CONTROLS OF SUPER CRITICAL BOILERS

Slides:



Advertisements
Similar presentations
An Introduction To Marine Steam Propulsion Plant [Source: US Navy]
Advertisements

Main Condensate & Feed Systems
Coach Air Conditioning
Steam and Water Accessories
OFF DESIGN PERFORMANCE PREDICTION OF STEAM TURBINES
Operational Ideas for Supercritical Systems The Ultimate Criteria for Appreciation ….. P M V Subbarao Professor Mechanical Engineering Department I I.
Super Critical Boilers SYSTEM STUDIES ON ADVANCED POWER GENERATION TECHNOLOGIES FOR 21st CENTURY Dr V K Sethi Director MOP/ CEA.
Laddomat 21 For accumulation when using a wood-fired boiler Picture 1
Main Steam Cycle Let the fun begin….
Energy Efficient Steam Systems
Mountings & Accessories
Advanced Boiler Control for Biomass and Chemical Recovery Boilers
Boilers Dept. of Mech & Mfg. Engg..
Engine Cooling And Lubrication
HEATING AIR © Commonwealth of Australia 2010 | Licensed under AEShareNet Share and Return licence.
Refrigeration Flow Control
Energy Efficient Steam Systems. Steam Systems Steam systems most widely used type of process heating Advantages of steam: –Heat carrying capacity of steam.
Watertube Boiler.
Thermal Power Station Plant. Introduction 150 MW Thermal power station plant, produce 450t/hr steam at full load The max steam pressure is 150 bar with.
Section 5: Commercial Refrigeration
Superheaters.
Boiler Circulation Natural Circulation
Chapter 1 VAPOR AND COMBINED POWER CYCLES
Engineer Presentation
CHE 185 – PROCESS CONTROL AND DYNAMICS
Steam Power Plant.
Harnessing Free Heat. The Energy Harness provides hot water using multiple heat sources, making the best use of low grade heat. It improves the efficiency.
Main Condensate & Feed Systems
Product Introduction.
Thermal_Power_Plant_2 Prepared by: NMG
Lesson 7 Steam Power Plant.
Control & Automation For Super Critical Units
COMMISSIONING DEPARTMENT, NTPC-SIPAT
TURBINE & COOLING SYSTEM Presented By – AVIJEET PRATAP 07ME12 IET AGRA
Steam Power Station Presented By Ashvin G. Patel Asst. Prof. (E.E.)
Cascade, Ratio, and Feedforward Control
Vapor and Combined Power Cycles (2)
STUDY OF BOILER’S ACCESSORIES
Prof. D.N. Reddy Director Centre for Energy Technology University College of Engineering Osmania University.
HVAC523 Basic Subsystems.
BOILER PLANT OPERATION Presented By Mr. Sivanand Ray
SUBMITED BY BISWAJIT BEHERA
Generating Stations. Bulk electric power is produced by special plants known as generating stations or power plants. Depending upon the form of energy.
Lecture Objectives: Finish with absorption cooling Power generation Rankine cycles Connect power generation with heating and cooling –CHP –CCHP.
STEAM POWER PLANTS.
World Leaders in Combustion Management Solutions PID Control (P)roportional (I)ntegral Internal Stat PID (D)erivative Further.
World Leaders in Combustion Management Solutions Training School Autoflame Training 2013 PID.
Page 1 Petten 27 – Feb ALFRED and ELFR Secondary System and Plant Layout.
Super Critical Boilers Measures to improve Plant Efficiency And / or Heat Rate of Supercritical Units Turbine side measures : Higher steam parameters.
Thermal Power Station.
Presentation on Steam Power Plants R.C.Chaturvedi
Effect of Furnace Heat Transfer on Maximum Cycle Pressure Understanding of Fuel to Cycle Connections….. P M V Subbarao Professor Mechanical Engineering.
Prepared by : Nishant .A. Raval
Refrigeration Systems
MISS. RAHIMAH BINTI OTHMAN
Boiler Safety Valve Regulations
S.K.Thapa General Manager BHEL, Kolkata EFFICIENT CYCLE IN POWER GENERATION AN INDIAN PERSPECTIVE.
James McIntyre VRF Training Manager V5 Key Components.
Lesson 7 Steam Power Plant.
Review Questions Chapter 5
EP4P03 Nuclear Plant Systems and Operation
STEAM CAPACITY UPGRADING FOR BAGASSE FIRED BOILERS
Thermodynamics Cycles.
Controllers and Positioners
DELTAK HEAT RECOVERY STEAM GENERATOR
HIGH PERFORMANCE LEVEL CONTROL.
Furnace Heat Transfer & Steam Generation
Priyatmadi Jurusan teknik Elektro FT UGM
WATER AND STEAM SYSTEM.
Boiler Safety Valve Regulations
Presentation transcript:

CONTROLS OF SUPER CRITICAL BOILERS Presentation By AJAY SHUKLA Sr.Faculty PMI, Electricity generation is very complex in nature , where load demand changes on minute to minite basis, it is not manufacturing industry where u have got enough time match your demand and supply .In no industry other than power where real time matching of supply and demands is done on second to second basis. If you fail to response you are gone, and frequency may collapse or increase leading to grid failure. To match the demand you need continuous control of your turbine and boiler. Turbine is customer and boiler supplier but both should work in tandem to create win win situation

Boiler Turbine Control Let us see how any power plant controls the load or generate the MW. There are two components boiler and turbine, turbine has it own controls , since it consist of rotating mass of around 200 T rotor, many precaution is taken so that no point of time it should not go in unsafe zone. Now see the boiler utimate aim of boiler is to generate steam at required pressure and temp for turbine . Every thing is so dynamic in boiler that very complex boiler control is required. In the boiler we are burning the fuel , we need air and water so all the controls are required. Since we are burning fossil fuel so Boiler manufacture ensure that his boiler remains safe in all operating conditions follows certain standards while

Boiler Following Mode Now we have to meet the load demand so we can follow certain strategy there are different mode in which When ever gen load is increased , tur c/v will be open first , then pr will be dropped , so FW and fuel has to increased to meet MW demand, load followin capacity will be fast in this case

Turbine Following Mode In this when ever load is increased load demand will given first to increse Fuel and FW , Then based on pressure change load will be changed , so load following will be slow

Coordinate Mode Control When ever load is increased the command is given to increse fuel flow and FW flow both as well as load is increased same time to meet demand , load followin will be fast and throttle pr will not dropped , In SC we follow this mode for fast load pick up

Coordinate Mode Control This is CMC our unit generally run on this mode , many logic are in buiit based on unit capability and aux availibality , frequescy correction are taken as feed forward signal , what will happen if some thing will happen to any aux it gets tripped .

Drum and OT Control Comparison 1) I hope control for drum type is known to you , How we control feed water in drum type ,Drum acts as buffer ,It can work as 03 lement and 01 element .It is one of most important loop of C&I , Operation always demands this loop to be on auto ,So feed water loop which control the drum level in Drum type boiler in OT feed water controls the feed water flow. 2)Firing is there any differnce no 3) Pressure generally constant pressure but in OT it is sliding pressure control only. 4)

Drum and OT Control Comparison Why super heater temp control required , how it is done in drum type there are 02 methods Burner Tilt and other is super heater spray In OT super heater spray is used for short duration and feed water and firing ratio is used fro long term temp control RH temp control is same for both Start up system Drum type circulation natural or forced and out let goes to condenser At low load Feed water flow is less so circulation

OT Control Overview Hear realese and heat demand has to be balanced

Cycle of Supercritical Power Plant This is cycle of SC , extra is start up system

This is graphics based on PID and final garphic Fuel form 10 mills so 10 coal elevation, what mill u r giving all ball mill or tube , 2 LP , 2 COND CEP AND 4 LP 1-4 , 6-8 HPH where is 5th , b

Supercritical Power Plant This is korean plant with 4 sepeartor

OT Control Overview We use start up syste, , scheme , FW / Firing rate either these feed forward we can use feed water side or fule side

OT Start up Control mode 30% of TMCR KEPT , IN SOME FW = X1 + X1 X2

Super Critical Units Controls Mode

Flushing Mode

Flushing Mode

Start-Up System with Recirculation Recirculation Pump in Main Bypass Line SH Separator Flash Tank WW C ECO HWL To Condenser C Let see what is there in start up system , during start up water comes up to separator and it level is maintained, how that is maintained we will see Deaerator HPH C BFP

Start UP System Once sp level is maintained by WR and ZR valve , UG bcp

The separator water level remains stable for two(2) minutes START-UP If the water system of the boiler is empty (economizer, furnace walls, separators), then the system is filled with approximately 10% TMCR feed water flow. When the level in the separator reaches set-point, the WR valve will begin to open. When the WR valve reaches >30% open for approximately one minute, then increase feed water flow set-point to 30% TMCR. As the flow increases, WR valve will reach full open and ZR valve will begin to open. The water system is considered full when: The separator water level remains stable for two(2) minutes and The WR valve is fully opened and ZR valve is >15% open for two(2) minutes.

