IEEE T&D – Insulators 101 Insulators 101 Section A – Introduction Presented by Andy Schwalm IEEE Chairman, Lightning and Insulator Subcommittee IEEE/PES.

Similar presentations


Presentation on theme: "IEEE T&D – Insulators 101 Insulators 101 Section A – Introduction Presented by Andy Schwalm IEEE Chairman, Lightning and Insulator Subcommittee IEEE/PES."— Presentation transcript:

1 IEEE T&D – Insulators 101 Insulators 101 Section A – Introduction Presented by Andy Schwalm IEEE Chairman, Lightning and Insulator Subcommittee IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010

2 IEEE T&D – Insulators 101 What Is an Insulator? An insulator is a dam*** poor conductor! And more, technically speaking! An insulator is a mechanical support! Primary function - support the line mechanically Secondary function– electrical Air is the insulator Outer shells/surfaces are designed to increase leakage distance and strike distance

3 IEEE T&D – Insulators 101 What Does an Insulator Do? Maintains an Air Gap Separates Line from Ground length of air gap depends primarily on system voltage, modified by desired safety margin, contamination, etc. Resists Mechanical Stresses everyday loads, extreme loads Resists Electrical Stresses system voltage/fields, overvoltages Resists Environmental Stresses heat, cold, UV, contamination, etc.

4 IEEE T&D – Insulators 101 Where Did Insulators Come From? Basically grew out of the needs of the telegraph industry – starting in the late 1700s, early 1800s Early history centers around what today we would consider very low DC voltages Gradually technical needs increased as AC voltages grew with the development of the electric power industry

5 IEEE T&D – Insulators 101 History Glass plates used to insulate telegraph line DC to Baltimore Glass insulators became the norm soon thereafter – typical collectors items today Many, many trials with different materials – wood – cement – porcelain - beeswax soaked rag wrapped around the wire, etc. Ultimately porcelain and glass prevailed

6 IEEE T&D – Insulators 101 History Wet process porcelain developed for high voltage applications Porcelain insulator industry started Application voltages increased Insulator designs became larger, more complex Ceramics (porcelain, glass) still only choices at high voltages

7 IEEE T&D – Insulators 101 History US trials of first NCIs – cycloaliphatic based Not successful, but others soon became interested and a new industry started up Europeans develop modern style NCI – fiberglass rod with various polymeric sheds Now considered First generation

8 IEEE T&D – Insulators 101 History NCI insulator industry really begins in US with field trials of insulators Since that time - new manufacturers, new designs, new materials NCIs at generation X – there have been so many improvements in materials, end fitting designs, etc. Change in materials have meant changes in line design practices, maintenance practices, etc. Ceramic manufacturers have not been idle either with development of higher strength porcelains, RG glazes, etc.

9 IEEE T&D – Insulators 101 History Domestic manufacturing of insulators decreases, shift to offshore (all types) Engineers need to develop knowledge and skills necessary to evaluate and compare suppliers and products from many different countries An understanding of the basics of insulator manufacturing, design and application is more essential than ever before

10 IEEE T&D – Insulators 101 Insulator Types For simplicity will discuss in terms of three broad applications: Distribution lines (thru 69 kV) Transmission lines (69 kV and up) Substations (all voltages)

11 IEEE T&D – Insulators 101 Insulator Types Distribution lines Pin type insulators -mainly porcelain, growing use of polymeric (HDPE – high density polyethylene), limited use of glass (in US at least) Line post insulators – porcelain, polymeric Dead end insulators – polymeric, porcelain, glass Spool insulators – porcelain, polymeric Strain insulators, polymeric, porcelain

12 IEEE T&D – Insulators 101 Types of Insulators – Distribution

13 IEEE T&D – Insulators 101 Insulator Types Transmission lines Suspension insulators - new installations mainly NCIs, porcelain and glass now used less frequently Line post insulators – mainly NCIs for new lines and installations, porcelain much less frequent now

14 IEEE T&D – Insulators 101 Types of Insulators – Transmission

15 IEEE T&D – Insulators 101 Insulator Types Substations Post insulators – porcelain primarily, NCIs growing in use at lower voltages (~161 kV and below) Suspension insulators –NCIs (primarily), ceramic Cap and Pin insulators – legacy type

