THE SUBJECT G R O U N D I N G AND THE N E C.

Slides:



Advertisements
Similar presentations
Control Circuit Protection Supplementary Protectors vs
Advertisements

The Electrical GuruTM Paul W. Abernathy,CME
DC Circuits Ch. 28 These circuit elements and many others can be combined to produce a limitless variety of useful devices wire open switch closed switch.
Bonding Requirements For Gas Piping Systems Bob Torbin October 2007
Stray Current Investigations A Method of Troubleshooting Stray Current on Underground Residential Distribution (URD) Loops Stacey Mighty Malcolm Distribution.
Telecom Cabling Grounding and bonding.
EE4503 Electrical Systems Design
EET Survey of Electronics
Electrical Power Systems
Electric Circuits. Danger – Do not attempt electrical work until you have learned the safe and proper technique from a certified electrician. Copyright.
Bonding, Grounding and the NEC  Presented by The National Association of Certified Home Inspectors
2011 NEC ROP - CMP 5 Report to SCC 18
The Home Inspection Book: A Guide for Professionals By Marcia Darvin Spada Copyright, Thomson/South-Western, 2003, Revised, 2006.
Purpose Power lines Equipment Assured Grounding GFCI Conclusion.
Grounding, bonding, and ground fault currents
Wiring and Grounding.
November 4, 2013 Topic: Electric Circuit Objectives:
Ag. Mechanics for Beginning Teachers
Electrical Safety Authority
1 © 2015 Eaton. All Rights Reserved.. Suggestion on How to Use Industry Trainers are encouraged to use this material in their sessions Download the presentation.
Starting Residential Wiring.  The most important element in wiring. Safety is proper grounding.  Grounding is the connection of all parts of a wiring.
Electrical Circuits Chapter 20 Section Three. Science Journal Entry #42 Expound upon Ohm’s Law and its relationship to current, resistance, and voltage.
HOUSE WIRING Final Review. Electricity Electricity = flow of electrons Conductor= electricity passes thru easily - Metal, water, person Insulator = restricts.
HOUSE WIRING NOTES. Electricity  Proton – positive charge  Electron – Negative charge  Electricity = flow of electrons Conductor= electricity passes.
Residential Wiring Unit 3 – Installation and Planning.
Grounding the Electrical System Reference: AAVIM “Electrical Wiring” Created May 2007.
ELECTRICAL WIRING WIRING BASICS Written by Bobby Joslin
“Charge it today!”. Charges were first discovered in ancient Greece when cloth was rubbed on amber and the amber attracted bits of straw to it. It was.
Unit 231 Grounding Bonding Overcurrent Protection.
Chapter 3 Basic Electrical Circuits Chapter 3 Basic Electrical Circuits.
Electrical Safety.
UNIT-5. ELECTRICAL SAFETY, WIRING & INTRODUCTION TO POWER SYSTEM
Smitty’s Two Minute Drill Grounding
SERIES, PARALLEL, AND SERIES-PARALLEL CIRCUITS
Grounding the Electrical System
Grounding.
Circuit Protection Unit 9.
Basic Electrical Safety
QQ: How are electric force and charge related?
Grounding the Electrical System
"Don't Get Amped Up! Electrical Safety to Keep Your Team Grounded!"
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
AFCI Protection: AFCI Receptacles and the NEC
Electrical Safety in the Home
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
“Ladder” Diagrams Chapter 6 - Ladder Logic LADDER DIAGRAMS ARE SPECIALIZED SCHEMATICS COMMONLY USED TO DOCUMENT INDUSTRIAL CONTROL LOGIC SYSTEMS.
The Electric Circuit.
EET 323 – Electrical System Design Lecture 4: Wiring Devices
Domestic Electricity AIM: To understand the use of domestic electricity and safety features such as fuses, circuit breakers and the earth circuit
Overcurrent Protection— Fuses and Circuit Breakers
EET 323 – Electrical System Design Lecture 9: Grounding
EET 323 – Electrical System Design Lecture 11: Panel-boards and Switch-boards Instructor: Radian Belu, PhD.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Safety Meeting Topics Standby Generator Safety
Basic Electrical Safety
Basic Electrical Safety
Smitty’s Two Minute Drill Grounding and Bonding
P2.5.Mains Electricity AC and DC Current Cables and Plugs
Objectives Learn about 3 Phase vs. 1 phase F&N vs. 1 phase F&F
DC Circuits Ch. 27 These circuit elements and many others can be combined to produce a limitless variety of useful devices wire open switch closed switch.
2008 Code Drills Health Care Facilities
Electrical components and systems
Electrical components and systems
2020 National Electric Code
North Carolina Department of Insurance Office of State Fire Marshal
State Electrical Division North Carolina Department of Insurance
2019 ECR Presentation “HOT SKIN”
Presentation transcript:

THE SUBJECT G R O U N D I N G AND THE N E C

THE SPEAKER BOB LUDECKE Member IAEI CA Certified Electrician Lic. Electrical Contractor CSLB Industry Expert CSLB Subject Matter Expert Hands on Electrician Since 1974

SPECIAL THANKS TO Thomas E. Trainor Chief Electrical Inspector City of San Diego, California Representing IAEI on CMP 7 Member - NFPA Member - U.L. Electrical Council

ALSO GUILTY OF: Member of the original NFPA Task Group on the Useability of the National Electrical Code Chaired the sub-committee assigned to review Article 250 and make recommendations to improve it’s “useability”

The ‘99 NEC Completely Reorganized Exceptions Minimized And Most Importantly....... Performance Requirements Added

Prescriptive vs Performance NEC rules are typically Prescriptive A Prescriptive Rule tells you what to do But, what it doesn’t tell you is..... Why you’re doing it!

Prescriptive vs Performance A Performance Rule is descriptive It describes what has to be accomplished And this description will most generally Explain the intent of the rule

Why is this Important? Grounding continues to be a Mystery Improper Grounding is Commonplace Proper Grounding is vital for an installation To protect from Fire and Electrocution

Why is this Important? It is my considered opinion, That a better understanding of The intent of the Grounding Rules Will lead to better, safer installations

TYPICAL CIRCUIT OPERATION Only four things can happen when a circuit is energized. It can operate normally There can be an overload There can be a short circuit There can be a ground fault

HOW DOES GROUNDING FIT IN? As long as the circuit is operating normally, GROUNDING IS NOT NEEDED

THE “UNGROUNDED” CIRCUIT A circuit consisting of a transformer, 2 - 15A conductors and a light bulb will operate just fine (Check out the barn) Grounding is not needed To make it work or To make it safe

HOW DOES GROUNDING FIT IN? Under an overload condition, GROUNDING IS NOT NEEDED PROTECTION FROM OVERLOAD IS PROVIDED BY THE OVERCURRENT DEVICE Note that current is only flowing on the conductors that we installed to carry current

HOW DOES GROUNDING FIT IN? Under a short circuit condition, GROUNDING IS NOT NEEDED PROTECTION AGAINST SHORT CIRCUIT IS PROVIDED BY THE OVERCURRENT DEVICE Again, current is only flowing on the conductors we installed to carry current

HOW DOES GROUNDING FIT IN? Under a ground fault condition, GROUNDING IS NOT NEEDED PROTECTION AGAINST GROUND FAULT IS PROVIDED BY THE OVERCURRENT DEVICE HOWEVER……...

RETURN PATH REQUIRED THE OVERCURRENT DEVICE CAN ONLY PROTECT AGAINST A GROUND FAULT IF, THE CIRCUIT IS INSTALLED SO THAT ALL METAL PARTS ARE BONDED TOGETHER AND TO THE SERVICE NEUTRAL, WHICH CREATES A LOW RESISTANCE PATH FOR FAULT CURRENT TO RETURN TO THE SOURCE OF SUPPLY

LETS LOOK AT A TYPICAL CIRCUIT D 100’ of Overhead Distribution Line, 25’ of Service Drop, 25’ of Service Entrance Conductor, 100’ of Branch Circuit Conductors

LETS LOOK AT A TYPICAL CIRCUIT D Current flows…...