SEPARATOR STORAGE TANK LEVEL CONTROL Separator level is maintained by the combined action of a separator storage tank level feed water demand and the positioning of WR and ZR drain valves. Feed water demand is developed in response to separator storage tank level error and total fuel flow so as to prevent tank level from dropping too low. The WR and ZR valves are controlled in a split range manner to maintain the liquid level once the level reaches a high limit. The WR valve will respond first and then the ZR when the WR exceeds its linear operating range. Tank geometry is such that fluctuations in tank level are very dynamic, for this reason, only proportional control action established through the WR/ZR function curves is used to position these valves in response to level error. Sp level maintained ,FW Demand is trimmed by Sp lvl

UG VALVE CONTROL Control objective: Maintain minimum economizer inlet flow. Control action: The boiler circulating pump is started following the start of a turbine-driven feed water pump and the final clean-up cycle. This pump circulates feed water from the evaporator outlet back to the economizer inlet. Located at the outlet of this pump is the UG valve which controls economizer inlet flow during the start-up phase of operation. Demand for this recirculation control valve is established based on measured economizer inlet flow compared to a minimum boiler flow set point.

Separator water circuit of Super Critical BCP required at load < 30 ie that is wet mode , this is genarl ckt name of valve is different

FEEDWATER CONTROL LOOP Control objective: Develop total unit feed water demand as required to support unit load. Adjust feed water demand to maintain desired separator outlet temperature. Adjust separator outlet temperature set point as required to maintain acceptable platen superheat spray control range. Incorporate separator storage tank level (wet mode) feed water demand. Maintain minimum required economizer inlet flow. . Most important control loop CR 1 no storage luxury , why FW as per demand CR 1 , these are role

Feedwater Control This shows copmarison how feed water is controlled in drum type and once through , so in once through FW is not

Feed water firing rate ratio control

Feed water firing rate ratio control

Feed Forward with model Process Setpoint Feed Forward f(x) MODEL S P +/- C -/+ D d dt K  C +/- P +/- X

Feed Forward f(x) f(x) D D S X K K PROCESS FF process setpoint FF P +/- C -/+ P +/- C -/+ D D d dt d dt K K C +/- P +/- C +/- P +/- S X

Model predictive control + MW _ Fuel with model Without model Turbine setpoint Water wall Temperature C 60 120 180 240 300 t[sec]

Firing Rate Master

Fuel Rate Master

Feed Forward Firing Rate Control

Feed Forward Firing Rate Control

ANY QUESTIONS PLEASE

Yuhuan 4x1000MW Preparation of light off

Multi-combusting Nozzles with Separated Overfire Air Damper

BCP (Boiler Circulating Pump) will be stopped automatically. START-UP contd.. Water flows through the economizer and evaporator, and discharges the boiler through the WR valve to the flash tank and via connecting pipe to the condenser. Start BCP and open the UG valve to establish minimum water wall flow at 30% TMCR. As the pressure is raised, first the WR and then the ZR valves will open when separator water level increases due to boiler water swell. As pressure further increases, the WR and ZR valves will start to close as the water level decreases. The steam temperature at the separator inlet will reach a stable superheated condition at app. 30% TMCR, causing the level in the separator to decrease and eventually disappear. The boiler is now in once-through mode (dry mode). The BCP (Boiler Circulating Pump) will be stopped automatically. It is extremely important that minimum water wall flow be maintained at all times when firing the boiler to prevent tube damage due to overheating.

FEEDWATER CONTROL LOOP contd.. Demand for feed water is established predominately by the Boiler Master demand. This signal, processed though a “boiler transfer function” provides the feed forward component of the total feed water demand. The “boiler transfer function” is a tunable dynamic element providing a means to dynamically match the feed water feed forward demand to actual evaporator heat transfer. Optimization of the feed forward in this manner minimizes temperature fluctuations that may otherwise result from varying dynamic response between the firing and feed water control systems (as they relate to evaporator heat transfer) thereby lessening the dependence on feedback correction.

FEEDWATER CONTROL LOOP contd.. The first controller acts on a load dependent average platen spray differential temperature. Its output represents the required adjustment to evaporator heat transfer/steam generation to maintain both the steam conditions and flue gas temperatures entering the platen superheat section so as to ensure adequate platen spray control range. A second controller acts on a load dependent separator outlet temperature set point corrected by the platen spray differential temperature controllers output. This controller acts to adjust feed water in response to firing system disturbances and the relatively fast effect they have on separator outlet steam temperatures. The overall combined feed water feedback control action is such that feed water demand is responsive to changes in the overall unit heat transfer profile.

FEEDWATER CONTROL LOOP contd.. The combined feed forward/feedback demand signal is subject to a minimum economizer inlet flow set point (wet mode) activated if the boiler circulation pump is not in service and the unit is being fired. This ensures the minimum economizer inlet cooling flow is maintained by the feed water supply system in the event the start-up system is not available. The feed forward/feedback demand signal is subject to a second “wet mode” feed water demand developed to support separator storage tank level control. The resulting demand provides the set point to a feed water master controller. The fuel/feed water ratio protection logic provides overriding control of individual feeder speed demands in the event of an excessively high fuel to feed water ratio.