Advanced Fuse-Saving Techniques

Slides:



Advertisements
Similar presentations
Page 1 Outage Management Roy Hoffman 29 Jan 2001.
Advertisements

Speaker Scott Whaley - EIT Protecting & Ice Melting Westmans Distribution Lines.
New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
© Southwest Electrical Distribution Exchange (SWEDE) May 2, 2008 Materials and Equipment John Macek Application Director, S&C Electric.
Distributed Intelligence Provides Self-Healing for the Grid
MOLDED CASE CIRCUIT BREAKER BASICS
Dynamic Distribution Grids © 2012 San Diego Gas & Electric Company. All trademarks belong to their respective owners. All rights reserved. Neal Bartek.
1 Pacific Gas & Electric Company MTS: Evolution of the Electric Distribution System Manho Yeung, Senior Director, System Planning and Reliability PG&E.
RT3b – André Smit, Siemens USA
Spencer Murray, Sr. Telecom Eng. Distribution Automation.
CIGRE 7-10 September 2009, Moscow
1 1 Substation Asset Strategy Kevin Dasso, Senior Director Engineering and Operations IEEE/PES Annual Substations Committee Meeting April 7, 2008.
IMPACTS OF LARGE DISTRIBUTED GENERATORS ON CENTERPOINT ENERGY’S DISTRIBUTION SYSTEM 1 Presented by Ed Briggs, P.E. Manager of Electric Distribution Planning.
Fault Hunting Using Three-Phase Reclosers Michael S. CostaJerome V. JoskenDennis A. Walder Eversource EnergyUC SynergeticEaton IEEE Rural Electric Power.
ECE 333 Renewable Energy Systems Lecture 13: Per Unit, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
EE 369 POWER SYSTEM ANALYSIS
Chapter 7 SYSTEM PROTECTION
Metropolitan Planning Council Roundtable Discussion November 17, 2011 ComEd J. Tyler Anthony Senior Vice President, Distribution Operations.
1 Power Quality Mary Santori, P.E. Senior Engineer September 12, 2013.
APPA Engineering and Operations Technical Conference Atlanta, Georgia April 13-18, 2007 “Nailing the Basics” Earns Princeton, IL RP3 Diamond Award.
SWEDE - April 26 th, Bastrop Tommy Nylec Austin Energy Fusing and Fault Indicator Applications.
Distribution Automation: Fault Detection, Isolation, and Restoration
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
WESTERN UNDERGROUND COMMITTEE 2015 Spring Conference 65 th ANNIVERSARY 1950‐2015 Welcome Remarks Bill Chiu Director of Engineering – T&D Southern California.
1 U.S. Energy Information Administration, Annual Energy Review All energy input US average = 90.3 MWh per person, per year. Corresponds to 10.3 kW.
Frankfurt (Germany), 6-9 June 2011 ROSA – PT – S3 – 0249 EDP DISTRIBUTION AUTOMATION (r)EVOLUTION.
© ABB PTMV - 1, ABB Overhead Distribution Systems.
Chapter 6 Voltage Regulators - Part 2-.
Power Quality Impacts of Distributed Generation Roger C. Dugan Sr. Consultant Electrotek Concepts, Inc. Tennessee Tech. February 9, 2004.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Paper 0622 TOWARDS SELF-HEALING POWER DISTRIBUTION BY MEANS OF THE ZONE CONCEPT  Antti Kostiainen,
Steady State Analysis Of A Microgrid Connected To A Power System
Glades Electric Cooperative Infrastructure Miles of Line 2,213  Overhead Dist.2,180  UndergroundDist. 33  Transmission 87 16,402 meters Average 7.
Oncor Transmission Service Provider Kenneth A. Donohoo Director – System Planning, Distribution and Transmission Oncor Electric Delivery Co LLC
DISTRIBUTED GENERATION ISSUES Technical Issues Non-Technical Issues.
ECE 498HZ: Power Distribution System Analysis
Loop-Sectionalizing Automation Scheme Colin Hawthorne 4/26/2016.
Dr. Vidya Vankayala Director, Grid Modernization (604) Richard Guo
Distribution Automation The utilization of IEDs (Intelligent Electronic Devices) and advanced communications to unlock the benefits of operational efficiency.
April 7, 2015 Washington, D.C. Area Low-Voltage Event Operations Training Seminar 2016 Erik Johnson System Operations Training (ERCOT)
Protection of Power Systems
Austin Energy Elevated Requests for High Reliability Service South West Electric Distribution Exchange (SWEDE) May 8, 2015 David Tomczyszyn, P.E. – Distribution.
Automatic Transfer Switches
Protection of Power Systems
Utility Needs and Smart Grid for Major Storm Events
ECE 476 Power System Analysis
Unit 02: Voltage sag (6 hrs)
Overhead Distribution Systems
Predictive-Based Maintenance Strategy
Management Of Tulkarm Electrical Network
35kV Assessment SWEDE 2007 May 10, 2007.
Subteam 1a Competitive Solicitations Framework Working Group Meeting
the CERN Electrical network protection system
Trane Standby Generators
Project WECC-0100 Update Load Modeling Task Force
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Chapter 7 System Protection
Design of Electric Power Systems and Utilities
Exelon’s Leased Circuit Retirement Program
Southwest Gas Corporation Chris Sohus, Vice President/Operations
The Joint Accounting Conference 2018
Distributed Generation (DG) Modeling Criteria
Protective Relaying Conference
Irvine Smart Grid Demonstration Distribution Volt / Var Control
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
Peter van Oirsouw (Phase to Phase)
Interconnection of AES With The Grid
Project WECC-0100 Update Load Modeling Task Force
Customized gis applications for Electric DISTRIBUTION Utilities
Presentation transcript:

Advanced Fuse-Saving Techniques Tamer Rousan October 12, 2015

Ameren Corporation Serving 2.4 million electric and 933,000 gas customers over 64,000 square miles in Illinois and Missouri Generating 10,300 MW regulated electric generation capacity in Missouri Maintaining 7,400 circuit miles of electric transmission Employing more than 8500 personnel Average annual economic impact of $8.6 billion

Ameren Illinois Serving approximately 1.2 million electric and 827,000 gas customers. Service territory of approximately 40,000 square miles in central and southern Illinois. 4,500 miles of electric transmission lines 45,700 miles of electric distribution lines 1,035 distribution substations. 2,688 distribution circuits.

Ameren’s Protection and Coordination Settings Philosophies Ameren Illinois Ameren’s Protection and Coordination Settings Philosophies

Ameren’s Protection and Coordination Settings Philosophies Ameren Illinois’ philosophy is to fundamentally use the fault interrupter as a feeder mid-point protection device for fault isolation, coupled with a fault interrupter at a tie point to allow for quick and automatic system restoration

Ameren’s Protection and Coordination Settings Philosophies Ameren Illinois Distribution Automation (DA) engineering group has standardized its protection and coordination settings philosophy for the mid-tie-mid application. To maintain the coordination of series devices that have the same protection settings, an advanced feature called the PulseFinding™ Fault Location Technique is enabled. We also elected to use Intelligent Fuse Savings on the fault interrupters.

Ameren’s Protection and Coordination Settings Philosophies Intelligent Fuse Savings automatically determines whether a fuse-saving “fast” trip should be used based on the fault-current magnitude. At high fault currents, a mechanical device cannot trip faster than a fuse will operate, so Intelligent Fuse Savings will avoid using the fast trip, thereby reducing momentary outages. Ameren engineering recommends enabling Intelligent Fuse Savings using a fuse-savings curve that matches the largest fuse size desirable to save downstream of the mid-point fault interrupter. Choosing the largest fuse to save should be based on the fuse size used most downstream of the fault interrupter and that serves the largest number of customers.

Ameren’s Protection and Coordination Settings Philosophies

Ameren Illinois Ameren Illinois’ IntelliRupter Fault Interrupter Protection and Coordination Settings Program.