LETS LOOK AT A TYPICAL CIRCUIT D From the transformer to our Service

Through the Overcurrent Device to our Load PATH OF CURRENT FLOW - NORMAL OPERATION L O A D Through the Overcurrent Device to our Load

Through the Load returning to the Service PATH OF CURRENT FLOW - NORMAL OPERATION L O A D Through the Load returning to the Service

And back to the transformer PATH OF CURRENT FLOW - NORMAL OPERATION L O A D And back to the transformer

What determines the amount of current that will flow in this circuit? PATH OF CURRENT FLOW - NORMAL OPERATION L O A D What determines the amount of current that will flow in this circuit?

PATH OF CURRENT FLOW - NORMAL OPERATION D The Total RESISTANCE or IMPEDANCE in the circuit will determine the amount of current that will flow in the circuit

OHMS LAW WORKS E = I x R still works THINGS YOU CAN COUNT ON We can change the code, or Hire a different contractor, or Use romex instead of EMT, but E = I x R still works

How is our circuit protected against overload and short circuit? OVERLOAD AND SHORT CIRCUIT CONDITIONS L O A D How is our circuit protected against overload and short circuit?

THE OVERCURRENT DEVICE PROTECTS THIS CIRCUIT FROM BOTH OVERLOAD AND SHORT CIRCUIT CONDITIONS 15A Circuit Breaker L O A D THE OVERCURRENT DEVICE PROTECTS THIS CIRCUIT FROM BOTH OVERLOAD AND SHORT CIRCUIT

SUMMARIZING TO THIS POINT CIRCUIT CONDITION PROTECTION PROVIDED BY: GROUNDING? O/C PROT? NORMAL OPERATION NO NO OVERLOAD CONDITION NO YES SHORT CIRCUIT CONDITION YES NO

GROUND FAULT CONDITION So lets talk about a Ground Fault Condition Which certainly sounds like the one condition where Grounding would be important and decide for ourselves whether Grounding Provides Protection for Equipment or Personnel under a Ground Fault Condition

GROUND FAULT CONDITION What happens if the hot conductor comes into contact with our metal box?

GROUND FAULT CONDITION And our friend comes along and touches it? IS HE IN JEOPARDY?

GROUND FAULT CONDITION NO NOT AT ALL AND WHY NOT?

GROUND FAULT CONDITION Because the transformer we’re looking at IS NOT GROUNDED so there is NO PATH THROUGH EARTH for current to return to the transformer

GROUND FAULT CONDITION Yes, that was a “Trick” question Sorry about that But the intent was to make a point

THINGS YOU CAN COUNT ON NO CIRCUIT - NO CURRENT CURRENT DOES NOT FLOW UNLESS THERE IS A CONTINOUS PATH FROM ONE SIDE OF THE SOURCE OF SUPPLY TO THE OTHER CURRENT CANNOT TRAVEL THROUGH THE EARTH TO RETURN TO A TRANSFORMER UNLESS THE TRANSFORMER IS GROUNDED

GROUND FAULT CONDITION So our friend in this situation is perfectly safe HOWEVER.....

GROUND FAULT CONDITION What do we know about utility company transformers?

GROUND FAULT CONDITION THEY’RE GROUNDED And, with this transformer grounded, our friend is in serious jeopardy

SO WHY ARE THEY GROUNDED? To minimize the damage caused if lightning strikes their distribution lines, or If a 12 KV line drops onto a low voltage line, In addition, grounding the neutral of the distribution system stabilizes the voltage. So, basically for the same reason we ground services at buildings.

GROUND FAULT CONDITION Because utility transformers are grounded, we need to do something to our equipment to keep our friend from being electrocuted

GROUND FAULT CONDITION Can we protect our friend by grounding our metal equipment? Lets take a look.

