Presentation is loading. Please wait.

Presentation is loading. Please wait.

Electrical Installation II

Similar presentations


Presentation on theme: "Electrical Installation II"— Presentation transcript:

1 Electrical Installation II
Wiring Enclosures & Support (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004) Chapter 4 Electrical Installation II

2 Protection of cables against Electromechanical & Mechanical Stresses
Electromechanical forces may be caused by fault currents Mechanical forces may be caused by accidental drilling of holes on a wall, the conduits own weight, etc. Electrical Installation II

3 Electrical Installation II
Conduits Rigid Steel Conduits Excellent mechanical protection Good protection against fire Can be used as circuit protective conductor (cpc) Resistant to ultra-violet radiation from sunlight BS classifies conduits by: Light gauge and heavy gauge (CoP permits only heavy gauge conduits) Classes 1, 2, 3 & 4 Electrical Installation II

4 Electrical Installation II
Conduits Rigid Insulating Conduits / PVC conduits Ambient temperature is a major consideration Overall cost saving Separate circuit protective conductor must be used Weight reduction compared with steel conduits Electrical Installation II

5 Electrical Installation II
Conduits Flexible Conduit (Metallic / PVC) Used in applications involving constant movement, e.g. connection to a pump Separate circuit protective conductor must be used Where exposed to damp situation, it should have metallic pattern with PVC oversheath and IP rating not less than IP54 (Table 4.16) Electrical Installation II

6 Electrical Installation II
Conduit Supports: Horizontally surface-mounted Vertically surface-mounted For rigid steel conduit, refer to Table 4.5 For rigid insulating conduit, refer to Table 4.7 Electrical Installation II

7 Electrical Installation II
Conduit Cable capacity - Selection principle: Conduit Factor ≥ ∑ (Cable Factors) Refer to Tables 4.1 to 4.4 Solid and stranded cables Short run (3m and no bend) and long run (>3m or with bends) Adaptable boxes to be installed at least every 10m straight run. Example: How many 2.5 mm2 1-C PVC cables can be accommodated in a 20 mm conduit 10m long incorporating 2 bends? Electrical Installation II

8 Electrical Installation II
Conduit Solution: From Table 4.4, conduit factor for a 20mm conduit, 10m long incorporating 2 bends is 141. Let the max. no. of cables that can be drawn in be x, and from Table 4.3, cable factor for 2.5mm2 1/C PVC cable is 30, then 30x ≤  x ≤ 4.7 Therefore, we select x = 4 Electrical Installation II

9 Electrical Installation II
Trunkings Construction Steel trunking (screw-on-lid) Electrical Installation II

10 Electrical Installation II
Trunkings PVC (or insulating) trunking (clip-on-lid) Electrical Installation II

11 Electrical Installation II
Trunkings There are other trunking systems also of PVC steel construction, e.g. 2- and 3- compartment trunkings (telephone and / or data + power):- Raised floor trunkings (flush with raised floor panels) Underfloor trunkings (flush with floor screed) Skirting trunkings Electrical Installation II

12 Electrical Installation II
Trunkings Classification The higher the Class, the better the mechanical protection, e.g. Class 3 steel trunking  heavy protection on both inside and outside of trunking Electrical Installation II

13 Electrical Installation II
Trunkings Can Be Used as Circuit Protective Conductor (cpc) Steel trunkings may be used as cpc, whereas for PVC trunkings, separate cpc must be used. Electrical Installation II

14 Electrical Installation II
Trunkings Bends and supports Support requirements for steel trunking and insulating trunking refer to Tables 4.13 and 4.15 Electrical Installation II

15 Electrical Installation II
Trunkings Cable Capacity - Selection principle: Trunking Factor ≥ ∑ (Cable Factors) Refer to Tables 4.10, 4.11 and 4.12 For sizes and types of cable and sizes of trunking other than those given in the table, the no. of cables drawn into a trunking should be ≤ 45% Space factor is the percentage occupancy of space inside the trunking Example What is the max. number of 10 mm2 1-C PVC cables that can be accommodated in a 100mm x 50mm trunking? What if a space factor of 0.45 is applied? Electrical Installation II

16 Electrical Installation II
Cable Supports Cable Clips For surface-mounted PVC-insulated PVC-sheathed non-armoured cables  10 mm.sq. Electrical Installation II

17 Electrical Installation II
Cable Supports Cable Cleats / Saddles As above but for > 10 mm.sq. cables and all armoured cables. Electrical Installation II

18 Electrical Installation II
Cable Supports Cable Trays and Ladders Suitable for almost any mounting method but for heavier cables than those accommodated in a trunking. The mechanical strength of cable ladders is better than cable trays. Electrical Installation II


Download ppt "Electrical Installation II"

Similar presentations


Ads by Google