FIRE SERVICES AT DATA CENTRE

Similar presentations


Presentation on theme: "FIRE SERVICES AT DATA CENTRE"— Presentation transcript:

1 FIRE SERVICES AT DATA CENTRE

2 FM200 TRAINING COURSE

3 Introduction of FM 200

4 THE PROPERTIES OF FM-200®

5 ASHRAE Designation = HFC227ea
WHAT IS FM-200® ? C F H ASHRAE Designation = HFC227ea

6 THE PHYSICS OF FIRE Fire Triangle Fuel, oxygen, heat What is fire?
A series of highly exothermic chain-branching free radical reactions Removal of any element of fire triangle results in suppression

7 Fast & Efficient Performance
Removes heat, so fire can’t sustain itself

8 FM-200® CHEMICAL/PHYSICAL EXTINGUISHING MECHANISM
80% 20% Halon 1301 FM-200®

9 How is FM-200® Applied? Cup Burner Conc. [Heptane] - 5.8%
Use Concentration [Minimum] - 7.5% for ISO compliance Maximum Discharge Time limited to 10 Seconds

10 FAST & EFFICIENT PERFORMANCE
Compact storage space requirements Halon 1301 CO Inert Gas

11 HUMAN SAFETY FM-200® is completely safe for use in occupied spaces.

12 FM-200® IS FAST & EFFECTIVE
Reaches extinguishing concentration within 10 seconds Provides ACTIVE Fire Protection FM-200® IS FAST & EFFECTIVE

13 FM-200® ENGINEERED SYSTEMS

14 ENGINEERED CENTRAL STORAGE FM-200® SYSTEM
Distribution Pipe Smoke Detectors Discharge Nozzles Containers Manual Station Raised Floor

15 PRIMARY APPLICATIONS Computer Rooms

16 3M™ Novec™ 1230 Fire Protection Fluid
Novec 1230 fluid has distinct environmental benefits Ozone depletion potential (ODP) of 0 5 day atmospheric lifetime Global Warming Potential (GWP) of 1 THE NEW CLEAN AGENT

17 FM200 CONTROL EQUIPMENT

18 FM200 CONTROL EQUIPMENT Kentec Panel Kentec lock off

19 FM200 CONTROL EQUIPMENT Kidde Panel Kidde Panel

20 Viking & Notifier Panel
FM200 CONTROL EQUIPMENT Chubb Panel Viking & Notifier Panel

21 FM200 CONTROL EQUIPMENT Thorn Panel

22 FM200 CYLINDER

23 FM200 CYLINDER Kidde FM200

24 FM200 CYLINDER Chemetron FM200

25 FM200 CYLINDER ThornFM200

26 FM200 CYLINDER Fike FM200

27 FM200 CYLINDER Siemens FM200

28 Signage Box and Pressure Switch
Pressure Switch for Fed-back Signal

29 Mode Selection - “System Inoperative” Signal Box Flash
AUTO-MANUAL Mode Selection Provided Next to the Panel Outside the Room When Personal Before Enter the Room: - Switch the Auto-Manual Switch to “MANUAL” - “System Inoperative” Signal Box Flash - Switch Back to “AUTO” when Leave the Room

30 FM200 Operation In Auto Mode
Two Detection Zones for Each System Cross Zone Operation Activating Anyone Zone: - Alarm Sound - “Do Not Enter” Sign Flash, Don’t Enter the Room

31 FM200 Operation in Auto Mode
Two Zones Activated: - Two-Tone Sounder Raised - “Evacuate” Sign Flash, Evacuate Room Immediately - A/C in the Room Will Shunt Down - System Start Count Down for 30 Sec. - Gas Discharge to Room After Count Down

32 FM200 System Operation in Manual Mode
When Personal Working inside the Room: One Zone of Alarm Activated and Alarm Sound: - Check Any Fire Happened in Room - Inform Others to Leave the Room if Fire Happened - Go out of the Room, Push the “Manual Release” Switch to Discharge Gas Two Zone Activated: - Evacuate Room Immediately

33 MAINTENANCE OF AFA AND FM200 SYSTEMS
Check Smoke Detectors - Corrosion - Dirty - Generate False Alarm Frequently Check Modules - Simulate Tests to Check the Modules Working Properly

34 MAINTENANCE Monthly & Annual - To Be Carried-Out By FS Contractor

35 Introduction of VESDA system
What is VESDA… Aspirating Smoke Detection 吸气式烟雾探测

36 THEINTRODUCTION OF VESDA SYSTEM VESDA ADVANTAGE…

37 Introduction of VESDA system
VESDA Panel VESDA Panel

38 Introduction of HSSD system
Kidde HSSD Panel Kidde HSSD Panel 主機板 鐳射探測器 風機

39 Introduction of HSSD system
Kidde HSSD Sampling Point

40 Introduction of Pre-action system

41 Introduction of Pre-action system

42 THANK YOU