GROUND FAULT CONDITION Grounding our equipment provides a second path for fault current

GROUND FAULT CONDITION The first is through our friend to earth and back to the transformer

GROUND FAULT CONDITION The new second path is through our metal equipment to earth and back to the transformer

FAULT CURRENT PATH We need to open a 15A Circuit Breaker as quickly as possible. This will require a fault current of 60A to 75A. (4 to 5 times the rating of the breaker) We can use Ohm’s Law to find out how much current will flow on our new path.

GROUND FAULT CONDITION The voltage is 120V. We need to know the resistance in this circuit to calculate current

FAULT CURRENT PATH Assuming a minimum of 5 ohms resistance through each grounding electrode, we know there is at least 10 ohms resistance in the fault path that we created by grounding our equipment.

FAULT CURRENT PATH THEREFORE, USING OHM’S LAW: E = I x R and Transposing, I = E / R I (current) = E(voltage) / R(resistance) and so, I = 120 / 10 = 12A

ONLY 12 AMPS FAULT CURRENT PATH ABSOLUTELY NOT WILL 12 AMPS TRIP OUR 15A CIRCUIT BREAKER? ABSOLUTELY NOT

WITH EQUIPMENT GROUNDED L O A D So the Overcurrent Device does not open And we have fried our friend

EQUIPMENT OR PERSONNEL CONCLUSION GROUNDING DOES NOT PROTECT EQUIPMENT OR PERSONNEL FROM A GROUND FAULT

THE BONDING CONNECTION L O A D The vital connection left out of our discussion until now is the bonding of metal equipment to the service neutral

THE BONDING CONNECTION Every piece of conductive metal which is a part of our system or likely to become energized Must be connected together by an electrically continuous metal-to-metal contact or by an equipment grounding conductor

THE BONDING CONNECTION These connections create an electrically continuous, low resistance path from every part of our system back to the service equipment At the Service, these connections terminate on the Neutral Bus

THE BONDING CONNECTION L O A D These bonding connections let us use the neutral as a return path for fault current

THE BONDING CONNECTION L O A D Bonding provides a third path for fault current to return to the source of supply

FAULT CURRENT PATH We need to open a 15A Circuit Breaker as quickly as possible. This will require a fault current of 60A to 75A. (4 to 5 times the rating of the breaker) We can use Ohm’s Law to find out how much current will flow on our new path.

FAULT CURRENT PATH The resistance in this path includes 100’ - #2 AL OH Distribution .032 25’ - #4 AL Service Drop .013 25’ - #2 CU Service Entrance .005 100’ - #14 CU Branch Circuit .307 Resistance to the point of fault .357 ohms

THE BONDING CONNECTION .357 ohms L O A D .3 ohms The resistance from the point of fault through our metal equipment back to the neutral is assumed to be the same as the branch circuit wiring and 100’ of #14 cu has a resistance of .3 ohm

THE BONDING CONNECTION .357 ohms .57 ohms L O A D .3 ohms The total resistance in this path created by bonding is .714 ohms

FAULT CURRENT PATH USING OHM’S LAW: E = I x R and Transposing, I = E / R I (current) = E(voltage) / R(resistance) and so, I = 120 / .714 = 168A

THE BONDING CONNECTION L O A D The Fault Current Return Path through the Neutral allows 168A of fault current to flow and forces the overcurrent device to open

THE BONDING CONNECTION L O A D THIS PATH DOES NOT RELY ON GROUNDING AND WORKS EVEN IF OUR SYSTEM IS NOT GROUNDED

CONCLUSION THE OVERCURRENT DEVICE PROTECTS AGAINST GROUND FAULT CONDITIONS PROVIDED THAT OUR CIRCUITS HAVE BEEN INSTALLED SO THAT ALL CONDUCTIVE METALS ARE BONDED TOGETHER AND TO THE SERVICE NEUTRAL

GROUNDING IN REVIEW IS A CONNECTION TO EARTH INTENDED TO PROTECT OUR ELECTRICAL SYSTEM FROM LIGHTNING AND HIGH VOLTAGE

THE OVERCURRENT DEVICE IN REVIEW THE OVERCURRENT DEVICE PROTECTS OUR ELECTRICAL SYSTEM FROM OVERLOAD AND SHORT CIRCUIT

THE OVERCURRENT DEVICE IN REVIEW THE OVERCURRENT DEVICE PROTECTS OUR ELECTRICAL SYSTEM FROM A GROUND FAULT CONDITION IF…….