Ameren Illinois’ IntelliRupter Fault Interrupter Protection and Coordination Settings Program To drive consistency, DA engineering built a program that takes in data similar to the information in the previous tables, and the group automatically runs through the rules of calculating CTI. It then selects the standard recloser emulation, the optimal PulseFinding setting, and the Intelligent Fuse Savings curve. The program runs the above tasks for coordination in both directions, draws a circuit diagram with the settings printed on it, and plots the TCC coordination curves

Ameren Illinois’ IntelliRupter Fault Interrupter Protection and Coordination Settings Program

Ameren Illinois’ IntelliRupter Fault Interrupter Protection and Coordination Settings Program

Ameren Illinois Ameren Illinois’ IntelliRupter Field Results of Intelligent Fuse Saving.

Field Results of Intelligent Fuse Saving Service restored after ~ 200ms ~1900 A RMS – Pole 3 PulseClose lasting ~ 5ms Based on the TCC plots, effective fuse-saving ranges from 560 A through 1900 A. Faults greater than 1900 A exceed the maximum coordinating current of the fuse-saving curve, so timing only occurs on the delayed curve. A fast Intelligent Fuse Savings trip clears the fault after several cycles (66 ms) before the down-line fuse begins to melt. Single-phase tripping reduces momentary outages by approximately two-thirds because the customers served by poles 1 and 2 remained in service throughout this event. Example of a fuse saved on a transient fault. B163 6/14/2014

Field Results of Intelligent Fuse Saving Larger PulseCloses in both polarities Service restored after fuse cleared the fault ~2000 A RMS – Pole 3 A hard close allows fuse to operate For the next example, the event starts off similar to the previous event. However, the pulse closes seen in trace 3 are larger and indicate that the fault is still present. A lateral experiences a low-magnitude phase-ground fault (~2000 A RMS). After the initial trip, pulse closes in both polarities indicate that the fault is still present, so the fault interrupter remains open for several more seconds. A close operation on the second test allows the fuse to operate on the sustained fault down line of the fuse. It is evident that the fuse cleared the fault because the current in trace 3 goes from fault current immediately to load current. Example of a fuse operation for a sustained fault on lateral–B163 9/14/2014

Field Results of Intelligent Fuse Saving Service restored immediatley (except for customers downstream of the fuse) ~3493 A RMS – Pole 1 A lateral experiences a high magnitude phase-ground sustained fault on pole 1 (~3493 A RMS). Because of the high magnitude, the fuse cannot be saved. The Intelligent Fuse Savings feature skips the fast curve tripping, and timing occurs using a delayed curve that allows the fuse to operate before the fault interrupter trips. The fuse interrupts the fault in roughly 73 ms. Load current on pole 1 is immediately restored (except to customers downstream of the fuse). All customers downstream of this fault interrupter have been spared from a momentary outage. Example of a fuse blown on a transient fault–B176–10/2/2014

Field Results of Intelligent Fuse Saving Fault on mainline, no fuse operation, fault interrupter trips after 217 ms ~3600 A RMS – Pole 1 The main line experiences a phase-ground transient fault of 3600 A on pole 1, which exceeds the fuse-saving cutoff. Because of the high magnitude, fast tripping is skipped and timing occurs using a delayed curve that allows the fuse to operate before the fault interrupter trips. Because the fault is on the main line, the lateral does not see the fault, and there is no fuse operation. The fault interrupter trips after 217 ms. Example of a transient fault on the main line–MV155 8/23/2014.

Advanced Fuse-Saving Techniques Conclusions   Ameren Illinois has standardized on the S&C IntelliRupter PulseCloser Fault Interrupter for 12-kV distribution feeder-protection applications. The objective is to simplify the coordination and configuration of the distribution-system devices by using advanced features of the fault interrupter. The calculator tool created by the DA engineering group simplifies coordination for the typical mid-tie-mid application by automating and optimizing the protection settings. The real-life examples of faults on main lines and laterals demonstrate that single-phase tripping and Intelligent Fuse Savings features are improving customer service reliability. Ameren Illinois will continue to monitor the field events and look for opportunities to improve reliability of electricity service while simplifying and standardizing protection and coordination practices.

Distribution Automation Questions?

Thank you for attending and participating. Have a great day! Contact me with any follow-up questions. Provide email and phone number