16 IEEE T&D – Insulators 101 Types of Insulators – Substation

17 IEEE T&D – Insulators 101 Insulator Types - Comparisons Ceramic Porcelain or toughened glass Metal components fixed with cement ANSI Standards C29.1 through C29.10 Non Ceramic Typically fiberglass rod with rubber (EPDM or Silicone) sheath and weather sheds HDPE line insulator applications Cycloaliphatic (epoxies) station applications, some line applications Metal components normally crimped ANSI Standards C29.11 – C29.19

18 IEEE T&D – Insulators 101 Insulator Types - Comparisons Ceramic Materials very resistant to UV, contaminant degradation, electric field degradation Materials strong in compression, weaker in tension High modulus of elasticity - stiff Brittle, require more careful handling Heavier than NCIs Non Ceramic Hydrophobic materials improve contamination performance Strong in tension, weaker in compression Deflection under load can be an issue Lighter – easier to handle Electric field stresses must be considered

19 IEEE T&D – Insulators 101 Insulator Types - Comparisons Ceramic Generally designs are mature Limited flexibility of dimensions Process limitations on sizes and shapes Applications/handling methods generally well understood Non Ceramic Material properties have been improved – UV resistance much improved for example Standardized product lines now exist Balancing act - leakage distance/field stress – take advantage of hydrophobicity Application parameters still being developed Line design implications (lighter weight, improved shock resistance)

20 IEEE T&D – Insulators 101 Insulators 101 Section B - Design Criteria Presented by Al Bernstorf IEEE Chairman, Insulator Working Group IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010 Insulators 101 Section B - Design Criteria Presented by Al Bernstorf IEEE Chairman, Insulator Working Group IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010

21 IEEE T&D – Insulators 101 Design Criteria - Mechanical An insulator is a mechanical support! Its primary function is to support the line mechanically Electrical Characteristics are an afterthought. Will the insulator support your line? Determine The Maximum Load the Insulator Will Ever See Including NESC Overload Factors.

22 IEEE T&D – Insulators 101 Design Criteria - Mechanical Suspension Insulators Porcelain -M&E (Mechanical & Electrical) Rating Represents a mechanical test of the unit while energized. When the porcelain begins to crack, it electrically punctures. Average ultimate strength will exceed the M&E Rating when new. -Never Exceed 50% of the M&E Rating NCIs (Polymer Insulators) -S.M.L. – Specified Mechanical Load Guaranteed minimum ultimate strength when new. R.T.L. – Routine Test Load – Proof test applied to each NCI. -Never Load beyond the R.T.L.

23 IEEE T&D – Insulators 101 Design Criteria - Mechanical Line Post insulators Porcelain -Cantilever Rating Represents the Average Ultimate Strength in Cantilever – when new. Minimum Ultimate Cantilever of a single unit may be as low as 85%. -Never Exceed 40% of the Cantilever Rating – Proof Test Load NCIs (Polymer Insulators) -S.C.L. (Specified Cantilever Load) Not based upon lot testing Based upon manufacturer testing -R.C.L. (Rated Cantilever Load) or MDC or MDCL (Maximum Design Cantilever Load) or MCWL or WCL (Working Cantilever Load) -Never Exceed RCL or MDC or MDCL or MCWL or WCL -S.T.L. (Specified Tensile Load) -Tensile Proof Test=(STL/2)

24 IEEE T&D – Insulators 101 Design Criteria - Mechanical Other Considerations Suspensions and Deadends – Only apply tension loads Line Posts – -Cantilever is only one load -Transverse (tension or compression) on line post – loading transverse to the direction of the line. -Longitudinal – in the direction of travel of the line -Combined Loading Curve – Contour curves representing various Longitudinal loads Available Vertical load as a function of Transverse loading Manufacturers have different safety factors!!!

25 IEEE T&D – Insulators 101 Design Criteria - Mechanical

26 IEEE T&D – Insulators 101 Design Criteria - Electrical An Insulator is a mechanical support! Air imparts Electrical Characteristics Strike Distance (Dry Arcing Distance) is the principal constituent to electrical values. Dry 60 Hz F/O and Impulse F/O – based on strike distance. Wet 60 Hz F/O -Some would argue leakage distance as a principal factor. -At the extremes that argument fails – although it does play a role. -Leakage distance helps to maintain the surface resistance of the strike distance. Leakage Requirements do play a role!!!