PROPER BONDING HAS CREATED IN REVIEW PROPER BONDING HAS CREATED AN ELECTRICALLY CONTINOUS, LOW RESISTANCE PATH FOR FAULT CURRENT TO RETURN TO THE NEUTRAL AT THE SERVICE

“GROUNDING” SO WHAT’S THE PROBLEM? WHY DOES CONTINUE TO BE A SUBJECT OF MYSTERY AND CONFUSION?

IN MY OPINION There are Three Areas where the CODE has not dealt well with this subject. THEY ARE: CONFUSING VOCABULARY OVER-EMPHASIS ON GROUNDING ACTUAL MISINFORMATION

VOCABULARY WHICH TERMS ARE EASIER TO READ AND UNDERSTAND? unGROUNDed GROUNDed GROUNDing HOT NEUTRAL GROUND ENOUGH SAID

OVER-EMPHASIS ON GROUNDING ARTICLE 250 IN THE 1996 NEC IS DIVIDED INTO TWELVE PARTS ELEVEN ARE ON GROUNDING ONLY ONE IS ON BONDING The Term “Low Impedance Ground Fault Return Path” is not mentioned at all

ACTUAL MISINFORMATION IN THE 1990 NEC, THE FINE PRINT NOTES TOLD US THAT EQUIPMENT WAS GROUNDED IN ORDER TO “FACILITATE THE OPERATION OF OVERCURRENT DEVICES UNDER FAULT CONDITIONS”

ACTUAL MISINFORMATION IN THE 1996 NEC, SECTION 250-51 STILL TELLS US THAT THE “PATH TO GROUND” MUST BE OF LOW IMPEDANCE IN ORDER TO “FACILITATE THE OPERATION OF THE CIRCUIT PROTECTIVE DEVICES”

A CONNECTION TO EARTH, and ACTUAL MISINFORMATION ARTICLE 100 PROVIDES GOOD DEFINITIONS OF: GROUNDING, which is A CONNECTION TO EARTH, and BONDING, which is AN INTERCONNECTION OF PARTS

THE CONNECTION TO EARTH, THE INTERCONNECTION OF PARTS ACTUAL MISINFORMATION BUT ARTICLE 250 HAS TENDED TO USE THE TERM “GROUNDING” AS IF IT INCLUDED THE CONNECTION TO EARTH, THE INTERCONNECTION OF PARTS and THE FAULT CURRENT PATH

A RESTRUCTURED AND REVISED ARTICLE 250 THE 1999 NEC BRINGS US……. A RESTRUCTURED AND REVISED ARTICLE 250 Which not only: Puts requirements in a more logical order, And reduces the number of exceptions by changing them to positive text

THE 1999 NEC BRINGS US……. BUT ALSO ADDS: PERFORMANCE REQUIREMENTS FOR GROUNDING and BONDING, AND THE NEW TERM “FAULT CURRENT PATH”

THE 1999 NEC BRINGS US……. AND, THROUGH THESE NEW PERFORMANCE REQUIREMENTS, MORE CLEARLY IDENTIFIES WHAT GROUNDING, BONDING AND THE FAULT CURRENT PATH ARE REQUIRED TO ACCOMPLISH

THE 1999 NEC BRINGS US……. Appendix E which provides cross references from the “96 to the ‘99 NEC and vice versa Figure 250-2 which graphically depicts the relationship of Bonding to the other Parts of Article 250 to emphasize it’s importance

