Part Three – Relay Input Sources

Slides:



Advertisements
Similar presentations
Introductory Circuit Analysis Robert L. Boylestad
Advertisements

CURRENT TRANSFORMERS AND VOLTAGE TRANSFORMERS
INTRODUCTION With this chapter, we begin the discussion of the basic op-amp that forms the cornerstone for linear applications; that is, the signal is.
ECE Electric Drives Topic 6: Voltage-Fed Converters Spring 2004.
ENERGY CONVERSION ONE (Course 25741)
Power System Fundamentals
Voltage-Series Feedback
Chapter 4 Synchronous Generators
SYNCHRONOUS MACHINES SUBMITTED BY: Ms. APOORVA KANTHWAL
SYNCHRONOUS GENERATORS
VOLTMETER LOADING EFFECTS
Lecture 8 Power Amplifier (Class A)
Series Resonance ET 242 Circuit Analysis II
TESTING AND COMMISIONING
Combined Selective Systems :-
Transformers.
Problem Solving Part 2 Resonance.
Transformers.
Transformer with open secondary.
Part B-3 AMPLIFIERS: Small signal low frequency transistor amplifier circuits: h-parameter representation of a transistor, Analysis of single stage transistor.
Alternating Current Circuits
Single Phase Transformer
1.6 Real Single-Phase Transformer.
Instrument Transformers
Connections of a CT and a PT to supply, load and relay.
EET 103 Transformer Chapter 5 1. A transformer is a device that changes ac electric energy at one voltage level to ac electric energy at another voltage.
Protection of Microgrids Using Differential Relays
Chapter 4 Bipolar Junction Transistors
BASIC ELECTRICAL TECHNOLOGY Chapter 6: Single Phase Transformer
Chapter 2 Transformers Edit by Chi-Shan Yu Electric Machinery.
Chapter 31 Lecture 33: Alternating Current Circuits: II HW 11 (problems): 30.58, 30.65, 30.76, 31.12, 31.26, 31.46, 31.56, Due Friday, Dec 11. Final.
BASIC ELECTRICAL TECHNOLOGY DET 211/3 Chapter 6: Single Phase Transformer (Continued)
Instructor :Kashif Mehmood
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
POWER CIRCUIT & ELECTROMAGNETICS EET 221 Transformer.
Prepared by: Garima Devpriya ( ) Jamila Kharodawala ( ) Megha Sharma ( ) ELECTRONICS DEVICES AND CIRCUITS G.H.Patel.
Transformer A transformer is a static piece of equipment used either for raising or lowering the voltage of an a.c. supply with a corresponding decrease.
Protection of Power Systems
D.C. Machine & Transformer Topic: Instrument Transformer Electrical:-1 presented by: Jill Chauhan ( ) Chirag Agarawal ( )
1 :. Introduction These are special type of transformers used for the measurement of voltage, current, power and energy. As the name suggests, these transformers.
Chapter 14 Series and Parallel AC Circuits. Objectives Become familiar with the characteristics of a series and parallel ac circuit Find the total impedance.
Parul Institute Of Technology Name Of Subject:-Electrical Machines Name Of Faculty:-(1) Suresh Sahoo (2) Yogendra Tiwari E&C 3 rd Sem. Prepaid By :- Sr.No.NameEnrolment.
Power System Protective Relaying-Part One
Power System Protective Relaying-Part Two
MOSFET Basic FET Amplifiers The MOSFET Amplifier
1 ELECTRICAL TECHNOLOGY ERT 105/3 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
Transformers. Single Phase Transformers Principles of Operation – Single Phase.
1. 2 Magnetization Current in a Real transformer Although the output of the transformer is open circuit, there will still be current flow in the primary.
Current Transformer Testing
HNC/D Engineering Science
TRANSFORMERS.
Protection of Power Systems
Lesson 10: Transformer Performance and Operation
CHAPTER 6 SPECIAL TRANSFORMERS Electrical Machines.
BASIC ELECTRICAL TECHNOLOGY DET 211/3
Electric Machine Transformers
GUIDED BY: Prof. Nipa Modi
Transformers. Transformer An A.C. device used to change high voltage low current A.C. into low voltage high current A.C. and vice-versa without changing.
Electromechanical Systems
electronics fundamentals
Energy Conversion and Transport George G. Karady & Keith Holbert
Electrical Engineering Principle DNT 235/3
EE216 Electrical Engineering
Power System Protective Relaying-Part One
EET 503 Power System Protection (Instrument transformer )
Chapter 14.
Alternating Current Circuits
PRACTICAL TRANSFORMER
Electrical Machines (EELE 3351)
Presentation transcript:

Part Three – Relay Input Sources Wei-Jen Lee, Ph.D., PE Professor of Electrical Engineering Dept. The Univ. of Texas at Arlington

Introduction Protective relays require reasonably accurate reproduction of the normal, tolerable, and intolerable conditions in the power system fro correct sensing and operation. This information input from the power system is usually through current and voltage transformers. Some exceptions, such as temperature and vibration relays, which receive their information from other type of transducers.