27 IEEE T&D – Insulators 101 Design Criteria - Electrical Dry Arcing Distance – (Strike Distance) – The shortest distance through the surrounding medium between terminal electrodes…. 1 1 – IEEE Std 100 - 1992

28 IEEE T&D – Insulators 101 Design Criteria - Electrical Define peak l-g kV Determine Leakage Distance Required Switching Over-voltage Requirements Impulse Over-voltage Chart Courtesy of Ohio Brass/HPS – EU1429-H

29 IEEE T&D – Insulators 101 Design Criteria – Leakage Distance What is Leakage Distance? The sum of the shortest distances measured along the insulating surfaces between the conductive parts, as arranged for dry flashover test. 1 1 – IEEE Std 100 - 1992

30 IEEE T&D – Insulators 101 Design Criteria - Electrical Whats an appropriate Leakage Distance? Empirical Determination -Whats been used successfully? -If Flashovers occur – add more leak? ESDD (Equivalent Salt Deposit Density) Determination -Measure ESDD Pollution Monitors Dummy Insulators Remove in-service insulators -Evaluate ESDD and select appropriate Leakage Distance

31 IEEE T&D – Insulators 101 Design Criteria - Electrical Application Guide for Insulators in a Contaminated Environment by K. C. Holte et al – F77 639-8 ESDD (mg/cm 2 )Site Severity Leakage Distance I-string/V-string (/kV l-g) 0 – 0.03Very Light0.94/0.8 0.03 – 0.06Light1.18/0.97 0.06 – 0.1Moderate1.34/1.05 >0.1Heavy1.59/1.19

32 IEEE T&D – Insulators 101 Design Criteria - Electrical IEC 60815 Standards ESDD (mg/cm 2 )Site Severity Leakage Distance (/kV l-g) <0.01Very Light0.87 0.01 – 0.04Light1.09 0.04 – 0.15Medium1.37 0.15 – 0.40Heavy1.70 >0.40Very Heavy2.11

33 IEEE T&D – Insulators 101 Design Criteria - Electrical

34 IEEE T&D – Insulators 101 Improved Contamination Performance

35 IEEE T&D – Insulators 101 Improved Contamination Performance Polymer insulators offer better contamination flashover performance than porcelain? Smaller core and weathershed diameter increase leakage current density. Higher leakage current density means more Ohmic Heating. Ohmic Heating helps to dry the contaminant layer and reduce leakage currents. In addition, hydrophobicity helps to minimize filming

36 IEEE T&D – Insulators 101 Improved Contamination Performance the contamination performance of composite insulators exceeds that of their porcelain counterparts the contamination flashover performance of silicone insulators exceeds that of EPDM units the V 50 of polymer insulators increases in proportion to the leakage distance CEA 280 T 621, Leakage Distance Requirements for Composite Insulators Designed for Transmission Lines

37 IEEE T&D – Insulators 101 Insulator Selection Where do I get these values? Leakage Distance or Creepage Distance Manufacturers Catalog Switching Surge Wet W/S ((Wet Switching Surge W/S)/2) 60 Hz Wet Flashover (r.m.s.) Peak Wet 60 Hz value will be lower than Switching Surge Wet W/S Impulse Withstand Take Positive or Negative Polarity, whichever is lower If only Critical Impulse Flashover is available – assume 90% (safe estimate for withstand)

38 IEEE T&D – Insulators 101 Insulator Selection Select the 69 kV Insulator shown at right. I-string – Mechanical Worst Case – 6,000 lbs Suspension: 12k min ultimate Leakage Distance 42 Switching Surge 125 kV Impulse Withstand 359 kV

39 IEEE T&D – Insulators 101 Insulator Selection Porcelain – 5-3/4 X 10 bells X 4 units CharacteristicRequiredAvailable Leakage Distance 4246 Wet Switching Surge W/S 125 kV240 kV Impulse W/S359 kV374 kV M & E12,000 lbs15,000 lbs