HOWEVER............. AMENDMENTS TO ARTICLE 250 IN THE 1999 NEC HAVE BEEN APPROVED BY CMP-5 AND AT THE NFPA ANNUAL MEETING IN ANAHEIM WE CAN BENEFIT FROM THESE ADOPTED CHANGES WHICH WILL BE PUBLISHED IN THE 2002 NEC

Help From The 2002 NEC In a new Section 250-2, the 2002 NEC adds definitions of technical terms, such as: Ground Fault Ground-Fault Current Path Effective Ground-Fault Current Path A real help in understanding the intent of the Grounding and Bonding requirements

Help From The 2002 NEC Old Section 250-2 becomes 250-4 Which now better explains the differences between Grounding and Bonding, and Separates the requirements for Grounded and Ungrounded Systems Another plus for user-friendly code

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. Ground Fault. An unintentional, electrically conducting connection between an ungrounded conductor of an electrical circuit and the normally non-current carrying conductors, metallic enclosures, metallic raceways, metallic equipment or earth.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. Ground-Fault Current Path. An electrically conductive path from the point of a ground fault on a wiring system through normally non-current carrying conductors, equipment or the earth to the electrical supply source.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. FPN: Examples of ground-fault current paths could consist of any combination of equipment grounding conductors, metallic raceways, metallic cable sheaths, electrical equipment, and any other electrically conductive material such as metal water and gas piping, steel framing members, stucco mesh, metal ducting, reinforcing steel, shields of communication cables and the earth itself.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. Effective Ground-Fault Current Path. An intentionally constructed, permanent, low impedance, electrically conductive path designed and intended to carry current under ground fault conditions from the point of a ground fault on a wiring system to the electrical supply source.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. FPN: An effective ground-fault current path is created by effectively bonding together all of the electrically conductive materials that are likely to be energized by the wiring system. Effective bonding is accomplished through the use of equipment grounding conductors, bonding jumpers or bonding conductors, approved metallic raceways, connectors and couplings, approved metallic sheathed cable and cable fittings, and other approved devices. A ground fault path is effective when it will safely carry the maximum ground fault current likely to be imposed on it.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. An effective ground-fault current path is created by effectively bonding together all of the electrically conductive materials that are likely to be energized by the wiring system.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. Effective bonding is accomplished through the use of equipment grounding conductors, bonding jumpers or bonding conductors, approved metallic raceways, connectors and couplings, approved metallic sheathed cable and cable fittings, and other approved devices.

New Section 250-2 Definitions. THE 2002 NEC New Section 250-2 Definitions. A ground fault path is effective when it will safely carry the maximum ground fault current likely to be imposed on it.

Help From The 2002 NEC Old Section 250-2 becomes: 250-4. General Requirements for Grounding and Bonding which is divided into: (A) Grounded Systems, and (B) Ungrounded Systems

Help From The 2002 NEC New Section 250-4 (A) (1) Electrical System Grounding (2) Grounding of Electrical Equipment (3) Bonding of Electrical Equipment (4) Bonding of Electrically Conductive Materials and Other Equipment (5) Effective Ground Fault Current Path

Help From The 2002 NEC New Section 250-4 (A) (1) Electrical System Grounding Electrical systems that are grounded shall be connected to earth in a manner that will limit the voltage imposed by lightning, line surges, or unintentional contact with higher voltage lines and that will stabilize the voltage to earth during normal operation.

Help From The 2002 NEC New Section 250-4 (A) (2) Grounding of Electrical Equipment Non-current carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth so as to limit the voltage to ground on these materials.

Help From The 2002 NEC New Section 250-4 (A) (3) Bonding of Electrical Equipment Non-current carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected together and to the electrical supply source in a manner that establishes an effective ground fault current path.

Help From The 2002 NEC New Section 250-4 (A) (4) Bonding of Electrical Conductive Materials and Other Equipment Electrically conductive materials that are likely to become energized shall be connected together and to the electrical supply source in a manner that establishes an effective ground fault current path.

