Download presentation
Presentation is loading. Please wait.
Published byErnest Cox Modified over 8 years ago
1
ACS Annunciators
2
EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet
3
Control Button CONTROL for: - SLC Relay - NAC Control Modules - Speaker Circuits - Software Zones ACM-24AT and ACM-48A ACM-24AT - Visual Indication ONLY ACM-48A
4
Rear View
5
Address Wheels NFS-320 / NFS2-640 MAP NFS2-3030 / NCA-2 MAP
6
Keylock Switch Key Lock Connection
7
Dip Switches
8
Receive & Transmit LED’s
9
End of Line Resistor
10
24V Power Connection
11
ACS Connection
12
EIA-485 CircuitsPower Circuits RETROFIT CONSIDERATIONS
13
- A 64 point map exceeds physical points on an annunciator - So we add an expander ACM-24ATAEM-24AT Address Expansion Note the difference in device population
14
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 NOTUSEDNOTUSED ACM-24AT AEM-24AT Set Address Intelligence resides on board Expansion annunciators connect to communication bus and receive information through host ACM ACM-24AT with 64-Point Limit
15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ACM-48A Set Address Intelligence resides on board AEM-48A Expansion annunciators connect to communication bus and receive information through host ACM 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 NOTUSEDNOTUSED NOTUSEDNOTUSEDNOTUSEDNOTUSED ACM-48A with 64-Point Limit
16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 ACM-24AT AEM-24AT Set Address Intelligence resides on board Expansion annunciators connect to communication bus and receive information through host ACM ACM-24AT with 96-Point Limit 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 AEM-24AT
17
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ACM-48A Set Address Intelligence resides on board AEM-48A Expansion annunciators connect to communication bus and receive information through host ACM 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 ACM-48A with 96-Point Limit
18
DOORS
19
CABINETRY
20
Address Wheel Relationship NFS-320 / NFS2-640 MAP 16
21
MAP Assignment
22
SETUP in the NFS-320 and NFS2-640 Pre-defined Maps: ACS GroupAnnunciator Display A 8 System points & Zones 1 – 56 B Zones 57 - 99, 9 F Zones, 8 R Zones, 4 NACs C Loop 1, Modules 1 – 64 D Loop 2, Modules 1 – 64 E Loop 1, Modules 65 – 128 F Loop 2, Modules 65 – 128 G Loop 1, Modules 129 - 159 (1 unused point) Loop 2, Modules 129 - 159 (1 unused point) H Loop 1, Detectors 1 – 64 I Loop 2, Detectors 1 – 64 J Loop 1, Detectors 65 – 128 K Loop 2, Detectors 65 – 128 L Loop 1, Detectors 129 - 159 (1 unused point) Loop 2, Detectors 129 - 159 (1 unused point) M For use with FireVoice NFV-25/50ZS N 8 System Points & Zones 1-56 O MAP A 8 System points & Zones 1 – 56 Points 11 – 62 Zones 3 thru 54 SYSTEM POINTS
23
POINTTYPERED LEDYELLOW LEDSWITCH FUNCTION* 1InputSystem AlarmSystem TroubleAcknowledge 2OutputNot UsedSignal SilencedAlarm Silence 3OutputNot UsedProgram ModeSystem Reset 4OutputNot UsedSupervisoryDrill 5OutputNAC #1 ActiveNAC TroubleControl NAC #1 6InputSecurityP/A Maint AlertNot Used 7InputNot UsedLow BatteryNot Used 8InputNot UsedAC FailNot Used * Pressing the switch button when the Switch Function is "Not Used" causes the associated LED to stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel. SYSTEM POINTS
24
Pre-defined and USER Maps ACS GroupAnnunciator Display A 8 System points & Zones 1 – 56 B Zones 57 - 99, 9 F Zones, 8 R Zones, 4 NACs C Loop 1, Modules 1 – 64 D Loop 2, Modules 1 – 64 E Loop 1, Modules 65 – 128 F Loop 2, Modules 65 – 128 G Loop 1, Modules 129 - 159 (1 unused point) Loop 2, Modules 129 - 159 (1 unused point) H Loop 1, Detectors 1 – 64 I Loop 2, Detectors 1 – 64 J Loop 1, Detectors 65 – 128 K Loop 2, Detectors 65 – 128 L Loop 1, Detectors 129 - 159 (1 unused point) Loop 2, Detectors 129 - 159 (1 unused point) M For use with FireVoice NFV-25/50ZS N 8 System Points & Zones 1-56 O 1 – 10 USER-DEFINED MAPS
25
SETUP in the NFS-320 and NFS2-640 ACS GroupAnnunciator Display 1 Programmable Annunciator #1 2 Programmable Annunciator #2 3 Programmable Annunciator #3 4 Programmable Annunciator #4 5 Programmable Annunciator #5 6 Programmable Annunciator #6 7 Programmable Annunciator #7 8 Programmable Annunciator #8 9 Programmable Annunciator #9 10 Programmable Annunciator #10
26
User Defined Maps
27
User Map Programming Select User Map #1
28
User Map Programming Select a point TYPE
29
User Map Programming When you choose the point, installed points appear
30
User Map Programming Selecting the point will install it on the map
31
User Map Programming You must decide what to DO with the point
32
User Map Programming Monitor/Control or Enable/Disable
33
User Map Programming Select MODIFY to install the point
34
Final ACS Addressing When the User-Defined map is saved, it will appear in the list
35
CLICK ACS1 Final ACS Addressing When it’s added, ACS 1 is highlighted providing a quick-link
36
Final ACS Addressing The quick-link brings you back to the User Map
37
ACS Map in VeriFire Tools NFS-320 / NFS2-640 MAP
38
Questions