40 IEEE T&D – Insulators 101 Grading Rings Simulate a larger, more spherical object Reduce the gradients associated with the shielded object Reduction in gradients helps to minimize RIV & TVI Porcelain or Glass – Inorganic – breaks down very slowly NCIs Polymers are more susceptible to scissioning due to corona UV – short wavelength range – attacks polymer bonds. Most short wavelength UV is filtered by the environment UV due to corona is not filtered

41 IEEE T&D – Insulators 101 NCIs and Rings Grading (Corona) Rings Due to corona cutting and water droplet corona – NCIs may require the application of rings to grade the field on the polymer material of the weathershed housing. Rings must be: -Properly positioned relative to the end fitting on which they are mounted. -Oriented to provide grading to the polymer material. Consult the manufacturer for appropriate instructions. As a general rule – rings should be over the polymer – brackets should be on the hardware.

42 IEEE T&D – Insulators 101 Questions? Questions?

43 IEEE T&D – Insulators 101 Insulators 101 Section C - Standards Presented by Tony Baker IEEE Task Force Chairman, Insulator Loading IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010

44 IEEE T&D – Insulators 101 American National Standards Consensus standards Standards writing bodies must include representatives from materially affected and interested parties. Public review Anybody may comment. Comments must be evaluated, responded to, and if found to be appropriate, included in the standard. Right to appeal By anyone believing due process lacking. Objective is to ensure that ANS Standards are developed in an environment that is equitable, accessible, and responsive to the requirements of various stakeholders*. * The American National Standards Process, ANSI March 24, 2005

45 IEEE T&D – Insulators 101 American Standards Committee on Insulators for Electric Power Lines ASC C-29 EL&P Group IEEE NEMA Independents

46 IEEE T&D – Insulators 101 C29ANSI C29 Insulator Standards (available on-line at nema.org).1Insulator Test Methods.2Wet-process Porcelain & Toughened Glass - Suspensions.3Wet-process Porcelain Insulators - Spool Type.4 - Strain Type.5 - Low & Medium Voltage Pin Type.6 - High Voltage Pin Type.7 - High Voltage Line Post Type.8 - Apparatus, Cap & Pin Type.9 - Apparatus, Post Type.10 - Indoor Apparatus Type.11Composite Insulators – Test Methods.12 - Suspension Type.13 - Distribution Deadend Type.17 - Line Post Type.18 - Distribution Line Post Type.19 - Station Post Type (under development)

47 IEEE T&D – Insulators 101 ANSI C29 Insulator Standards Applies to new insulators Definitions Materials Dimensions & Marking (interchangeability) Tests 1.Prototype & Design, usually performed once for a given design. (design, materials, manufacturing process, and technology). 2.Sample, performed on random samples from lot offered for acceptance. 3.Routine, performed on each insulator to eliminate defects from lot.

48 IEEE T&D – Insulators 101 ANSI C 29 Insulator Standard Ratings Electrical & Mechanical Ratings How are they assigned? How is conformance demonstrated? What are application limits?

49 IEEE T&D – Insulators 101 Electrical Ratings Average flashover values Low-frequency Dry & Wet Critical impulse, positive & negative Impulse withstand Radio-influence voltage Applies to all the types of high voltage insulators Rated values are single-phase line-to-ground voltages. Dry FOV values are function of dry arc distance and test configuration. Wet FOV values function of dry arc distance and insulator shape, leakage distance, material and test configuration. Tests are conducted in accordance with IEEE STD 4-1995 except test values are corrected to standard conditions in ANSI C29.1. - Temperature 25 ° C - Barometric Pressure 29.92 ins. of Hg - Vapor Pressure 0.6085 ins. of Hg - For wet tests: rate 5 ± 0.5 mm/min, resistivity 178 ± 27 Ωm, 10 sec. ws

50 IEEE T&D – Insulators 101 Dry Arcing Distance Shortest distance through the surrounding medium between terminal electrodes, or the sum of distances between intermediate electrodes, whichever is shortest, with the insulator mounted for dry flashover test. Dry Arcing Distance Shortest distance through the surrounding medium between terminal electrodes, or the sum of distances between intermediate electrodes, whichever is shortest, with the insulator mounted for dry flashover test.