(5) Effective Ground Fault Current Path Help From The 2002 NEC New Section 250-4 (A) (5) Effective Ground Fault Current Path Electrical equipment and wiring and other electrically conductive material likely to become energized shall be installed in a manner that creates a permanent, low impedance circuit capable of safely carrying the maximum ground fault current likely to be imposed on it from any point on the wiring system where a ground fault may occur to the electrical supply source. The earth shall not be used as the sole equipment grounding conductor or fault current path.

Help From The 2002 NEC New Section 250-4 (B) (1) Grounding of Electrical Equipment (2) Bonding of Electrical Equipment (3) Bonding of Electrically Conductive Materials and Other Equipment (4) Path for Fault Current

(1) Grounding of Electrical Equipment Help From The 2002 NEC New Section 250-4 (B) (1) Grounding of Electrical Equipment Non-current carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth so as to limit the voltage imposed by lightning, line surges, or unintentional contact with higher voltage lines and limit the voltage to ground on these materials

(2) Bonding of Electrical Equipment Help From The 2002 NEC New Section 250-4 (B) (2) Bonding of Electrical Equipment Non-current carrying conductive materials enclosing electrical conductors or equipment, shall be connected together and to the supply system grounded equipment in a manner that creates a permanent, low impedance path for ground fault current which is capable of safely carrying the maximum fault current likely to be imposed on it.

(3) Bonding of Electrical Conductive Materials and Other Equipment Help From The 2002 NEC New Section 250-4 (B) (3) Bonding of Electrical Conductive Materials and Other Equipment Electrically conductive materials that are likely to become energized shall be connected together and to the supply system grounded equipment in a manner that creates a permanent, low impedance path for ground fault current which is capable of safely carrying the maximum fault current likely to be imposed on it.

(4) Path for Fault Current Help From The 2002 NEC New Section 250-4 (B) (4) Path for Fault Current Electrical equipment, wiring and other electrically conductive material likely to become energized shall be installed in a manner that creates a permanent, low impedance circuit from any point on the wiring system to the electrical supply source to facilitate the operation of overcurrent devices should a second fault occur on the wiring system. The earth shall not be used as the sole equipment grounding conductor or fault current path.

IN CLOSING THE CHANGES TO ARTICLE 250 IN THE ‘99 & ‘O2 NEC ARE EXTENSIVE IT HAS BEEN COMPLETELY RENUMBERED AND REWORDED MANY EXCEPTIONS HAVE BEEN REWRITTEN INTO POSITIVE TEXT

IN CLOSING SOME RULES, SUCH AS 250-32, HAVE BEEN COMPLETELY CHANGED OTHERS HAVE BEEN RELOCATED, REWRITTEN AND/OR REORGANIZED THESE CHANGES WILL AFFECT EVERYONE INVOLVED IN THE ELECTRICAL INDUSTTRY

THE POSITIVE APPROACH These changes are a blessing in disguise We all need to get a fresh start on this subject and clarify our understanding of why we ground and bond electrical systems and how grounding and bonding are related to safe electrical installations

THE POSITIVE APPROACH The best way to do that is to work through Article 250 as if it were totally new Check that terms are used consistently as they are defined Check the rules against what you see in the field

THE POSITIVE APPROACH Always question the “why” of the rule Don’t stop until you really understand it And how to apply it on the job

THE POSITIVE APPROACH And, when you review Grounding Use the wording in the 2002 NEC It’s the closest we’ve ever gotten to accurately describing this topic

THE POSITIVE APPROACH Using the new wording in the 2002 NEC Will make it easier to show contractors what Grounding and Bonding have to accomplish And that’s important because

Ground-Fault Current Path THE POSITIVE APPROACH Grounding Bonding and the Ground-Fault Current Path are critical elements of electrical safety

FOR YOUR TIME AND ATTENTION THANK YOU FOR YOUR TIME AND ATTENTION