Introduction

Introduction

Introduction

Equivalent Diagram for Instrument Transformers

Current Transformers Typical CT ratio 50:5 100:5 150:5 200:5 250:5 300:5 400:5 450:5 500:5 600:5 800:5 900:5 1000:5 1200:5 1500:5 1600:5 2000:5 2400:5 2500:5 3000:5 3200:5 4000:5 5000:5 6000:5

Current Transformers Current transformer performance on a symmetrical AC component If the CT does not saturate, it is reasonable to assume that Ie is negligible. However, the CT excitation current is never equal to zero. Thus, it must be checked to assure that it does not cause intolerable errors. This can be done by one of the three methods: 1) classic transformer formula, 2) CT performance curves, or 3) ANSI/IEEE accuracy classes for relaying.

Current Transformers Current transformer performance check Classic analysis The load of the CT consists of secondary resistance Rs, the impedance of he connecting leads Zld, and the equipment (relays and such) Zr. The voltage required by the burden (load) is

Current Transformers Current transformer performance check CT characteristic curves The calculation of the performance with the equivalent circuit of Fig. 5.6a is difficult. ANSI/IEEE (C53.71) classifies CTs that have significant leakage flux within the transformer core as class T (class H before 1968) The class C (class L before 1968) is CTs constructed to minimize the leakage flux in the core that can represented by the Fig. 5.6b.

Current Transformers Current transformer performance check CT characteristic curves The knee or effective point of saturation is defined by ANSI/IEEE standard as the intersection of the curve with 45o tangent line. However, the IEC defines the knee as the intersection of straight lines extended from the nonsaturated and saturated parts of the exciting curve. The IEC knee is higher voltage than the ANSO curve.

Current Transformers Current transformer performance check CT characteristic curves - Typical overcurrent ratio curve for class T CT

Current Transformers Current transformer performance check CT characteristic curves - Typical excitation curves for a multiratio class C CT

Current Transformers Current transformer performance check ANSI/IEEE standard accuracy class In many applications, the use of ANSI/IEEE accuracy class designation is adequate to assure satisfactory relay performance. Manufacturer’s test curves must be used for Class T CTs. For class C, the designations are followed by a number indicating the secondary terminal voltage (Vgh) that the transformer can deliver to a standard burden at 20 times the rated secondary current without exceeding the 10% ratio correction.

Current Transformers Current transformer performance check ANSI/IEEE standard accuracy class

Current Transformers Current transformer performance check ANSI/IEEE standard accuracy class For relaying, the voltage classes are 100, 200, 400, and 800, corresponding to standard burdens of B-1, B-2, B-4, and B-8, respectively. These burdens are at 0.5 power factor. If the current is lower, the burden can be higher in proportion. The lower voltage classes of 10, 20, and 50 with standard burdens of B-0.1, B-0.2, and B-0.5 at 0.9 power factor are primary for metering service and should be used very cautiously for protection.

Current Transformers Current transformer performance Two similar CTs connected in the primary circuit, with the same ratio and their secondaries in series, will increase the accuracy capability. Two similar CTs, with their secondaries in parallel, provides an overall lower ratio with higher-ratio individual CTs and their correspondingly higher accuracy rating.

Current Transformers Current transformer performance ANSI classification does not provide actual value of error. Also, the accuracy class only applies to the full winding and reduces proportionally when lower taps are available and used.

Current Transformers Current transformer performance IEC specifies the accuracy of the current transformers as: XX VA Class YY P ZZ where XX: Continuous VA (2.5, 5, 10, 15, and 30) YY: Accuracy class (5 and 10%) P: For protection ZZ: Accuracy limit factor (5, 10, 15, 20, and 30) Rated secondary amperes: 1, 2, and 5 A

Current Transformers Secondary burdens during faults

Current Transformers Secondary burdens during faults

Current Transformers Secondary burdens during faults

Current Transformers CT selection and performance evaluation for phase faults Assumption Imax load = 90A, Imax fault= 2500A, and Imin. fault = 350A. CT ratio selection The conventional practice, over many years, has been that the secondary current should be just under 5A for the maximum load. Therefore, select CT ratio of 100/5 in this case.

Current Transformers CT selection and performance evaluation for phase faults Select relay tap for the phase-overcurrent relay The tap should be higher than 4.5 A Small tap 5 is selected Minimum fault of 350/20=17.5 A, and 17.5/5=3.5 times the minimum relay pick up. This is desirable for any possible fault restriction. If tap 6 is selected, then the margin above the load is greater (6/4.5=1.33), but a smaller margin (17.5/6=2.9) above the relay pick up.