51 IEEE T&D – Insulators 101 Electrical Ratings Product is designed to have a specified average flashover. This is the manufacturers rated value, R. Samples are electrically tested in accordance with standard This is the tested value, T. Due to uncontrollable elements during the test such as atmospheric fluctuations, minor differences in test configuration, water spray fluctuations, etc. the test value can be less than the rated value. Does T satisfy the requirements for the rating R? If T/R Yes where = 0.95 for Low-frequency Dry flashover tests = 0.90 for Low-frequency Wet flashover tests = 0.92 for Impulse flashover tests

52 IEEE T&D – Insulators 101 Electrical Ratings

53 IEEE T&D – Insulators 101 Electrical Ratings ANSI C2 Insulation Level Requirements ANSI C2-2007, Table 273-1 Electrical Ratings ANSI C2 Insulation Level Requirements ANSI C2-2007, Table 273-1 Higher insulation levels required in areas where severe lightning, high atmospheric contamination, or other unfavorable conditions exist

54 IEEE T&D – Insulators 101 Electrical Ratings - Application Customer determines needs and specifies electrical requirements: -60 Hz Dry & wet flashover -Impulse flashover and/or withstand -Leakage distance Does offered product meet customers specification S? If R S and T R yes, otherwise no. IEEE T&D – Insulators 101

55 Mechanical Ratings Sample & Routine Mechanical Tests are based on the primary in-service loading conditions STD. No.Insulator TypeSample test Routine test C 29.2Ceramic SuspensionM&ETension C29.6 Pin TypeCantilever----- C29.7 Line PostCantilever4 quad. cantilever C29.8 Cap & PinCantilever Torsion Tension C29.9 Station PostCantilever Tension Tension, Cantilever or Bending Moment C29.12Composite SuspensionSMLTension C29.13 DeadendSMLTension C29.17 Line PostCantilever Tension C29.18 Dist. Line PostCantileverTension

56 IEEE T&D – Insulators 101 Mechanical Ratings M&E Test Ceramic Suspensions Bending Tests Composite Posts IEEE T&D – Insulators 101 Hubbell Power Systems Kinectrics

57 IEEE T&D – Insulators 101 ANSI C29 High Voltage Insulator Standards Std. No. Insulator Type Ult. Strength QC Test Lot Acceptance Criteria Routine Test C29.2 Ceramic Suspension Combined M&E strength of 10 units Ave. Std. dev. = S X 10 R +1.2 S s 10 1.72 S 3 sec. tension at 50% of R C29.7 Ceramic Line post Cantilever strength of 3 units X 3 R no one x i.85 R 4 quad. bending at 40% of R C29.8 Ceramic Apparatus Cap & Pin Cantilever, tension, & torsion strength of 3 units each X 3 R no one x i.85 R 3 sec. tension at specified value C29.9 Ceramic Apparatus Post Type Cantilever & tension strengths of 3 units each X 3 R no one x i.85 R Tension at 50% of R or 4 quad. bending at 40% of R C29.12 Composite Suspension Specified Mech. Load (SML) test of 3 units x i.R 10 sec. tension at 50% of R C29.13 Composite Distribution Deadend SML test of 3 unitsx i.SML rating 10 sec. tension at 50% of R C29.17 Composite Line Post Cantilever strength of 1 unit Tension test of 1 unit Strength R 10 sec. tension at 50% of R C29.18Composite Distribution Line Post Cantilever strength of 1 unitStrength R10 sec. tension at 50% of R

58 IEEE T&D – Insulators 101 Lot Acceptance Criteria – ANSI C29.2 Lot acceptance according to ANSI C 29.2. Select ten random units from lot and subject to M&E test. Requirements are: M&E rating X 10 -1.2S H & s 10 1.72S H s 10 is std. dev. of the 10 units S H is historical std. dev. If s 10 = S H then for minimally acceptable lot, ~ 11.5% of units in lot could have strengths below the rated value. IEEE T&D – Insulators 101

59 Lot Acceptance Criteria – ANSI C29.2 Possible low strengths for ceramic suspension units in a lot minimally acceptable according to ANSI C29.2 Coefficient of variation, v R Strength value at -3 σ 5%90% of M&E rating 10%79% of M&E rating 15%67% of M&E rating IEEE T&D – Insulators 101

