied to the plant at 4000 V. Determine the total current and plant power factor.   From power factor we have  (kVA)

Example – 3 (p.212) An industrial load consists of the following: 30 kW of heating (resistive) and 150 kVA of induction motors operating 0.6 lagging pf. Power is supplied to the plant at 4000 V. Determine the total current and plant power factor.   The power factor gives

Example – 3 (p.212) An industrial load consists of the following: 30 kW of heating (resistive) and 150 kVA of induction motors operating 0.6 lagging pf. Power is supplied to the plant at 4000 V. Determine the total current and plant power factor.  (kVA)

AC power conservation  Whether the loads are connected in series or in parallel (or in general), the total power supplied by the source equals the total power delivered to the load. Thus, in general, for a source connected to N loads,  The complex, real, and reactive powers of the sources equal the respective sums of the complex, real, and reactive powers of the individual loads.

Example Find the real and reactive power absorbed by the source, the line and the load i) ii)

Example Find the real and reactive power absorbed by the source, the line and the load iii) iv)

Example Find the real and reactive power absorbed by the source, the line and the load v)

Power correction factor (Original)

Power correction factor  Example: When connected to a 120-V (rms), 60-Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the value of capacitance necessary to raise the pf to 0.95.

Example – 1 When connected to a 120-V (rms), 60-Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the value of capacitance necessary to raise the pf to 0.95.

Example – 2 (p.213) An industrial load consists of the following: 30 kW of heating (resistive) and 150 kVA of induction motors operating 0.6 lagging pf. Power is supplied to the plant at 4000 V. Power factor of the previous example is to be corrected to 0.9 lagging. Specify the necessary auxiliary equipment.

Example – 2 (p.213) Power factor of the previous example is to be corrected to 0.9 lagging. Specify the necessary auxiliary equipment. The necessary correction is