Current Transformers CT selection and performance evaluation for phase faults Determine the total secondary burden The total connected secondary load determination must include all of the impedance between the CTs and the equipment in the phase circuit. Assume tap 5 is used and the burden is 2.64 VA at 5A and 580 VA at 20X. Also, the lead from the CT to relay is 0.4W. The total secondary impedance at pick up: Relay burden 2.64/52 = 0.106W Lead resistance = 0.40W Total impedance to CT terminals = 0.506W at 5A

Current Transformers CT selection and performance evaluation for phase faults Determine the total secondary burden The total secondary impedance at 20X: Relay burden 580/1002 = 0.058W Lead resistance = 0.40W Total impedance to CT terminals = 0.458W at 100A It is frequently practical to add the burden impedance and the current algebraically (they should be combined phasorally) Burdens are generally near unity power factor; hence Is tends to be near unity power factor. Ie (the excitation current) is around 90o lagging. Combine Is and Ie at right angle is a good approximation.

Current Transformers CT selection and performance evaluation for phase faults Determine the CT performance When using a class T CT Use the provided curves. Use actual relay burden (0.506 or 0.458 in this case) When using a class C CT and performance by ANSI/IEEE standard If a 600/5 multiratio CT with C100 rating is selected. Vgh = (2500/20)*0.458 = 57.25 V The C100 600/5 CT on the 100/5 tap can only develop, Vgh = (100/600)*100 = 16.67 V This is not a good selection

Current Transformers CT selection and performance evaluation for phase faults Determine the CT performance When using a class C CT and performance by ANSI/IEEE standard An alternative is to use the 400/5 tap on the 600/5 C100 CT. The secondary CT current at maximum load is (90/80=1.125A) Tap 1.5 is selected. Assume the relay burden at 100 A is 1.56W. Total CT burden is equal to 1.96W (1.56W+0.40W) Vgh = (2500/80)*1.96=61.25 V The CT capability on the 400/5 tap is Vgh = (400/600)*100 = 66.7 V

Current Transformers CT selection and performance evaluation for phase faults Determine the CT performance When using a class C CT and performance with CT excitation curve

Current Transformers CT selection and performance evaluation for phase faults Determine the CT performance When using a class C CT and performance with CT excitation curve An alternative is to use the 400/5 tap on the 600/5 C100 CT. The CT secondary resistance is 0.211W (Check figure) Total impedance to excitation point ef.= 2.171W The 1.5 A to develop voltage in the relay is Vef = 1.5 * 2.171 = 3.26 V Ie = 0.024 A The pick up current is either120 or 122.92 A, which is much smaller than 350 A.

Current Transformers CT selection and performance evaluation for phase faults Determine the CT performance When using a class C CT and performance with CT excitation curve For maximum fault current Vef = (2500/80)*2.171 = 67.84 Ie = 0.16 A Although this is near the knee of the saturation curve, the excitation current does not significantly decrease the fault current to the relay.

Current Transformers Performance evaluation for ground relays

Current Transformers Effect of unenergized CTs on performance

Current Transformers Effect of unenergized CTs on performance Fault happens at phase A. Unfaulted CTs do not have current. Assumption: 100:5 tap of a C100, 600:5 multiratio CT is used. The secondary resistance of the CT, the leads, and the phase relay is 0.63 W. The ground relay has 16 W on its 0.5A tap at 68o lag. 8 V (0.5A*16 W) will be established at the ground relay. This voltage, less the small drop through the phase relay circuit, will appear across the secondary of the CTs at phase B & C

Current Transformers Effect of unenergized CTs on performance It will have 0.38A flows through Ze of the Phase B & C CTs. The current at phase A CT secondary terminal is 1.26 A or 1.24 A. The exciting current of phase A CT is 0.41 A It requires 33.4 A ((0.41+1.26)*20) primary current to pick up the ground relay. Only 10 A primary current required to pick up the ground relay if the exciting currents were neglected.

Current Transformers Effect of unenergized CTs on performance

Current Transformers Flux summation

Current Transformers CT performance on the DC component

Current Transformers Saturation on Symmetrical AC current input

Current Transformers Saturation by the DC offset of the Primary AC current

Voltage Transformers Voltage Transformer (VT) or Capacitor Coupled Voltage Transformer (CCVT) Typical output voltage is 120 V line-to-line or 69.3 V per phase.

Voltage Transformers Typical VT ratio 1:1 2:1 2.5:1 4:1 5:1 20:1 40:1 60:1 100:1 200:1 300:1 400:1 600:1 800:1 1000:1 2000:1 3000:1 4500:1

Voltage Transformers Internal configuration of CCVT

New Development Low signal level optical CT Hall Effect current transducer