60 Lot Acceptance Criteria – CSA C411.1 Possible low strengths for ceramic suspension units in a lot minimally acceptable according to CSA C411.1 Requirements Rating X S – 3s & X i R On a -3 sigma basis, minimum strength that could be expected in a lot is the rated value regardless of the coefficient of variation for the manufacturing process that produced the lot. IEEE T&D – Insulators 101

61 Lot Acceptance Criteria – ANSI C29 Possible low strengths for ceramic units in a lot minimally acceptable according to ANSI C29.7, C29.8 & C29.9 Cantilever rating X 3 & no x i < 85% of rating Coefficient of variation, v R Strength value at -3 σ 5%85% of Cantilever rating 10%70% of Cantilever rating 15%55% of Cantilever rating IEEE T&D – Insulators 101

62 Lot Acceptance Criteria ANSI C29 –Composite Insulators Random samples selected from an offered lot. Ultimate strength tests on samples. Requirement is: x i Rating The rated value is assigned by the manufacturer based on ultimate strength tests during design. However for a lot minimally acceptable according to the standard, statistical inference for the strength distribution for entire lot not possible. Composite Insulators have a well defined damage limit providing good application direction. IEEE T&D – Insulators 101

63 Mechanical Ratings – Application Limits NESC ANSI C Table 277-1 Allowed percentages of strength ratings Insulator Type%Strength RatingRef. ANSI Std. Ceramic Suspension 50% Combined mechanical & electrical strength (M&E) C29.2-1992 Line Post 40% 50% Cantilever strength Tension/compression strength C29.7-1996 Station Post 4 40% 50% Cantilever strength Tension/compression/torsion strengthC29.9-1983 Station Cap & Pin 40% 50% Cantilever strength Tension/compression/torsion strengthC29.8-1985 Composite Suspension 50%Specified mechanical load (SML) C29.12-1997 C29.13-2000 Line Post50% Specified cantilever load (SCL) or specified tension load (STL) C29.17-2002 C29.18-2003 Station Post50%All strength ratings ----------

64 IEEE T&D – Insulators 101 Mechanical Ratings – Application Limits Worst loading case load (% Table 277-1)(Insulator Rating) In most cases, % from Table 277-1 is equal to the routine proof -test load. Bending tests on a production basis are not practicable in some cases, (large stacking posts, cap & pins, and polymer posts) and tension proof-load tests are specified. IEEE T&D – Insulators 101

65 Mechanical Ratings – Application Limits Composite Post Insulators – Combined Loading IEEE T&D – Insulators 101

66 Mechanical Ratings – Application Limits Composite Post Insulators – Combined Loading IEEE T&D – Insulators 101

67 Recent Developments for Application Limits Component strength cumulative distribution function F R and probability density function of maximum loads f Q. IEEE T&D – Insulators 101

68 Component Damage Limit DAMAGE LIMIT Strength of a component below ultimate corresponding to a defined limit of permanent damage or deformation. For composites the damage limit is fairly well understood. IEEE T&D – Insulators 101

69 Component Damage Limit Defining Damage Limit for ceramics more difficult to define as shown by comparing stress-strain curves for brittle and ductile materials. L&I WG on Insulators is addressing this problem now

70 IEEE T&D – Insulators 101 Insulators 101 Section D – Achieving Quality Presented by Tom Grisham IEEE Task Force Chairman, Insulators 101 IEEE/PES – T&D Conference and Exposition New Orleans, LA April 20, 2010Insulators 101 Section D – Achieving Quality Presented by Tom Grisham IEEE Task Force Chairman, Insulators 101 IEEE/PES – T&D Conference and Exposition New Orleans, LA April 20, 2010

71 IEEE T&D – Insulators 101 Objectives of Quality Presentation Present ideas to verify the supplier qualification, purchasing requirements, manufacturer inspections of lots, shipment approval, material handling, and training information for personnel Routine inspection of the installation Identify steps to analyze field complaints To stimulate Quality improvement

72 IEEE T&D – Insulators 101 Quality Defined QUALITY – An inherent, basic or distinguishing characteristic; an essential property or nature. QUALITY CONTROL – A system of ensuring the proper maintenance of written standards; especially by the random inspection of manufactured goods.

73 IEEE T&D – Insulators 101 What Is Needed in a Quality Plan? Identifying critical design parameters Qualifying new suppliers Evaluating current suppliers Establishing internal specifications Monitoring standards compliance (audits) Understanding installation requirements Establishing end-of-life criteria Ensuring safety of line workers Communicating and training All aspects defined by the company plan

74 IEEE T&D – Insulators 101 What Documents Should Be Included? Catalog specifications and changes Supplier audit records and lot certification Qualification testing of the design Utility-specific testing Additional supplier testing for insulators (vibration, temperature, long-term performance, etc) ANSI or equivalent design reports Storage methods Installation records (where, by whom, why?) Interchangeability with other suppliers product Handling methods (consult manufacturer) Installation requirements and techniques

75 IEEE T&D – Insulators 101 Proven Installation Procedures

76 IEEE T&D – Insulators 101 Handling of Ceramics – NEMA HV2-1984 Insulators should not be dropped or thrown….. Insulators strings should not be bent….. Insulator strings are not ladders….. Insulators with chips or cracks should be discarded and companion units should be carefully inspected….. Cotter keys should be individually inspected for twisting, flattening or indentations. If found, replace keys and retest the insulator….. The maximum combined load, including safety requirements of NESC, must not exceed the rating….. Normal operating temperature range for ceramics is defined as –40 to 150 Degrees F…..

77 IEEE T&D – Insulators 101 Handling of NCIs NEMA is working on a new application guide for NCI products. It will likely include…………………… Insulators should not be dropped, thrown, or bent… Insulators should not be used as ladders… Cotter keys for ball sockets should be inspected identically to the instructions for ceramic insulators… The maximum combined loads should not exceed the RTL… Normal operating temperature is –40 to 150 Degrees F… Insulators should not be used as rope supports… Units with damaged housings that expose the core rod should be replaced and discarded… Units with cut or torn weathersheds should be inspected by the manufacturer… Bending, twisting and cantilever loading should be avoided during construction and maintenance…

78 IEEE T&D – Insulators 101 Line outage Failures Your objective is to find the problem, quickly!

79 IEEE T&D – Insulators 101 Inspection Techniques Subjective: What you already know Outage related Visual methods from the ground Previous problem Thermal camera (NCI – live line) Objective: Answer is not obvious Leakage current measurements Daycor camera for live line inspections (live) Mechanical and electrical evaluations

80 IEEE T&D – Insulators 101 Porcelain and Glass Failures Failures are typically visible or have a new history or upgrade on the site? New products may not be your Grandfathers Oldsmobile, however! Have the insulators deteriorated? Perform thermal-mechanical test before failing load and compare to ultimate failing load Determine current ultimate strength versus new Should the insulators be replaced? Establish internal criteria by location

81 IEEE T&D – Insulators 101 Non-Ceramic (NCI) Failures Cause of failures may NOT be visible! More subjective methods used for live line replacement Some external deterioration may NOT be harmful Visual examples of critical issues are available to you Imperative to involve the supplier! Evaluate your expertise to define root cause condition Verify an effective corrective action is in place Utilize other sources in the utility industry Establish subjective baselines for new installations as future reference! Porcelain and glass, also!

82 IEEE T&D – Insulators 101 What To Do for an Insulator Failure? Inspection of Failure What happened? Extraordinary factors? Save every piece of the unit! Take lots of pictures! Inspect other insulators! Supplier Involvement Verification of production date? Available production records? Determination of root cause? Recommended action? Safety requirements?

83 IEEE T&D – Insulators 101 Summary of Quality Presentation In todays environment, this presentation suggests that the use of a well documented quality program improves long term performance and reduces outages. Application information that is communicated in the organization will help to minimize installation issues and reduce costs. Actively and accurately defining the condition, or determining the root cause of a failure, will assist in determining end-of-life decisions.

84 IEEE T&D – Insulators 101 Source of Presentation http://ewh.ieee.org/soc/pes/iwg/


Download ppt "IEEE T&D – Insulators 101 Insulators 101 Section A – Introduction Presented by Andy Schwalm IEEE Chairman, Lightning and Insulator Subcommittee IEEE/PES."